VENT-FREE NATURAL GAS PEDESTAL STOVE

For more information, visit www.desatech.com

Tee Joint

Pipe
Nipple

Cap

3" Minimum

Sediment
Trap

Gas
Regulator
of Heater

From Gas Meter
(5" W.C.** to 10.5"
W.C. Pressure)

CSA Design-Certified Equipment
Shutoff Valve With 1/8" NPT Tap*

Approved Flexible Gas Hose
(if allowed by local codes)

Figure 6 - Gas Connection

* Purchase the optional CSA design-certified equipment shutoff valve from your dealer.

See Accessories, page 24.

** Minimum inlet pressure for purpose of input adjustment.

 CAUTION: Avoid damage to

regulator. Hold gas regulator with
wrench when connecting it to gas
piping and/or fittings.

Installation must include an equipment
shutoff valve, union, and plugged 1/8" NPT
tap. Locate NPT tap within reach for test
gauge hook up. NPT tap must be upstream
from heater (see Figure 6).

IMPORTANT:

 Install equipment shutoff

valve in an accessible location. The equip-
ment shutoff valve is for turning on or
shutting off the gas to the appliance.

 WARNING: Never connect

heater to private (non-utility) gas
wells. This gas is commonly
known as wellhead gas.

 CAUTION: Use pipe joint seal-

ant that is resistant to liquid pe-
troleum (LP) gas.

We recommend that you install a sediment
trap in supply line as shown in Figure 6.
Locate sediment trap where it is within
reach for cleaning. Install in piping system
between fuel supply and heater. Locate sedi-
ment trap where trapped matter is not likely
to freeze. A sediment trap traps moisture
and contaminants. This keeps them from
going into heater controls. If sediment trap
is not installed or is installed wrong, heater
may not run properly.

INSTALLATION

Continued

CONNECTING TO GAS
SUPPLY

 WARNING: A qualified service

person must connect heater to gas
supply. Follow all local codes.

Installation Items Needed

Before installing heater, make sure you have
the items listed below.

• piping (check local codes)

• sealant (resistant to propane/LP gas)

• equipment shutoff valve *

• test gauge connection *

• sediment trap

• tee joint

• pipe wrench

*  An CSA design-certified equipment
shutoff valve with 1/8" NPT tap is an ac-
ceptable alternative to test gauge connec-
tion. Purchase the optional CSA design-
certified equipment shutoff valve from your
dealer. See Accessories, page 24.

Apply pipe joint sealant lightly to male
threads. This will prevent excess sealant
from going into pipe. Excess sealant in pipe
could result in clogged heater valves.

Figure 5 - Gas Regulator Location and
Gas Line Access Into Stove Cabinet

 CAUTION: Use only new,

black iron or steel pipe. Inter-
nally-tinned copper tubing may
be used in certain areas. Check
your local codes. Use pipe of 1/2"
diameter or greater to allow
proper gas volume to heater. If
pipe is too small, undue loss of
pressure will occur.

Front
of
Stove
Unit

Gas Regulator
Inlet Connection

Back View

Side View

Summary of Contents for Comfort Glow S39NT

Page 1: ...If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING Improper installa tion adj...

Page 2: ...urn heater off If heated the vapors from these products may create a white pow der residue within burner box or on adjacent walls or furniture 8 This heater needs fresh outside air ven tilation to run...

Page 3: ...UNPACKING 1 Remove top inner pack 2 Tilt carton so that stove is upright 3 Remove protective side packaging 4 Slide stove out of carton 5 Remove protective plastic wrap 6 Remove screen by lifting and...

Page 4: ...eater shall notbeinstalledinaconfinedspace or unusually tight construction unless provisions are provided foradequatecombustionandven tilation air Read the following in structions to insure proper fre...

Page 5: ...rect vent draws combustion air from the outdoors and vents to the outdoors 4 Compare the maximum Btu Hr the space can support with the actual amount of Btu Hr used _________________ Btu Hr maximum the...

Page 6: ...tilation grills or ducts Ventilation Air From Outdoors Provide extra fresh air by using ventilation grills or ducts You must provide two per manent openings one within 12 of the ceiling and one within...

Page 7: ...reater clearances from floor ceiling and adjoining side and back walls Carefullyfollowtheinstructionsbelow This stove is a freestanding unit designed to set directly on the floor IMPORTANT You must ma...

Page 8: ...r cleaning Install in piping system betweenfuelsupplyandheater Locatesedi ment trap where trapped matter is not likely to freeze A sediment trap traps moisture and contaminants This keeps them from go...

Page 9: ...nnect heater and equipment shutoff valve to gas supply Check re connected fittings for leaks Test Pressures Equal To or Less Than 1 2 PSIG 3 5 kPa 1 Close equipment shutoff valve see Fig ure 7 2 Press...

Page 10: ...ols required Phillips screwdriver NOTICE Shutoffgasheaterduring the following blower installation 1 Remove 2 screws from rear tabs on top trim Pull trim forward to remove see Figure 11 2 Remove top pa...

Page 11: ...inside control compartment door in front of stove see Figure 16 15 Using two screws provided in blower kit mount blower speed control hous ing to mounting tab in left side of lower control compartment...

Page 12: ...after servicing Wiring Diagram Decal Figure 18 Attaching Wire Harness to ThermostaticSwitchandCoverAssembly Thermostatic Switch Mounted to Cover Wire Harness Lower Hole Figure 19 Assembling Thermosta...

Page 13: ...ighted by hand When lighting the pilot follow these instructions exactly B BEFORE LIGHTING smell all around the appliance area for gas Be sure to smell next to the floor because some gas is heavier th...

Page 14: ...n and burner flame patterns often PILOT FLAME PATTERN Figure 23 shows a correct pilot flame pat tern Figure 24 shows an incorrect pilot flame pattern Note Appearance of pilot assembly may vary by mode...

Page 15: ...cleanandfreeofdust and dirt To clean these parts we recommend using compressed air no greater than 30 PSI Yourlocalcomputerstore hardwarestore or home center may carry compressed air in a can You can...

Page 16: ...ged 7 Control valve damaged REMEDY 1 Reconnect ignitor cable 2 Free ignitor cable if pinched by any metal or tubing Keep ignitor cable dry 3 Tighten nut holding piezo ignitor to base panel of log set...

Page 17: ...ute 2 Operate burner until air is removed from line Have gas line checked by local natu ral gas company 3 Observe minimum installation clearances see pages 7 through 9 4 Clean burner see Cleaning and...

Page 18: ...ater produces unwanted odors Heater shuts off in use ODS operates Gas odor even when control knob is in OFF position Gas odor during combustion Burner flame is excessively large and is very near or to...

Page 19: ...ent Baltimore Electric 1348 Dixwell Avenue Hamden CT 06514 0322 1 800 397 7553 203 248 7553 Parts Department Portable Heater Parts 342 N County Rd 400 East Valparaiso IN 46383 9704 All States 219 462...

Page 20: ...20 107434 VENT FREE NATURAL GAS PEDESTAL STOVE For more information visit www desatech com ILLUSTRATED PARTS BREAKDOWN S39NT 7 6 9 4 10 3 2 1 14 5 12 11 10 8 13...

Page 21: ...manual KEY PART NO NUMBER DESCRIPTION QTY 1 107433 02 Log Set 1 2 104285 01 ODS Pilot NG 1 3 098249 01 ODS Nut 2 4 107090 01 Burner Outlet Tube 1 5 107089 01 Inlet Tube 1 6 102843 01 Burner Clip 1 7...

Page 22: ...107434 VENT FREE NATURAL GAS PEDESTAL STOVE For more information visit www desatech com ILLUSTRATED PARTS BREAKDOWN S39NT 1 10 4 13 3 2 14 7 16 15 11 18 20 5 6 9 8 17 12 23 21 19 19 26 26 22 22 21 25...

Page 23: ...9 107080 01CK Firebox Floor 1 10 107081 01CJ Firebox Top 1 11 107365 01CK Screen Assembly 1 12 101382 01 Valve Bracket 1 13 107092 01 Brass Trim Bottom 1 14 107093 01 Brass Trim Firebox 1 15 105576 0...

Page 24: ...nt part s call DESA International s Parts Department at 1 800 972 7879 for referral information WhencallingDESAInternational haveready model number of your heater the replacement part number ACCESSORI...

Page 25: ..._________________________________________ _______________________________________________________________________________________________ ______________________________________________________________...

Page 26: ...sedbyimproperinstallation Travel diagnostic cost labor transportation and any and all such other costs related to repairing a defective heater will be the responsibility of the owner TO THE FULL EXTEN...

Reviews: