background image

www.desatech.com

5

107902-01L

AIR FOR COMbUSTION 

AND VENTILATION

 WARNING: This heater shall 

not  be  installed  in  a  confined 

space  or  unusually  tight  con

-

struction unless provisions are 

provided for adequate combus

-

tion and ventilation air. Read the 

following instructions to insure 

proper  fresh  air  for  this  and 

other  fuel-burning  appliances 

in your home.

Today’s homes are built more energy efficient 
than ever. New materials, increased insulation 
and new construction methods help reduce 
heat  loss  in  homes.  Home  owners  weather 
strip  and  caulk  around  windows  and  doors 
to keep the cold air out and the warm air in. 
During  heating  months,  home  owners  want 
their homes as airtight as possible.
While it is good to make your home energy 
efficient, your home needs to breathe. Fresh 
air must enter your home. All fuel-burning ap-
pliances need fresh air for proper combustion 
and ventilation.
Exhaust  fans,  fireplaces,  clothes  dryers  and 
fuel burning appliances draw air from the house 
to operate. You must provide adequate fresh 
air for these appliances. This will insure proper 
venting of vented fuel-burning appliances.

PROvIDING ADEQUATE 
vENTILATION

The following are excerpts from 

National Fuel 

Gas  Code, ANSI  Z223.1/NFPA  54,  Section 
5.3, Air for Combustion and Ventilation.

All spaces in homes fall into one of the three 
following ventilation classifications:
1.  Unusually Tight Construction
2.  Unconfined Space
3.  Confined Space
The information on pages 5 through 7 will help 
you classify your space and provide adequate 
ventilation.

Unusually Tight Construction

The air that leaks around doors and windows 
may provide enough fresh air for combustion 
and ventilation. However, in buildings of un-
usually tight construction, you must provide 
additional fresh air.
Unusually  tight  construction  is  defined  as 
construction where:
a.  walls and ceilings exposed to the outside 

atmosphere  have  a  continuous  water 
vapor retarder with a rating of one perm 
(6 x 10

-11

 kg per pa-sec-m

2

) or less with 

openings gasketed or sealed and

b.  weather  stripping  has  been  added  on 

openable windows and doors and

c.  caulking or sealants are applied to areas 

such  as  joints  around  window  and  door 
frames,  between  sole  plates  and  floors, 
between  wall-ceiling  joints,  between  wall 
panels, at penetrations for plumbing, electri-
cal and gas lines and at other openings.

If your home meets all of these three criteria, 
you  must  provide  additional  fresh  air.  See 

Ventilation Air From Outdoors

, page 7.

If your home does not meet all of the three 
criteria above, proceed to 

Determining Fresh-

Air Flow For Heater Location

, page 6.

Confined and Unconfined Space

The National Fuel Gas Code, ANSI Z223.1/
NFPA 54

 defines a confined space as a space 

whose volume is less than 50 cubic feet per 
1,000 Btu/hr (4.8 m

3

 per kw) of the aggregate 

input rating of all appliances installed in that 
space and an unconfined space as a space 
whose volume is not less than 50 cubic feet 
per 1,000 Btu/hr (4.8 m

3

 per kw) of the ag-

gregate input rating of all appliances installed 
in that space. Rooms communicating directly 
with  the  space  in  which  the  appliances  are 
installed*,  through  openings  not  furnished 
with doors, are considered a part of the un-
confined space.
* Adjoining rooms are communicating only if 
there are doorless passageways or ventilation 
grills between them.

Summary of Contents for GWRN10

Page 1: ...apors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building...

Page 2: ...to the State of California to cause cancer or birth defects or other reproductive harm IMPORTANT Read this owner s manualcarefullyandcompletely before trying to assemble operate or service this heater...

Page 3: ...other gases 2 Do not place propane LP supply tank s inside any structure Locate propane LP supply tank s outdoors 3 Do not install in a bathroom 4 If you smell gas Shut off gas supply Do not try to li...

Page 4: ...gas fired supplemental room heaters shall provide to each purchaser a copy of 527 CMR 30 upon sale of the unit Vent free gas products are prohibited for bedroom and bathroom installation in the Commo...

Page 5: ...on The air that leaks around doors and windows may provide enough fresh air for combustion and ventilation However in buildings of un usually tight construction you must provide additional fresh air U...

Page 6: ...Btu Hr actual amount used AIR FOR COMBUSTION AND VENTILATION Continued 50 000 10 000 60 000 Example 51 200 Btu Hr maximum the space can support 60 000 Btu Hr actual amount of Btu Hr used The space in...

Page 7: ...event of a power outage you can use this heater as your primary heat source WARNING A qualified ser vice person must install heater Follow all local codes CHECK GAS TYPE Use only the correct type of g...

Page 8: ...odors IMPORTANT Vent free heaters add moisture to the air Although this is beneficial installing heater in rooms without enough ventilation air may cause mildew to form from too much moisture See Air...

Page 9: ...thin walls 1 2 or less insert red key into wall anchor Push red key to pop open anchor wings see Figure 7 IMPORTANT Do not hammer key For thick walls over 1 2 thick or solid walls do not pop open win...

Page 10: ...ot replace front panel at this time Replace front panel after making gas connections and checking for leaks see pages 10 through 12 IMPORTANT For natural gas check gas line pressure before connecting...

Page 11: ...Piping System Test Pressures In Excess Of 1 2 PSIG 14 WC 1 Disconnect appliance with its appliance main gas valve control valve and equip ment shutoff valve from gas supply piping system Pressures in...

Page 12: ...n D Do not use this appliance if any part has been under water Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas contro...

Page 13: ...ade light pilot with match To light pilot with match see Manual Lighting Procedure page 14 8 Keep control knob pressed in for 30 sec onds after lighting pilot After 30 seconds release control knob If...

Page 14: ...Figure 23 turn heater off see To Turn Off Gas to Ap pliance see Cleaning page 15 Thermocouple Pilot Burner Pilot Burner Thermocouple Blue Flame Yellow Flame Figure 20 Correct Pilot Flame Pattern Figur...

Page 15: ...SI Your local computer store hardware store or home center may carry compressed air in a can If using compressed air in a can please follow the directions on the can If you don t follow directions on...

Page 16: ...as lines when in stalled 5 Depleted gas supply pro pane LP only 6 ODS pilot is clogged 7 Gas regulator setting is not correct REMEDY 1 Replace pilot assembly 2 Replace pilot assembly 3 Reconnect ignit...

Page 17: ...nob fully 2 After ODS pilot lights keep control knob pressed in 30 seconds 3 Fully open equipment shut off valve 4 Hand tighten until snug then tighten 1 4 turn more 5 A Contact local natural or propa...

Page 18: ...gas regulator 1 Problem will stop after a few hours of operation 1 Turn control knob to lowest position and let warm up for a minute 2 Operate burner until air is removed from line Have gas checked by...

Page 19: ...15 1 Locate and correct all leaks see Checking Gas Con nections page 11 2 Replace control valve 1 Take apart gas tubing and remove foreign matter 2 Locate and correct all leaks see Checking Gas Con n...

Page 20: ...www desatech com 107902 01L 20 17 16 15 14 13 12 9 11 8 8 10 6 7 5 4 3 2 1 18 19 23 20 A B Parts Models GWRP10 and GWRN10 7 2 7 1 ODS PILOT...

Page 21: ...Burner Assembly 1 8 099056 01 Injector 2 099056 06 Injector 2 9 099390 02 Tubing Valve to Plaque A 1 10 099387 17 Pilot Tubing Valve to Pilot 1 11 099392 01 Tubing Valve to Plaque B 1 12 099391 02 Tu...

Page 22: ...del and serial numbers of your heater ready You can also visit DESAHeating Products tech nical service web site at www desatech com Service Publications You can purchase a service manual from the addr...

Page 23: ...ms Street Bowling Green KY 42103 3414 270 846 1199 1 800 654 8534 Fax 1 800 846 0090 franktalk aol com Master Parts Dist 1251 Mound Ave NW Grand Rapids MI 49504 2672 616 791 0505 1 800 446 1446 www nb...

Page 24: ...arts voids this warranty The heater MUST be installed by a qualified installer in accordance with all local codes and instructions furnished with the unit This warranty does not apply to parts that ar...

Page 25: ...ca de este aparato ni de cualquier otro QU HACER SI PERCIBE OLOR A GAS No intente encender ning n aparato No toque ning n interruptor el ctrico no use ning n tel fono en el edificio Llame inmediatamen...

Page 26: ...asa m vil con ubicaci n permanente y adquirida en el mercado de posventa siempre que no est prohibido por los c digos locales Mercado de posventa venta completada por parte del fabricante sin fines de...

Page 27: ...ca del mismo Nunca coloque nin g n objeto sobre el calentador Lasuperficiedelcalentadoralcan zatemperaturasmuyaltascuando steest funcionando Mantengaa los ni os y a los adultos alejados de las superfi...

Page 28: ...a 2 Retire todo el empaque de protecci n que se agreg al calentador para su env o 3 Revise el calentador para ver si hay alg n da o debido al transporte Si el calentador est da ado devu lvalo de inmed...

Page 29: ...asificar su espacio y a proporcionar la ventilaci n adecuada Construcci n inusualmente sellada El aire que se filtra por los bordes de las puer tas y ventanas puede proporcionar suficiente aire fresco...

Page 30: ...ble ANSI Z223 1 NFPA 54 secci n 5 3 Aire para combusti n y ventilaci n para conocer el tama o requerido de las rejillas o conductos de ventilaci n DETERMINACI N DEL FLUJO DE AIRE FRESCO PARA UBICAR EL...

Page 31: ...tadorcomo fuente de calefacci n principal Si tiene un sistema de calefacci n central puede activar el ventilador de circulaci n del sistema mientras utiliza el calentador Esto ayudar a queelcalorcircu...

Page 32: ...aceite o queroseno entre otros puede decolorar las paredes o producir olores IMPORTANTE los calentadores sin ventilaci n a aden humedad al aire Aunque esto es ben fico la instalaci n del calentador e...

Page 33: ...ndo una broca de 5 16 Para las paredes s lidas de concreto o mampos ter a perfore a una profundidad de por lo menos 3 2 cm 1 1 4 2 Doble el anclaje de pared consulte la figura 6 3 Inserte el anclaje d...

Page 34: ...ional de 3 8 al regulador de presi n ADVERTENCIA una per sona de servicio capacitada debe conectar el calentador al suministro de gas Siga todos los c digos locales Instalaci n Continuaci n Colocaci n...

Page 35: ...o o de acero En ciertas reas se puede usar tuber a de cobre galvanizada internamen te Consultelosc digoslocales Utilice tuber a de un di metro lo suficientemente grande para permitir el paso del volum...

Page 36: ...o en todas las uniones La formaci n de burbujas indicar unafuga Reparetodaslasfugas inmediatamente PRECAUCI N para propa no o gas LP aseg rese de que el regulador externo se haya instalado entre el su...

Page 37: ...de gas si usa gas natural consulte la figura 15 o entre el tanque de suminis tro de propano o gas LP si usa este tipo de gas y la v lvula de cierre del equipo consulte la figura 16 Aplique en todas l...

Page 38: ...oro consulte el Procedimiento para encendido manual en la p gina 16 8 Una vez que haya encendido el piloto mantenga la perilla de control presionada durante 30 segundos Despu s de los 30 segundos suel...

Page 39: ...ea el manual del propietario para obtener las instrucciones completas PRECAUCI N no intente ajustar los niveles de calefac ci n por medio de la v lvula de cierre del equipo Termopar Quemador del pilot...

Page 40: ...ulte Limpieza en la p gina 17 Termopar Quemador del piloto Quemador del piloto Termopar Llama azul Llama amarilla Figura 20 Patr n correcto de la llama del piloto Figura 21 Patr n incorrecto de la lla...

Page 41: ...que la tienda local de equipo de c mputo ferreter a o de mejoras al hogar tengan aire comprimido en latas Si utiliza aire comprimido en lata siga las instrucciones que aparecen en la misma Si no sigue...

Page 42: ...s cuando se instalaron 5 Se agot el suministro de gas propano o gas LP ni camente 6 El piloto con ODS est tapado 7 La posici n del regulador de gas no es la correcta REMEDIO 1 Reemplace el conjunto de...

Page 43: ...enda manten ga la perilla de control presio nada durante 30 segundos 3 Abra la v lvula de cierre del equipo totalmente 4 Apriete con la mano hasta que sienta que topa luego apriete 1 4 de vuelta m s 5...

Page 44: ...gina 17 2 Comun quese con la com pa a local de gas natural o de propano o gas LP 3 Reemplace el regulador de gas 1 El problema desaparecer despu s de algunas horas de funcionamiento 1 Gire la perilla...

Page 45: ...con sulte Limpieza p gina 17 1 Localice y repare todas las fugas consulte Revisi n de las conexiones de gas en la p gina 12 2 Reemplace la v lvula de control 1 Desensamble la tuber a de gas y extraig...

Page 46: ...www desatech com 107902 01L 22 Piloto con ODS 17 16 15 14 13 12 9 11 8 8 10 6 7 5 4 3 2 1 18 19 23 20 A B Piezas Modelos GWRP10 y GWRN10 7 2 7 1...

Page 47: ...8 099056 01 Inyector 2 099056 06 Inyector 2 9 099390 02 Tuber a v lvula a placa A 1 10 099387 17 Tubo de piloto v lvula a piloto 1 11 099392 01 Tuber a v lvula a placa A 1 12 099391 02 Tuber a regulad...

Page 48: ...repuesto originales Esto proteger la cobertura de su garant a para partes reemplazadas con garant a Piezas con garant a P ngase en contacto con los distribuidores autorizados de este producto Si no p...

Page 49: ...Bowling Green KY 42103 3414 EE UU 270 846 1199 1 800 654 8534 Fax 1 800 846 0090 franktalk aol com Master Parts Dist 1251 Mound Ave NW Grand Rapids MI 49504 2672 EE UU 616 791 0505 1 800 446 1446 www...

Page 50: ..._____________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ _____...

Page 51: ..._____________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ _____...

Page 52: ...nstalador capacitado DEBE haber instalado el calentador de acuerdo con todos los c digos locales e instrucciones incluidas con la unidad Esta garant a no se aplica a las piezas que no est n en su cond...

Reviews: