background image

www.desatech.com

119347-01A

10

Minimum Non- 
Combustible  
Material  

Minimum Non-
Combustible 
Material Height 

Distances to 
Underside of
Mantel 

Top of Fireplace
Opening

Underside of
Mantel Shelf

Mantel Shelf 

8"

(A) 

8"

14"

17" 20"

All minimum 
distances are
in inches

Log Set

All Models

1/2

6" 

8" 

10" 

If Using Mantel

You must have noncombustible material(s) above 

the fireplace opening. Noncombustible materials 

(such as slate, marble, tile, etc.) must be at least 1/2" 

thick. With sheet metal, you must have noncombus-

tible material behind it. Noncombustible material 

must extend at least 8" up. Even if noncombustible 

material is more than 12", you may need the hood 

accessory to deflect heat away from your mantel 

shelf. See Figure 5 (see page 9), Figure 6 and 

Figure 7  for minimum clearances. 

IMPORTANT:

 If you cannot meet these minimum 

clearances, you must operate heater with chimney 

flue damper open. Go to 

Installing Damper Clamp 

Accessory for Vented Operation,

 page 11.

MANTEL CLEARANCES

In addition to meeting noncombustible material 

clearances, you must also meet required clearances 

between fireplace opening and mantel shelf. If 

you do not meet the clearances listed below, you 

will need a hood.

Determining Minimum Mantel Clearance

If you meet minimum clearance between mantel 

shelf and top of fireplace opening, a hood is not 

required (see Figure 6).

INStALLAtION

Continued

Determining Minimum Mantel Clearance 
when Using a Hood

If minimum clearances in Figure 6 are not met, you 

must have a hood. When using a hood there are 

still certain minimum mantel clearances required. 

Follow minimum clearances shown in Figure 7 

when using a hood.

NOTICE:  Surface  temperatures 

of adjacent walls and mantels be-

come hot during operation. Walls 

and  mantels  above  the  firebox 

may  become  hot  to  the  touch. 

If installed properly, these tem-

peratures meet the requirement 

of the national product standard. 

Follow all minimum clearances 

shown in this manual.

NOTICE: If your installation does 

not  meet  the  minimum  clear-

ances shown, you must do one 

of the following:

•  operate the logs only with the 

flue damper open

•  raise the mantel to an accept-

able height

•  remove the mantel

Figure 6 - Minimum Mantel Clearances 

Without Using Hood

Figure 7 - Minimum Mantel Clearances 

When Using Hood

Minimum
Noncombustible 
Material 

8"
Min.

12"

15"

18"

All minimum 
distances are
in inches

20"

1/2

"

6"

8"

10"

12"

Distances to 
Underside of
Mantel 

Hood (GA6050,
GA6052 and
GA6053)

Top of Fireplace
Opening

Underside of
Mantel Shelf

Mantel Shelf

f i r e - p a r t s . c o m

Summary of Contents for CSL2718N

Page 1: ...in your building Immediatelycallyourgassupplierfromaneighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service mus...

Page 2: ...s for installation only in a solid fuel burning mason ry or UL127 factory built fireplaceorinalistedvent lessfireboxenclosure Itis design certified for these installations in accor dance with ANSI Z21...

Page 3: ...Make certain you read and understand all warnings Keep this manual for reference It is your guide to safe and proper operation of this fireplace WARNING Any change to this heater or its controls can b...

Page 4: ...orsclosed heatbuildupinsidefire placewillcauseglasstoburst Makesurethereare no obstructions across openings of fireplace 9 This log heater is designed to be smokeless If logs ever appear to smoke turn...

Page 5: ...ace or unusually tight con struction unless provisions are provided for adequate combus tionandventilationair Readthe following instructions to insure proper fresh air for this and other fuel burning...

Page 6: ...A 54 defines a confined space as a space whose volume is less than 50 cubic feet per 1 000 Btu per hour 4 8 m3 per kw of the aggregate input rating of all appliances installed in that space and an unc...

Page 7: ...n5 3 or applicable local codes VENTILATION AIR Ventilation Air From Inside Building This fresh air would come from an adjoining un confined space When ventilating to an adjoining unconfined space you...

Page 8: ...the rating plate This appliance is not convertible for use with other gases WARNING This appliance is equipped for natural or pro pane LP gas Field conversion is not permitted Installation NOTICE Thi...

Page 9: ...16 from Side Wall Example INSTALLATION Continued NOTICE Manual control heaters may be used as a vented product If so you must always run heater with chimney flue damper open If running heater with da...

Page 10: ...ances listed below you will need a hood Determining Minimum Mantel Clearance If you meet minimum clearance between mantel shelf and top of fireplace opening a hood is not required see Figure 6 INSTALL...

Page 11: ...nted heater appliance must be installed only in a solid fuel burning fireplace with a working flue and constructed of noncombustible material You may use this heater as a vented product There are thre...

Page 12: ...resistant to propane LP gas not provided electric drill with 3 16 drill bit flathead screwdriver 1 Apply pipe joint sealant lightly to male threads of the fitting to be threaded into gas regulator Con...

Page 13: ...egulator will reduce incoming gas pressure You must reduce incoming gas pressure to between 11 and 14 of water If you do not reduce incoming gas pres sure heater regulator damage could occur Install e...

Page 14: ...stem by either opening propane LP supply tank valve for propane LP gas or opening main gas valve located on or near gas meter for natural gas or using compressed air 4 Check all joints of gas supply p...

Page 15: ...ng Heater page 16 Check all other internal joints for leaks 7 Turn off heater see To Turn Off Gas to Appli ance page 17 INSTALLING Log WARNING Failuretoposition thepartsinaccordancewiththese diagrams...

Page 16: ...control system and any gas control which has been under water LIGHTING INSTRUCTIONS WARNING If fireplace has glass doors never operate this heater with glass doors closed If you op erateheaterwithdoo...

Page 17: ...olknobcoun terclockwise to desired heating level The burner should light Set control knob to any heat level between HI and LO WARNING Do not operate heaterbetweenPILOTandHIGH positions Figure 19 Contr...

Page 18: ...lot Burner Pilot Burner Thermocouple Propane LP Natural Gas BURNER PRIMARY AIR HOLES Air is drawn into the burner through the holes in the fitting at the entrance to the burner These holes may become...

Page 19: ...clumpsof dusthave now been pushed into the burner repeat steps 3 and 4 Clean the pilot assembly also Ayellow tip on the pilot flame indicates dust and dirt in the pilot as sembly There is a small pilo...

Page 20: ...talled 5 Depleted gas supply propane LP only 6 ODS pilot is clogged 7 Gas regulator setting is not correct OBSERVED PROBLEM When ignitor button is pressed there is no spark at ODS pilot When ignitor b...

Page 21: ...atural or pro pane LP gas company 1 Contact local natural or pro pane LP gas company 2 Clean burner see Cleaning and Maintenance page 18 or replace burner orifice 1 Clean burner see Cleaning and Maint...

Page 22: ...until air is removed from line Have gas line checked by local natural or propane LP gas company 3 Observe minimum installation clearances see page 8 4 Clean burner see Cleaning and Maintenance page 18...

Page 23: ...ecking Gas Connec tions page 14 1 Open window and or door for ventilation 2 Contact local natural or pro pane LP gas company 3 Clean ODS pilot see Cleaning and Maintenance page 18 1 Locate and correct...

Page 24: ...ll have delayed ignition heater will not produce specified heat propane LP gas supply may be low You may feel your gas pressure is too low If so con tact your local natural or propane LP gas supplier...

Page 25: ...arts Centrals are privately owned businesses They have agreed to support our customer s needs by providing original replacement parts and accessories Tool Equipment Co 5 Manila Ave Hamden CT 06514 032...

Page 26: ...desatech com 119347 01A 26 15 17 18 16 9 5 6 7 19 16 4 11 3 19 19 14 2 27 12 13 8 10 1 Illustrated Parts Breakdown Variable Manually Controlled Winchester Oak Models CSL2718N AND CSL2718P fire parts...

Page 27: ...Burner Orifice Injector 1 099056 21 Burner Orifice Injector 1 9 111124 01 Burner Retainer Spring 1 10 102963 02 Burner 1 11 102568 07 Control Valve 1 102568 08 Control Valve 1 12 098508 01 Valve Retai...

Page 28: ...ualified installer in accordance with all local codes and instructions furnished with the unit This warranty does not apply to parts that are not in original condition because of normal wear and tear...

Reviews: