www.desatech.com
119347-01A
10
Minimum Non-
Combustible
Material
Minimum Non-
Combustible
Material Height
Distances to
Underside of
Mantel
Top of Fireplace
Opening
Underside of
Mantel Shelf
Mantel Shelf
8"
(A)
8"
14"
17" 20"
All minimum
distances are
in inches
Log Set
All Models
2
1/2
"
6"
8"
10"
If Using Mantel
You must have noncombustible material(s) above
the fireplace opening. Noncombustible materials
(such as slate, marble, tile, etc.) must be at least 1/2"
thick. With sheet metal, you must have noncombus-
tible material behind it. Noncombustible material
must extend at least 8" up. Even if noncombustible
material is more than 12", you may need the hood
accessory to deflect heat away from your mantel
shelf. See Figure 5 (see page 9), Figure 6 and
Figure 7 for minimum clearances.
IMPORTANT:
If you cannot meet these minimum
clearances, you must operate heater with chimney
flue damper open. Go to
Installing Damper Clamp
Accessory for Vented Operation,
page 11.
MANTEL CLEARANCES
In addition to meeting noncombustible material
clearances, you must also meet required clearances
between fireplace opening and mantel shelf. If
you do not meet the clearances listed below, you
will need a hood.
Determining Minimum Mantel Clearance
If you meet minimum clearance between mantel
shelf and top of fireplace opening, a hood is not
required (see Figure 6).
INStALLAtION
Continued
Determining Minimum Mantel Clearance
when Using a Hood
If minimum clearances in Figure 6 are not met, you
must have a hood. When using a hood there are
still certain minimum mantel clearances required.
Follow minimum clearances shown in Figure 7
when using a hood.
NOTICE: Surface temperatures
of adjacent walls and mantels be-
come hot during operation. Walls
and mantels above the firebox
may become hot to the touch.
If installed properly, these tem-
peratures meet the requirement
of the national product standard.
Follow all minimum clearances
shown in this manual.
NOTICE: If your installation does
not meet the minimum clear-
ances shown, you must do one
of the following:
• operate the logs only with the
flue damper open
• raise the mantel to an accept-
able height
• remove the mantel
Figure 6 - Minimum Mantel Clearances
Without Using Hood
Figure 7 - Minimum Mantel Clearances
When Using Hood
Minimum
Noncombustible
Material
8"
Min.
12"
15"
18"
All minimum
distances are
in inches
20"
2
1/2
"
6"
8"
10"
12"
Distances to
Underside of
Mantel
Hood (GA6050,
GA6052 and
GA6053)
Top of Fireplace
Opening
Underside of
Mantel Shelf
Mantel Shelf
f i r e - p a r t s . c o m