background image

5

201839

OWNER’S MANUAL

CREATING WALL OPENING
AND MOUNTING FURNACE

Remove furnace front cover. Remove the
two screws at the lower edges of front cover.
Lift front cover away.

Installing in Normal Frame Wall

The 25,000 BTU/Hr model is designed to fit
between two wall studs set at 16 inch on
center. The 40,000 BTU/Hr model will not
fit between wall studs. Follow the steps
below to install.

1.

Turn off electrical circuits that pass
through mounting wall. Make sure
there are no pipes or electrical wires in
area you intend to cut.

2.

Use stud locator or small finishing nail
to find wall studs. When you locate
studs, drive a small finishing nail into
each stud. This provides a visual refer-
ence for stud locations.

3.

25,000 BTU/Hr Model:

 Cut an open-

ing in wall between the two studs. Make
opening 14

1

/

4

" wide by 13

5

/

8

" high

(see Figure 2). 

IMPORTANT:

 You

must install furnace horizontally. Do
not install furnace vertically.

40,000 BTU/Hr Model:

 Cut a 20 

5

/

16

"

wide by 14 

3

/

8

" high opening in wall (see

Figure 2). Start your cut right next to
stud you are going to anchor cabinet to.
Cut across wall and through the next
stud. Stop cut at proper width.

IMPORTANT:

 You must install furnace

horizontally. Do not install furnace ver-
tically.

4.

25,000 BTU/Hr Model:

 Mark screw

locations on wall (see Figure 2). Make
sure screws will anchor into studs.
Make sure screw locations match screw
holes on cabinet flange.

40,000 BTU/Hr Model:

 Mark screw

locations on wall (see Figure 2). Make
sure screws on one side will anchor into
studs. Screws on other side will only
anchor in wall material. Make sure
screw locations match screw holes on

INSTALLATION

(Continued)

Figure 2 - Wall Openings and Screw
Locations

Wall Studs

Wall
Opening

14 

1

/

4

"

13 

5

/

8

"

Approx.
Screw
Locations

Wall Studs

20 

5

/

16

"

14 

3

/

8

"

Wall Opening

Approx.
Screw
Locations

25,000 BTU/Hr Model

cabinet flange.

5.

25,000 BTU/Hr Model:

 Use a proper-

sized drill bit. Drill holes through wall
and into studs at marked locations.

40,000 BTU/Hr Model:

 Use a proper-

sized drill bit. On wall stud side of
opening, drill holes through wall and
into studs at marked locations. On other
side, drill holes through wall material.

6.

Insert furnace into opening. Do this
from inside the room. Secure furnace
to wall with four large screws provided.

7.

On outside of wall, caulk opening be-
tween the cabinet and the rough edges
of opening.

40,000 BTU/Hr Model

Approx.
Screw
Locations

Installing in Masonry Wall

You can mount both models in a masonry
wall. Follow the steps below to install.

1.

Cut opening in wall. Make opening 14 

1

/

4

"

wide by 13 

5

/

8

" high for 25,000 BTU/Hr

models. Make opening 20 

5

/

16

" wide by

14 

3

/

8

" high for 40,000 BTU/Hr mod-

els. 

IMPORTANT:

 You must install

furnace horizontally. Do not install fur-
nace vertically.

INSTALLING THERMOSTAT

Mount the thermostat directly on the fur-
nace or on a wall in another part of the room.
If you have solid or masonry walls, mount
the thermostat on the furnace.

Mounting Thermostat to Furnace

1.

Unplug furnace.

2.

Locate red and white thermostat wires
coming out of side of furnace. These
wires are labeled “Thermostat.”

3.

Cut thermostat wires to desired length.

4.

Route thermostat wires through slot/
hole in side of thermostat mounting
plate. Then route wires through 5/8"
diameter hole in center of plate (see
Figure 4, page 6).

5.

Connect thermostat wires to the two
terminal screws on back of thermostat
(see Figure 3). Connect red wire to “R”
terminal. Connect white wire to “W”
terminal.

 WARNING: Unplug furnace

before installing thermostat.

2.

Secure furnace to wall with toggle bolts
or hook bolts set in mortar.

3.

Insert furnace into opening. Do this
from inside the room. Secure furnace
to wall with toggle bolts or hook bolts.

4.

On outside of wall, caulk opening be-
tween the cabinet and the rough edges
of opening. You can also use mortar to
seal opening.

Figure 3 - Connecting Thermostat Wires
to Thermostat

Continued

W

R

Red Wire

White Wire

Summary of Contents for DYNAVENT DNV25PB

Page 1: ...NING Improperin stallation adjustment alteration service or maintenance can cause injury or property dam age Refertothismanual for correct installation and operational proce dures Forassistanceor addi...

Page 2: ...LP gas is odor less An odor making agent is added to pro pane LP gas The odor helps you detect a propane LPgasleak However theodoradded to propane LP gas can fade Propane LP gas may be present even t...

Page 3: ...For purposes of input adjustment SPECIFICATIONS Install and use furnace with care Follow all localcodes Intheabsenceoflocalcodes use the latest edition of the following National Fuel Gas Code ANS Z223...

Page 4: ...installing thermostat in a wall make sure there are no pipes or wiring in the hollow wallabovethefurnace Thethermostatwires will pass through this wall from the attic Mounting hardware needed to moun...

Page 5: ...000 BTU Hr Model Use a proper sized drill bit Drill holes through wall and into studs at marked locations 40 000 BTU Hr Model Use a proper sized drill bit On wall stud side of opening drill holes thro...

Page 6: ...else that would interfere with install ing thermostat Do not mount thermo stat to stud If there are any obstruc tions choose a new location 3 Provide two 18 gauge insulated stranded wires for the the...

Page 7: ...t Wires to Thermostat Wall Anchors CAUTION Use only new black iron or steel pipe Copper tubing may be acceptable in cer tain areas Check local codes Use pipe large enough in diam eter to allow proper...

Page 8: ...de furnace back into furnace cabi net Make sure exhaust tube gaskets are in place Make sure exhaust and intake vent tubes extend into vent caps on back of cabinet Replace two screws by exhaust vent s...

Page 9: ...0 BTU Hr 15 000 BTU Hr for other gas appliances 55 000 BTU Hr total 55 000 2500 22 Locate 22 or higher on chart below According to the chart below you should use 40 feet or less of 3 8 pipe 125 feet o...

Page 10: ...5 CAUTION Usepipejointseal ant that is resistant to liquid pe troleum LP gas Slab Floor Installation Equipment Shutoff Valve Test Gauge Connection To Gas Supply 3 Min Sediment Trap Gas Piping Entering...

Page 11: ...0 cycle grounded outlet at furnace location 2 The furnace has a three pronged grounded plug Use only a grounded three prong outlet IMPORTANT Some local codes require rigid or semi rigid conduit or met...

Page 12: ...Do not try to light the burner by hand 8 Plug in furnace 9 Set thermostat to desired setting If thermostat is set above room tem perature the blower will come on 10 Allow approximately 45 seconds for...

Page 13: ...forces the combus tion products out of the exhaust tube s The Combustion air blower is sealed so that air does not pass between it and the circulating room air blower 3 When the blower motor reaches...

Page 14: ...r mixture Wipe cabinet and front cover to remove dust Use a vacuum cleaner to remove dust from front cover louvers EXHAUST AND INTAKE VENTS Make sure the exhaust and intake vents are not blocked The i...

Page 15: ...okay check for defective motor 5 Be sure the microswitch is sailing in far enough to open the solenoid valve and to energize the ignition control If the switch is not sailing in clean any dust or dir...

Page 16: ...t it WARNINGS Never connect unit or ignition circuit to 230 volts Never operate unit with glo bar touching burner or any other ground Damage to ignition control will occur Be sure sensor probe never t...

Page 17: ...bar broken 2 A Check for voltage 24 volts A C at valve 40 seconds after glo bar begins to glow If voltage present but valve not opening replace valve B If no voltage at valve check brown wire at igni...

Page 18: ...Be sure probe is positioned in the burner flame and glowing cherry red Check wire and wire connections at probe and ignition control B If wire and wire connections okay check for voltage across brown...

Page 19: ...hite Open WIRING DIAGRAMS Figure 21 Wiring Diagram 40 000 BTU Hr Model Figure 20 Wiring Diagram 25 000 BTU Hr Model Note Use only original replacement parts Thiswillprotectyourwarrantycoveragefor part...

Page 20: ...41 www portableheaterparts com sales portableheaterparts com techservice portableheaterparts com F B D 1349 Adams Street Bowling Green KY 42103 3414 1 800 654 8534 270 846 1199 Fax 1 800 846 0090 fran...

Page 21: ...1244 Operating Instructions Decal English 1 191246 Operating Instructions Decal French 1 531010 Warning Decal 1 191262 Nameplate 1 Parts available not shown You must order nameplate and operating inst...

Page 22: ...8 x 3 8 2 3 191241 Front Cover Trim 1 4 030642 Front Cover Assembly 1 5 100896 Cabinet Assembly 1 6 070511 Cabinet Insulation right and left sides 1 7 120158 Screw 8 x 3 8 2 8 160912 Thermostat inclu...

Page 23: ...44 Terminal Block 1 10 121224 Screw 10 x 3 4 2 11 070487 Gasket 1 12 231143 Transformer Assembly 1 13 121252 Screw 10 x 3 8 6 14 020983 Combustion Chamber Heat Shield Assembly 1 15 070606 Heat Shield...

Page 24: ...Terminals 1 13 070607 Heat Shield Gasket 1 14 020982 Combustion Chamber Heat Shield Assembly 1 15 061663 Wire Clamp 2 16 121252 Screw 10 x 3 8 12 17 230560 Limit Switch 1 KEY PART NO NUMBER DESCRIPTIO...

Page 25: ...3 4 5 6 7 8 9 10 11 12 KEY PART NO NUMBER DESCRIPTION QTY 1 120717 Hex Nut 10 24 2 2 121459 Screw 10 24 x 1 2 2 3 010701 Burner Assembly 1 4 180215 Main Burner Orifice 1 5 121388 Screw 10 x 1 2 4 6 07...

Page 26: ...PART NO NUMBER DESCRIPTION QTY 1 120717 Hex Nut 10 24 4 2 010621 Left Burner Assembly 1 3 010623 Right Burner Assembly 1 4 070591 Manifold Gasket 1 5 171167 Manifold Assembly 1 6 180188 Main Burner Or...

Page 27: ...oom air 1 8 121421 Hex Lock Nut 10 24 3 9 050751 Crossover Tube 1 10 121388 Screw 10 x 1 2 4 11 070385 Crossover Tube Gasket 2 12 121227 Screw 10 24 x 1 2 2 13 070362 Universal Bushing 1 14 231231 Cap...

Page 28: ...ombustion Air Cover Assy 1 12 121388 Screw 10 x 1 2 3 13 070420 Combustion Air Crossover Gasket 1 14 390318 Combustion Air and Motor Cover Assembly 1 KEY PART NO NUMBER DESCRIPTION QTY 15 121227 Screw...

Page 29: ...___________________ _______________________________________________________________________________________________ ____________________________________________________________________________________...

Page 30: ...lity of the owner TO THE FULL EXTENT ALLOWED BY THE LAW OF THE JURISDICTION THAT GOVERNS THE SALE OF THE PRODUCT THIS EXPRESS WARRANTY EXCLUDES ANY AND ALL OTHER EXPRESSED WARRANTIES AND LIMITS THE DU...

Reviews: