background image

13

13

www.desatech.com

116238-01C

INSTALLATION FOR VERTICAL TERMINATION

Note:

 Vertical restrictor must be installed in all vertical installations.

1.  Determine the route your vertical venting will take. If ceiling 

joists, roof rafters or other framing will obstruct the venting 

system, consider an offset (see Figure 19) to avoid cutting 

load bearing members. 

Note:

 Pay special attention to these 

installation instructions for required clearances (air space) 

to combustibles when passing through ceilings, walls, roofs, 

enclosures, attic rafters, etc. Do not pack air spaces with insu-

lation. Also note maximum vertical rise of the venting system 

and any maximum horizontal offset limitations. 

2.  Set the fireplace in desired location. Drop a plumb line down 

from the ceiling to the position of the fireplace exit flue. Mark 

the center point where the vent will penetrate the ceiling. Drill 

a small locating hole at this point.

 

Drop a plumb line from the inside of the roof to the locating 

hole in the ceiling. Mark the center point where the vent will 

penetrate the roof. Drill a small locating hole at this point.

VENTING INSTALLATION 

INSTRUCTIONS

Continued

Flat Ceiling Installation

1.  Cut a 10 

3

/

4

" square hole in the ceiling using the locating hole as 

a center point. The opening should be framed to 10 

3

/

4

"x10 

3

/

4

(273 mm x 273 mm) inside dimensions, as shown in Figure 9 on 

page 8 using framing lumber the same size as the ceiling joists. 

If the area above the ceiling is an insulated ceiling or a room, 

nail firestop from the top side. This prevents loose insulation 

from falling into the required clearance space. Otherwise, install 

firestop below the framed hole. The firestop should be installed 

with no less than three nails per side (see Figure 20).

Figure 19 - Offset with Wall Strap and 45° Elbows

Figure 20 - Installing Firestop

If area above is not a room, install 

firestop below framed hole.

If area above is a room or 

insulated area, install firestop 

above framed hole.

2.  Assemble the desired lengths of pipe and elbows necessary to 

reach from the fireplace flue up through the firestop. Be sure all 

pipe and elbow connections are fully twist-locked (see Figure 

8, page 8).

3.  Cut a hole in the roof using the locating hole as a center point. 

(Cover any exposed open vent pipes before cutting hole in roof.) 

The 10 

3

/

4

"x10 

3

/

4

" hole must be measured on the horizontal; 

actual length may be larger depending on the pitch of the roof. 

There must be a 1" clearance from the vent pipe to combustible 

materials. Frame the opening as shown in Figure 9, page 8.

4.  Connect a section of pipe and extend up through the hole.
 

Note:

 If an offset is needed to avoid obstructions, you must 

support the vent pipe every 3 feet. Use wall straps for this 

purpose (see Figure 19). Whenever possible, use 45° elbows 

instead of 90° elbows. The 45° elbow offers less restriction to 

the flow of the flue gases and intake air.

5.  Place the flashing over the pipe section(s) extending through 

the roof. Secure the base of the flashing to the roof and framing 

with roofing nails. Be sure roofing material overlaps the top 

edge of the flashing as shown in Figure 19. There must be a 

1" clearance from the vent pipe to combustible materials.

6.  Continue to add pipe sections until the height of the vent cap 

meets the minimum building code requirements described in 

Figure 7 on page 6. 

Note:

 You must increase vent height for 

steep roof pitches. Nearby trees, adjoining rooflines, steep 

pitched roofs and other similar factors may cause poor draft or 

down-drafting in high winds. Increasing the vent height may 

solve this problem.

7.  Twist-lock the vent cap onto the last section of vent pipe.

Note:

 If the vent pipe passes through any occupied areas above the 

first floor, including storage spaces and closets, you must enclose 

pipe. You may frame and sheetrock the enclosure with standard 

construction material. Make sure and meet the minimum allow-

able clearances to combustibles. Do not fill any of the required air 

spaces with insulation.

VENTING INSTALLATION INSTRUCTIONS

Installation for Vertical Termination

45° Elbow

Wall Strap

Roof Flashing

Ceiling Firestop

Summary of Contents for KC36NE Series

Page 1: ...a quali ed installer service agency or the gas supplier This appliance may be installed in an aftermarket permanently located manufactured mo bile home where not prohibited by state or local codes Thi...

Page 2: ...nual carefully and completely before trying to assemble operateor service this replace Improper use of this replace can cause serious injury or death from burns re explosions electrical shock and carb...

Page 3: ...per or other objects 13 Do not use any solid fuels wood coal paper cardboard etc in this replace Use only the gas type indicated on replace nameplate 14 This appliance when installed must be electrica...

Page 4: ...pliance Due to high temperatures do not locate this replace in high traf c areas windy or drafty areas or near furniture or draperies Proper clearances must be maintained If your replace is to be inst...

Page 5: ...replace as a heat source FRAMING AND FINISHING Figure4showstypicalframingofthis replace Figure5showsfram ing for corner installation All minimum clearances must be met For available accessories for th...

Page 6: ...earance above paved side walk or a paved driveway located on public property 84 inches 213 3cm minimum M clearance under veranda porch deck 12 inches 30 5cm minimum N clearance above a roof shall exte...

Page 7: ...wall restops when penetrating walls and restops when penetrating ceilings or attic spaces Install horizontal venting with a 1 4 rise for every 12 of run toward the termination WARNING Read all instru...

Page 8: ...cking lugs indentations These lugs will slide straight into matching slots on the male ends of adjacent pipes Push pipe sections together and twist one section clockwise approxi mately one quarter tur...

Page 9: ...the center of the 10 3 4 square hole and attach to exterior wall with wood screws provided see Figure 11 The siding standoff must sit ush against the exterior fascia material 7 Combustible Exterior W...

Page 10: ...al minimum and maximum dimensions which MUST be met IMPORTANT Rememberthatahorizontalrunofventingmust have a 1 4 rise for every 12 of run toward the termination Figure 13 Typical Horizontal Terminatio...

Page 11: ...sement installation where one foot clearance from ground to termination is possible SNORKEL TERMINATION INSTALLATION Recommended Applications Installations requiring a vertical rise on building exteri...

Page 12: ...tion Planning Cont HORIZONTAL SYSTEM INSTALLATION USING TWO 90 ELBOWS The following con gurations show the minimum vertical rise re quirements for a horizontal system using two 90 elbows Venting with...

Page 13: ...ove framed hole 2 Assemble the desired lengths of pipe and elbows necessary to reach from the replace ue up through the restop Be sure all pipe and elbow connections are fully twist locked see Figure...

Page 14: ...Shown Venting with Two 90 Elbows Vertical V1 Horizontal H 5 min 6 max 6 min 12 max 7 min 18 max 8 min 20 max Note Vertical V1 Vertical V2 40 max Figure23 VerticalVentingCon gurationUsingTwo90 Elbows V...

Page 15: ...with your local gas company for proper ori ce size identi cation When installing this replace at an elevation above 4500 feet in Canada check with local authorities Consult your localgas companyto hel...

Page 16: ...Components FIREPLACE INSTALLATION Check Gas Type Installing Optional Blower Accessory PARTS LIST FOR VENTING KITS AND COMPONENTS DESA 5 8 Pipe Vent Kits Number Description P58 6 6 Section Double Wall...

Page 17: ...LACE INSTALLATION Continued Speed Control Control Shaft Locknut Control Knob Switch Bracket Blower Plug In Duplex Outlet Located underneath rebox oor against lower right outside wall Thermodisc Figure...

Page 18: ...lator with Vent Pointing Down Propane LP Only Propane LP Supply Tank External Regulator Vent Pointing Down 5 Mount the speed control box against the mounting plate provided in the lower replace cavity...

Page 19: ...s for turning on or shutting off the gas to the appliance Checkyourbuildingcodesforanyspecialrequirementsforlocating equipment shutoff valve to replaces Apply pipe joint sealant lightly to male NPT th...

Page 20: ...d on or near gas meter for natural gas replace 3 Make sure control knob of replace is in the OFF position 4 Check all joints from equipment shutoff valve to gas valve see Figure 34 for propane LP or F...

Page 21: ...leaning Glass Door See Cleaning and Maintenance on page 25 Lock Unlock Glass Frame Assembly Screw Hinge Latch INSTALLING LAVA ROCK AND GLOWING EMBERS It is very important to keep logs exactly as insta...

Page 22: ...39 Installing Rear Brick Panel Rear Brick Panel Left Side Brick Panel INSTALLING BRICK LINER MODELS BL36DA SA AND BL36DHA SA WARNING If replace has been running turn off and unplug replace Let cool b...

Page 23: ...he wall switch to the ON position 11 Visuallylocatethepilot Theignitorshouldbegintosparkand the main burner should ignite once ame appears at pilot If lighting the appliance for the rst time each seas...

Page 24: ...te control for the replace your replace and blower will not turn on and off at the same time The replacemayrunforseveralminutesbeforetheblower turns on After the heater modulates to the pilot position...

Page 25: ...rom glass If glass has been broken carefully remove glass door see Remov ing Replacing Glass Door page 20 Vacuum all glass pieces with a shop vac CAUTION Do not vacuum if pieces are hot Use only the t...

Page 26: ...all air out of lines If after re peated attempts appliance does not light call for quali ed service and repair 3 Remove debris and dirt inspect and clean any other possible obstructions 4 Contact your...

Page 27: ...just after burner is lit or shut off Slight smoke or odor during initial operation Gas odor even when control knob is in OFF position Gas odor during combustion Glass soots Dark residue on logs or ins...

Page 28: ...TS Note Use only original replacement parts This will protect your warranty coverage for parts replaced under warranty PARTS UNDER WARRANTY Contact authorized retailers of this product If they can not...

Page 29: ...let Supply Pressure 5 5 w c 11 0 w c Dimension Inches mm HxWxD Fireplace Actual size of rebox Measurements do not 36 x 41 x 21 1 8 36 x 41 x 21 1 8 include nailing anges or 914 x 1041 x 537 mm 914 x 1...

Page 30: ...h com 116238 01C ILLUSTRATED PARTS BREAKDOWN Models KC36NE VKC36NE KC36PE VKC36PE ILLUSTRATED PARTS BREAKDOWN MODELS KC36NE VKC36NE KC36PE AND VKC36PE 6 7 20 17 18 13 2 12 19 8 1 4 11 9 14 3 16 5 15 1...

Page 31: ...ctory Brick Panel 1 12 see below see below Rear Refractory Brick Panel 1 13 see below see below Right Refractory Brick Panel 1 14 108719 01 108719 01 Screen Rod 1 15 12105 12105 Screen 2 16 11418 1141...

Page 32: ...2 2 3 13 9 11 6 12 14 18 17 17 18 19 20 16 14 8 4 5 22 23 24 21 31 33 32 30 29 28 25 27 26 ILLUSTRATED PARTS BREAKDOWN Models KC36NE VKC36NE KC36PE VKC36PE ILLUSTRATED PARTS BREAKDOWN BURNER ASSEMBLY...

Page 33: ...l 1 108866 02 Elec Pilot Assembly Propane LP 1 11 14569 Elec Valve Assembly Natural 1 14570 Elec Valve Assembly Propane LP 1 12 11165 Screw 10 x 5 8 Zinc 1 13 111913 01 Burner Base Gasket 1 14 14396 B...

Page 34: ...L36DSA Standard Refractory Brick Liner Kit BL36DHA Textured Refractory Herringbone Brick Liner Kit BL36DHSA Standard Refractory Herringbone Brick Liner Kit Thisbricklineraddsatouchofstyletoyourdirect...

Page 35: ...te School 13 Age of Purchaser Under 20 20 29 30 39 40 49 50 59 60 or Over 14 Buyer s total annual household income Under 15 000 15 000 to 19 999 20 000 to 34 999 35 000 to 49 999 50 000 to 74 999 75 0...

Page 36: ...36 www desatech com 116238 01C 2701 Industrial Drive P O Box 90004 Bowling Green KY 42102 9004 Postage Required TAPE TAPE...

Page 37: ...______________________ ________________________________________________________________________________________________ ________________________________________________________________________________...

Page 38: ...and all such other costs related to repairing a defective heater will be the responsibility of the owner TO THE FULL EXTENT ALLOWED BY THE LAW OF THE JURISDICTION THAT GOVERNS THE SALE OF THE PRODUCT...

Reviews: