background image

5

107434

OWNER’S MANUAL

For more information, visit www.desatech.com

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this worksheet to determine if you have a confined or unconfined space.

Space:

 Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between

the rooms.

1.

Determine the volume of the space (length x width x height).

Length x Width x Height = ____________________ cu. ft. (volume of space)

Example: 

Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) =  2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of
the space.

2.

Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.

_________________ (volume of space) x 20 = (Maximum Btu/Hr the space can support)

Example:

 2560 cu. ft. (volume of space) x 20 = 51,200 (maximum Btu/Hr the space can support)

3.

Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

_________________ Btu/Hr

Gas water heater*

_________________ Btu/Hr

Gas furnace

_________________ Btu/Hr

Vented gas heater

_________________ Btu/Hr

Gas heater logs

_________________ Btu/Hr

Other gas appliances* +

_________________ Btu/Hr

Total                            =

_________________ Btu/Hr

* Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.

Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_________________ Btu/Hr (maximum the space can support)

_________________ Btu/Hr (actual amount of Btu/Hr used)

Example:

 51,200 Btu/Hr (maximum the space can support)

69,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support.
You must provide additional fresh air. Your options are as follows:

A. Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining

room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 6.

B. Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 6.

C. Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no
additional fresh air ventilation.

 WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space

or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of
the methods described in the 

National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3 or applicable local codes.

AIR FOR
COMBUSTION AND
VENTILATION

Continued

Example:

Gas water heater

30,000

Btu/Hr

Vent-free heater  +

39,000

Btu/Hr

Total                        =

69,000

Btu/Hr

Continued

Summary of Contents for Comfort Glow S39NT

Page 1: ...If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING Improper installa tion adj...

Page 2: ...urn heater off If heated the vapors from these products may create a white pow der residue within burner box or on adjacent walls or furniture 8 This heater needs fresh outside air ven tilation to run...

Page 3: ...UNPACKING 1 Remove top inner pack 2 Tilt carton so that stove is upright 3 Remove protective side packaging 4 Slide stove out of carton 5 Remove protective plastic wrap 6 Remove screen by lifting and...

Page 4: ...eater shall notbeinstalledinaconfinedspace or unusually tight construction unless provisions are provided foradequatecombustionandven tilation air Read the following in structions to insure proper fre...

Page 5: ...rect vent draws combustion air from the outdoors and vents to the outdoors 4 Compare the maximum Btu Hr the space can support with the actual amount of Btu Hr used _________________ Btu Hr maximum the...

Page 6: ...tilation grills or ducts Ventilation Air From Outdoors Provide extra fresh air by using ventilation grills or ducts You must provide two per manent openings one within 12 of the ceiling and one within...

Page 7: ...reater clearances from floor ceiling and adjoining side and back walls Carefullyfollowtheinstructionsbelow This stove is a freestanding unit designed to set directly on the floor IMPORTANT You must ma...

Page 8: ...r cleaning Install in piping system betweenfuelsupplyandheater Locatesedi ment trap where trapped matter is not likely to freeze A sediment trap traps moisture and contaminants This keeps them from go...

Page 9: ...nnect heater and equipment shutoff valve to gas supply Check re connected fittings for leaks Test Pressures Equal To or Less Than 1 2 PSIG 3 5 kPa 1 Close equipment shutoff valve see Fig ure 7 2 Press...

Page 10: ...ols required Phillips screwdriver NOTICE Shutoffgasheaterduring the following blower installation 1 Remove 2 screws from rear tabs on top trim Pull trim forward to remove see Figure 11 2 Remove top pa...

Page 11: ...inside control compartment door in front of stove see Figure 16 15 Using two screws provided in blower kit mount blower speed control hous ing to mounting tab in left side of lower control compartment...

Page 12: ...after servicing Wiring Diagram Decal Figure 18 Attaching Wire Harness to ThermostaticSwitchandCoverAssembly Thermostatic Switch Mounted to Cover Wire Harness Lower Hole Figure 19 Assembling Thermosta...

Page 13: ...ighted by hand When lighting the pilot follow these instructions exactly B BEFORE LIGHTING smell all around the appliance area for gas Be sure to smell next to the floor because some gas is heavier th...

Page 14: ...n and burner flame patterns often PILOT FLAME PATTERN Figure 23 shows a correct pilot flame pat tern Figure 24 shows an incorrect pilot flame pattern Note Appearance of pilot assembly may vary by mode...

Page 15: ...cleanandfreeofdust and dirt To clean these parts we recommend using compressed air no greater than 30 PSI Yourlocalcomputerstore hardwarestore or home center may carry compressed air in a can You can...

Page 16: ...ged 7 Control valve damaged REMEDY 1 Reconnect ignitor cable 2 Free ignitor cable if pinched by any metal or tubing Keep ignitor cable dry 3 Tighten nut holding piezo ignitor to base panel of log set...

Page 17: ...ute 2 Operate burner until air is removed from line Have gas line checked by local natu ral gas company 3 Observe minimum installation clearances see pages 7 through 9 4 Clean burner see Cleaning and...

Page 18: ...ater produces unwanted odors Heater shuts off in use ODS operates Gas odor even when control knob is in OFF position Gas odor during combustion Burner flame is excessively large and is very near or to...

Page 19: ...ent Baltimore Electric 1348 Dixwell Avenue Hamden CT 06514 0322 1 800 397 7553 203 248 7553 Parts Department Portable Heater Parts 342 N County Rd 400 East Valparaiso IN 46383 9704 All States 219 462...

Page 20: ...20 107434 VENT FREE NATURAL GAS PEDESTAL STOVE For more information visit www desatech com ILLUSTRATED PARTS BREAKDOWN S39NT 7 6 9 4 10 3 2 1 14 5 12 11 10 8 13...

Page 21: ...manual KEY PART NO NUMBER DESCRIPTION QTY 1 107433 02 Log Set 1 2 104285 01 ODS Pilot NG 1 3 098249 01 ODS Nut 2 4 107090 01 Burner Outlet Tube 1 5 107089 01 Inlet Tube 1 6 102843 01 Burner Clip 1 7...

Page 22: ...107434 VENT FREE NATURAL GAS PEDESTAL STOVE For more information visit www desatech com ILLUSTRATED PARTS BREAKDOWN S39NT 1 10 4 13 3 2 14 7 16 15 11 18 20 5 6 9 8 17 12 23 21 19 19 26 26 22 22 21 25...

Page 23: ...9 107080 01CK Firebox Floor 1 10 107081 01CJ Firebox Top 1 11 107365 01CK Screen Assembly 1 12 101382 01 Valve Bracket 1 13 107092 01 Brass Trim Bottom 1 14 107093 01 Brass Trim Firebox 1 15 105576 0...

Page 24: ...nt part s call DESA International s Parts Department at 1 800 972 7879 for referral information WhencallingDESAInternational haveready model number of your heater the replacement part number ACCESSORI...

Page 25: ..._________________________________________ _______________________________________________________________________________________________ ______________________________________________________________...

Page 26: ...sedbyimproperinstallation Travel diagnostic cost labor transportation and any and all such other costs related to repairing a defective heater will be the responsibility of the owner TO THE FULL EXTEN...

Reviews: