background image

www.desatech.com

122493-01C

7

1.  Determine the volume of the space (length 

x width x height).

 

Length x Width x Height =__________cu. ft. 
(volume of space)

 

Example:

 Space size 20 ft. (length) x 16 ft. 

(width) x 8 ft. (ceiling height) = 2,560 cu. ft. 

(volume of space)

 

If  additional  ventilation  to  adjoining  room 

is supplied with grills or openings, add the 

volume of these rooms to the total volume 
of the space. 

2.  Multiply the space volume by 20 to determine 

the maximum Btu/Hr the space can support.

 

  ________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)

 

Example:

  2,560  cu.  ft.  (volume  of  space)  x 

20 = 51,200 (maximum Btu/Hr the space can 

support)

3.  Add the Btu/Hr of all fuel burning appliances 

in the space.

 

Vent-free fireplace 

 

 __________ Btu/Hr

 

Gas water heater* 

 

 __________ Btu/Hr

 

Gas furnace 

   __________ Btu/Hr

 

Vented gas heater 

   __________ Btu/Hr

 

Gas fireplace logs 

 

 __________ Btu/Hr

 

Other gas appliances* +  __________ Btu/Hr

 

Total 

=  __________ Btu/Hr

 

* Do not include direct-vent gas appliances. 

Direct-vent  draws  combustion  air  from  the 

outdoors and vents to the outdoors.

 

Example:

 

 

Gas water heater 

 

 __________ Btu/Hr

 

Vent-free fireplace 

 __________ Btu/Hr

 

Total 

=  __________ Btu/Hr

4.  Compare  the  maximum  Btu/Hr  the  space 

can support with the actual amount of Btu/Hr 

used.

 

  _______ Btu/Hr  (maximum  the  space  can 
support) 

 

  _______ Btu/Hr (actual amount of Btu/Hr 
used)

 

Example:

  51,200  Btu/Hr  (maximum  the 

space can support) 

 

 

71,500 Btu/Hr (actual amount of 

Btu/Hr used)

The space in the example is a confined space 

because the actual Btu/Hr used is more than the 

maximum  Btu/Hr  the  space  can  support.  You 
must  provide  additional  fresh  air. Your  options 
are as follows:
A.  Rework worksheet, adding the space of an 

adjoining room. If the extra space provides an 

unconfined space, remove door to adjoining 

40,000
31,500
71,500

AIR FOR COMbUSTION AND VENTILATION

Continued

Figure 2 - Ventilation Air from Inside Building

Or 

Remove 

Door into 
Adjoining 

Room, 
Option 

Ventilation Grills  

Into Adjoining Room, 

Option 2 

Ventilation

Grills Into

Adjoining 

Room,

Option 1

12" 

12" 

room or add ventilation grills between rooms. 

See 

Ventilation Air From Inside Building

.

B.  Vent  room  directly  to  the  outdoors.  See 

Ventilation Air From Outdoors

, page 8.

C.  Install a lower Btu/Hr fireplace, if lower Btu/Hr 

size makes room unconfined. 

If the actual Btu/Hr used is less than the maxi-

mum Btu/Hr the space can support, the space is 
an unconfined space. You will need no additional 

fresh air ventilation.

 WARNING: If the area in which 

the heater may be operated does 

not meet the required volume for 

indoor combustion air, combus-

tion and ventilation air shall be 

provided by one of the methods 

described  in  the 

National  Fuel 

Gas Code, ANSI Z223.1/NFPA 54

the 

International Fuel Gas Code

or applicable local codes.

VENTILATION AIR

Ventilation Air From Inside Building 

This fresh air would come from an adjoining 

unconfined  space.  When  ventilating  to  an 

adjoining unconfined space, you must provide 
two permanent openings: one within 12" of the 
ceiling and one within 12" of the floor on the 
wall connecting the two spaces (see options 1 
and 2, Figure 2). You can also remove door into 
adjoining room (see option 3, Figure 2). Fol

-

low the 

National Fuel Gas Code ANSI Z223.1/

NFPA 54 Air for Combustion and Ventilation

 for 

required size of ventilation grills or ducts.

Summary of Contents for HDL18N

Page 1: ...cal switch do not use any phone in your building Immediatelycallyourgassupplierfromaneighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire departme...

Page 2: ...vented gas fired heat er It uses air oxygen from the room in which it is installed Provisions for adequate combustion and ventilation air must be provided Refer to Air for Combustion and Ven tilation...

Page 3: ...nt even though no odor exists Make certain you read and understand all warnings Keep this manual for reference It is your guide to safe and proper operation of this fireplace WARNING Any change to thi...

Page 4: ...l operation slight smok ing could occur due to log curing and heater burning manufacturing residues 10 To prevent the creation of soot follow the instructions in Cleaning and Maintenance page 19 11 Be...

Page 5: ...s sembly The data plates contain important warranty and safety information 1 Remove logs and heater base assembly from carton Note Do not pick up heater base assem bly by burners This could damage hea...

Page 6: ...ight construction you must provide additional fresh air Unusually tight construction is defined as construction where a walls and ceilings exposed to the out side atmosphere have a continuous water va...

Page 7: ...an the maximum Btu Hr the space can support You must provide additional fresh air Your options are as follows A Rework worksheet adding the space of an adjoining room If the extra space provides an un...

Page 8: ...ation for required size of ventilation grills or ducts IMPORTANT Do not provide openings for inlet or outlet air into attic if attic has a thermo stat controlled power vent Heated air entering the att...

Page 9: ...RANCE TO COMBUSTIBLE MATERIALS Side Wall 16 Ceiling 42 Front 36 Carefully follow the instructions below This will ensure safe installation into a masonry UL127 listed manufactured fireplace or certi f...

Page 10: ...is not required see Figure 6 Figure 6 Minimum Mantel Clearances Without Using Hood Determining Minimum Mantel Clearance when Using a Hood If minimum clearances in Figure 6 are not met you must have a...

Page 11: ...to combustibles see Figure 8 B If combustible materials are less than 14 to the fireplace you must install appliance at least 5 above the combustible flooring see Figure 9 INSTALLING DAMPER CLAMP ACC...

Page 12: ...eater control panel This will in sure adequate air flow and guard against sooting and controls be ingdamaged Raisefireplacefloor with noncombustible material Make sure material is secure CAUTION Do no...

Page 13: ...lregu lator not supplied Install the external regulator between the heater and propane LP supply WARNING For natural gas units never connect heater to private non utility gas wells This gas is commonl...

Page 14: ...ible Gas Hose if allowed by local codes Natural From Gas Meter 5 W C to 10 5 W C Pressure Propane LP From External Regulator 11 W C to 14 W C Pressure We recommend that you install sediment trap in su...

Page 15: ...m by either opening propane LP supply tank valve for propane LP gas or opening main gas valve located on or near gas meter for natural gas or using compressed air 3 Check all joints from gas meter nat...

Page 16: ...will fit over burner see Figure 18 Holes in bottom of log must seat over pins on base as shown in Figure 18 Make sure back of log as Figure 18 Installing Main Log 1 Back Tab Burner Front Tab Notch for...

Page 17: ...to replace any part of the control system and any gas control which has been under water LIGHTING INSTRUCTIONS WARNING If fireplace has glass doors never operate this heater with glass doors closed If...

Page 18: ...tern Pilot Burner Thermocouple Pilot Burner Thermocouple Inspecting Burners Check pilot flame pattern and burner flame patterns often PILOT FLAME PATTERN Figure 22 shows a correct pilot flame pattern...

Page 19: ...to excessive lint from carpeting bedding material pet hair etc WARNING Failure to keep the primary air opening s of theburner s cleanmayresultin sooting and property damage Once every year a qualifie...

Page 20: ...ile in PILOT position 4 Air in gas lines when in stalled 5 Depleted gas supply pro pane LP only 6 ODS pilot is clogged 7 Gas regulator setting is not correct OBSERVED PROBLEM When control knob is pres...

Page 21: ...or propane LP gas company 1 Contact local natural or propane LP gas company 2 Clean burner see Cleaning and Maintenance page 19 or replace burner orifice 1 Clean burner see Cleaning and Maintenance pa...

Page 22: ...burner until air is removed from line Have gas line checked by local natural or propane LP gas company 3 Observe minimum instal lation clearances see page 9 4 Clean burner see Cleaning and Maintenance...

Page 23: ...see Checking Gas Con nections page 14 1 Open window and or door for ventilation 2 Contact local natural or propane LP gas company 3 Clean ODS pilot see Cleaning and Maintenance page 19 1 Locate and c...

Page 24: ...www desatech com 122493 01C 24 Parts MODELS hdl18 n p vdb18 n p 1 18 19 2 16 4 15 15 8 9 11 21 5 12 3 10 17b 17c 17a 14 7 6...

Page 25: ...Burner Inlet Tube 1 9 108188 02 Screw Type U Drive 2 x 0 75 1 10 108134 01 NG Plate 1 11 099056 26 Injector 1 099056 19 Injector 1 12 099387 08 Pilot Tube 1 13 098249 01 ODS Nut 2 14 M11084 38 Screw H...

Page 26: ...eating LLC have ready model number of your heater the replacement part number Technical Service You may have further questions about instal lation operation or troubleshooting If so con tact DESA Heat...

Page 27: ...n Street Kansas City MO 64108 KS MO AR 816 842 3911 www washerparts com East Coast Energy Products 10 East Route 36 W Long Branch NJ 07764 732 870 8809 1 800 755 8809 www njplaza com ecep 21st Century...

Page 28: ...proved by DESA Heating LLC Warranty parts must be obtained through authorized dealers of this prod uct and or DESA Heating LLC who will provide original factory replacement parts Failure to use origin...

Reviews: