www.desatech.com
119347-01A
11
INStALLAtION
Continued
14"
Min.
Combustible
Material
Noncombustible Material
Hearth
5"
Min.
Combustible
Material
Figure 9 - Minimum Fireplace Clearances
Above Combustible Flooring
Figure 8 - Minimum Fireplace Clearances
If Installed at Floor Level
FLOOR CLEARANCES
A. If installing appliance on the floor level, you
must maintain the minimum distance of 14"
to combustibles (see Figure 8).
B. If combustible materials are less than 14" to
the fireplace, you must install appliance at
least 5" above the combustible flooring (see
Figure 9).
Area of Various Standard Round Flues
Diameter
Area
5"
0 sq. inches
6"
9 sq. inches
7"
39 sq. inches
8"
51 sq. inches
Chimney
Height
Minimum permanent
Flue Opening
6' to 15'
39 sq. inches
15' to 30'
9 sq. inches
INSTALLING DAMpER CLAMp
ACCESSORY FOR VENTED
OpERATION
Note:
When used as a vented heater, appliance
must be installed only in a solid-fuel burning
fireplace with a working flue and constructed of
noncombustible material.
You may use this heater as a vented product. There
are three reasons for operating your heater in the
vented mode.
1. The fireplace does not meet the clearance
to combustibles requirements for vent-free
operation.
2. State or local codes do not permit vent-free
operation.
3. You prefer vented operation.
If reasons number 1 or 2 apply to you, you must
permanently open chimney flue damper. You must
install the damper clamp accessory (to order, see
Accessories
, page 25). This will insure vented
operation (see Figure 10). The damper clamp will
keep damper open. Installation instructions are
included with clamp accessory.
See chart below for minimum permanent flue
opening you must provide. Attach damper clamp
so the minimum permanent flue opening will be
maintained at all times.
Figure 10 - Attaching Damper Clamp
Manufactured
Fireplace
Masonry Fireplace
Damper
Damper
Clamp
Damper
Damper
f i r e - p a r t s . c o m