background image

6

201839

DIRECT-VENT PROPANE/LP GAS HEATER

DYNAVENT

®

6.

Attach thermostat to thermostat mount-
ing plate with screws provided (see Fig-
ure 4). 

IMPORTANT:

 Note mounting

plate position in Figure 4. Correctly
position mounting plate for your model
furnace.

7.

Insert thermostat mounting plate be-
tween wall and cabinet flange. Line up
top notch on mounting plate with top
screw on flange (see Figure 5).

IMPORTANT:

 Thermostat for 25,000

BTU/Hr model mounts on right side of
furnace (see Figure 5). Thermostat for
40,000 BTU/Hr model mounts on left
side of furnace (see Figure 5).

8.

Insert screw in cabinet flange and ther-
mostat mounting plate and tighten firmly.

IMPORTANT:

  Make sure thermostat

wires do not touch combustion chamber.

INSTALLATION

(Continued)

.2

.3

.4

.5

.7

1.

0

SOLID STATE       IGNITION

50   60   70   80   90

50   60   70   80   90

OFF

40,000 BTU/Hr Models

00000000000         00000000

00

   0

0   00

   00

   00

00   00   00   00   00

SO

LID

 S

TA

TE

       IG

NIT

IO

N

50   60   70   80   90

50   60   70   80   90

25,000 BTU/Hr Models

40,000 BTU/Hr Models

Figure 5 - Inserting Thermostat Mounting
Plate Between Wall and Cabinet Flange

Figure 4 - Attaching Thermostat to
Thermostat Mounting Plate

.2

.3

.4

.5

.7

1.

0

SOLID STATE       IGNITION

50   60   70   80   90

50   60   70   80   90

OFF

25,000 BTU/Hr Models

Locating Thermostat on Wall

1.

Locate thermostat 4 

1

/

2

 to 5 feet above

the floor on an inside wall away from
any heat sources. The thermostat needs
to sense average room temperature.
Avoid the following:

HOT SPOTS

Concealed pipes or ducts
Fireplaces
Registers
TV sets and radios
Lamps or direct sunlight
Kitchen

COLD SPOTS

Concealed pipes or ducts
Stairwells (drafts) or doors (drafts)
Unheated rooms on other side of wall

DEAD SPOTS

Behind doors
Corners and alcoves

2.

Before installing thermostat, inspect the
wall, floor, and attic areas. Make sure
there are no pipes, wiring, or anything
else that would interfere with install-
ing thermostat. Do not mount thermo-
stat to stud. If there are any obstruc-
tions, choose a new location.

3.

Provide two 18-gauge insulated stranded
wires for the thermostat wire. Also pro-
vide two wire nuts, and two wall anchors.
There is a red and a white thermostat wire
coming from the furnace. The extra ther-
mostat wires you furnish attach to these
wires. Make sure you furnish a red and a
white wire. This will insure correct
hookup. Purchase enough thermostat wire
to go from the furnace to the thermostat
location. Do not cut and splice this wire.
The thermostat wire must be unbroken.

Routing Thermostat Cable

All wiring must meet local codes. The fol-
lowing instructions cover routing the wire
through the attic. You can run wiring from
a basement or crawl space.

1.

Unplug furnace.

2.

Before drilling hole in wall, drive a small
finishing nail through ceiling directly
above thermostat location. Pull nail out
and push a small stiff wire through hole.
This helps you locate thermostat mount-
ing location when in attic.

3.

In attic, locate stiff wire. Drill 1/2" hole
in center of ceiling wall plate next to
stiff wire. Remove wire.

4.

Probe through drilled hole in wall plate
with a stiff wire to make sure there are
no pipes, wiring, or anything else
blocking the way for thermostat wires.
If you find blockage, choose new loca-
tion for thermostat.

5.

Drill a 1/2" hole through the wall at
thermostat mounting location.

6.

From attic, feed thermostat wires
through hole in ceiling plate until wires
reach thermostat location.

7.

Make a small hook with a piece of stiff
wire. Run wire hook through 1/2" hole
in wall. Hook thermostat wires. Pull
wires through hole in wall. Make sure
6" of wires stick out.

8.

Drive a small finishing nail in ceiling
above furnace.

25,000 BTU/Hr Model

 - Drive nail

above right side of furnace.

40,000 BTU/Hr Model

 - Drive nail

above left side of furnace.
Pull nail out and push a small stiff wire
through hole. This helps you locate wire
routing location when in attic.

9.

Repeat steps 3 and 4 above.

Summary of Contents for DYNAVENT DNV25PB

Page 1: ...NING Improperin stallation adjustment alteration service or maintenance can cause injury or property dam age Refertothismanual for correct installation and operational proce dures Forassistanceor addi...

Page 2: ...LP gas is odor less An odor making agent is added to pro pane LP gas The odor helps you detect a propane LPgasleak However theodoradded to propane LP gas can fade Propane LP gas may be present even t...

Page 3: ...For purposes of input adjustment SPECIFICATIONS Install and use furnace with care Follow all localcodes Intheabsenceoflocalcodes use the latest edition of the following National Fuel Gas Code ANS Z223...

Page 4: ...installing thermostat in a wall make sure there are no pipes or wiring in the hollow wallabovethefurnace Thethermostatwires will pass through this wall from the attic Mounting hardware needed to moun...

Page 5: ...000 BTU Hr Model Use a proper sized drill bit Drill holes through wall and into studs at marked locations 40 000 BTU Hr Model Use a proper sized drill bit On wall stud side of opening drill holes thro...

Page 6: ...else that would interfere with install ing thermostat Do not mount thermo stat to stud If there are any obstruc tions choose a new location 3 Provide two 18 gauge insulated stranded wires for the the...

Page 7: ...t Wires to Thermostat Wall Anchors CAUTION Use only new black iron or steel pipe Copper tubing may be acceptable in cer tain areas Check local codes Use pipe large enough in diam eter to allow proper...

Page 8: ...de furnace back into furnace cabi net Make sure exhaust tube gaskets are in place Make sure exhaust and intake vent tubes extend into vent caps on back of cabinet Replace two screws by exhaust vent s...

Page 9: ...0 BTU Hr 15 000 BTU Hr for other gas appliances 55 000 BTU Hr total 55 000 2500 22 Locate 22 or higher on chart below According to the chart below you should use 40 feet or less of 3 8 pipe 125 feet o...

Page 10: ...5 CAUTION Usepipejointseal ant that is resistant to liquid pe troleum LP gas Slab Floor Installation Equipment Shutoff Valve Test Gauge Connection To Gas Supply 3 Min Sediment Trap Gas Piping Entering...

Page 11: ...0 cycle grounded outlet at furnace location 2 The furnace has a three pronged grounded plug Use only a grounded three prong outlet IMPORTANT Some local codes require rigid or semi rigid conduit or met...

Page 12: ...Do not try to light the burner by hand 8 Plug in furnace 9 Set thermostat to desired setting If thermostat is set above room tem perature the blower will come on 10 Allow approximately 45 seconds for...

Page 13: ...forces the combus tion products out of the exhaust tube s The Combustion air blower is sealed so that air does not pass between it and the circulating room air blower 3 When the blower motor reaches...

Page 14: ...r mixture Wipe cabinet and front cover to remove dust Use a vacuum cleaner to remove dust from front cover louvers EXHAUST AND INTAKE VENTS Make sure the exhaust and intake vents are not blocked The i...

Page 15: ...okay check for defective motor 5 Be sure the microswitch is sailing in far enough to open the solenoid valve and to energize the ignition control If the switch is not sailing in clean any dust or dir...

Page 16: ...t it WARNINGS Never connect unit or ignition circuit to 230 volts Never operate unit with glo bar touching burner or any other ground Damage to ignition control will occur Be sure sensor probe never t...

Page 17: ...bar broken 2 A Check for voltage 24 volts A C at valve 40 seconds after glo bar begins to glow If voltage present but valve not opening replace valve B If no voltage at valve check brown wire at igni...

Page 18: ...Be sure probe is positioned in the burner flame and glowing cherry red Check wire and wire connections at probe and ignition control B If wire and wire connections okay check for voltage across brown...

Page 19: ...hite Open WIRING DIAGRAMS Figure 21 Wiring Diagram 40 000 BTU Hr Model Figure 20 Wiring Diagram 25 000 BTU Hr Model Note Use only original replacement parts Thiswillprotectyourwarrantycoveragefor part...

Page 20: ...41 www portableheaterparts com sales portableheaterparts com techservice portableheaterparts com F B D 1349 Adams Street Bowling Green KY 42103 3414 1 800 654 8534 270 846 1199 Fax 1 800 846 0090 fran...

Page 21: ...1244 Operating Instructions Decal English 1 191246 Operating Instructions Decal French 1 531010 Warning Decal 1 191262 Nameplate 1 Parts available not shown You must order nameplate and operating inst...

Page 22: ...8 x 3 8 2 3 191241 Front Cover Trim 1 4 030642 Front Cover Assembly 1 5 100896 Cabinet Assembly 1 6 070511 Cabinet Insulation right and left sides 1 7 120158 Screw 8 x 3 8 2 8 160912 Thermostat inclu...

Page 23: ...44 Terminal Block 1 10 121224 Screw 10 x 3 4 2 11 070487 Gasket 1 12 231143 Transformer Assembly 1 13 121252 Screw 10 x 3 8 6 14 020983 Combustion Chamber Heat Shield Assembly 1 15 070606 Heat Shield...

Page 24: ...Terminals 1 13 070607 Heat Shield Gasket 1 14 020982 Combustion Chamber Heat Shield Assembly 1 15 061663 Wire Clamp 2 16 121252 Screw 10 x 3 8 12 17 230560 Limit Switch 1 KEY PART NO NUMBER DESCRIPTIO...

Page 25: ...3 4 5 6 7 8 9 10 11 12 KEY PART NO NUMBER DESCRIPTION QTY 1 120717 Hex Nut 10 24 2 2 121459 Screw 10 24 x 1 2 2 3 010701 Burner Assembly 1 4 180215 Main Burner Orifice 1 5 121388 Screw 10 x 1 2 4 6 07...

Page 26: ...PART NO NUMBER DESCRIPTION QTY 1 120717 Hex Nut 10 24 4 2 010621 Left Burner Assembly 1 3 010623 Right Burner Assembly 1 4 070591 Manifold Gasket 1 5 171167 Manifold Assembly 1 6 180188 Main Burner Or...

Page 27: ...oom air 1 8 121421 Hex Lock Nut 10 24 3 9 050751 Crossover Tube 1 10 121388 Screw 10 x 1 2 4 11 070385 Crossover Tube Gasket 2 12 121227 Screw 10 24 x 1 2 2 13 070362 Universal Bushing 1 14 231231 Cap...

Page 28: ...ombustion Air Cover Assy 1 12 121388 Screw 10 x 1 2 3 13 070420 Combustion Air Crossover Gasket 1 14 390318 Combustion Air and Motor Cover Assembly 1 KEY PART NO NUMBER DESCRIPTION QTY 15 121227 Screw...

Page 29: ...___________________ _______________________________________________________________________________________________ ____________________________________________________________________________________...

Page 30: ...lity of the owner TO THE FULL EXTENT ALLOWED BY THE LAW OF THE JURISDICTION THAT GOVERNS THE SALE OF THE PRODUCT THIS EXPRESS WARRANTY EXCLUDES ANY AND ALL OTHER EXPRESSED WARRANTIES AND LIMITS THE DU...

Reviews: