background image

4

103427

UNVENTED PROPANE GAS LOG HEATER

DETERMINING AIR FLOW
FOR HEATER LOCATION

Determining if You Have a
Confined or Unconfined Space

Use this work sheet to determine if you have
a confined or unconfined space.

Space:

 Includes the room in which you

will install heater plus any adjoining rooms
with doorless passageways or ventilation
grills between the rooms.

1.

Determine the volume of the space
(length x width x height).

Length x Width x Height =

__________ cu. ft. (volume of space)

Example:

Space size

20 ft. (length) x 16 ft. (width) x 8 ft.
(ceiling height) = 2560 cu. ft. (volume
of space)

If additional ventilation to adjoining
room is supplied with grills or open-
ings, add the volume of these rooms to
the total volume of the space.

2.

Divide the space volume by 50 cubic
feet to determine the maximum Btu/Hr
the space can support.

__________ (volume of space) 

÷

 50

cu. ft. = (Maximum Btu/Hr the space
can support)

Example:

  2560 cu. ft. (volume of

space) 

÷

 50 cu. ft. = 51.2 or 51,200

(maximum Btu/Hr the space can sup-
port)

3.

Add the Btu/Hr of all fuel burning ap-
pliances in the space.

Vent-free heater __________ Btu/Hr

Gas water heater* ________ Btu/Hr

Gas furnace _____________ Btu/Hr
Vented gas heater _________ Btu/Hr
Gas fireplace logs ________ Btu/Hr
Other gas appliances*+ ____ Btu/Hr
Total                           = ____ Btu/Hr

Example:

Gas water heater

40,000 Btu/Hr

Vent-free heater

33,000 Btu/Hr

Total

73,000 Btu/Hr

* Do not include direct-vent gas appli-
ances. Direct-vent draws combustion
air from the outdoors and vents to the
outdoors.

PROVIDING ADEQUATE
VENTILATION

The following is exerpts from National Fuel
Gas Code. NFPA 54/ANSI Z223.1, Section
5.3, Air for Combustion and Ventilation.

All spaces in homes fall into one of the three
following ventilation classifications:

1. Unusually Tight Contruction; 2. Uncon-
fined Space; 3. Confined Space.

The information on pages 4 and 5 will help
you classify your space and provide ad-
equate ventilation.

Confined and Unconfined Space

The National Fuel Gas Code (ANSIZ2123.1,
1992 Section 5.3)
 defines a confined space
as a space whose volume is less than 50
cubic feet per 1,000 Btu per hour (4.8 m

3

 per

kw) of the aggregate input rating of all
appliances installed in that space and an
unconfined space as a space whose volume
is not less than 50 cubic feet per 1,000 Btu
per hour (4.8 m

3

 per kw) of the aggregate

input rating of all appliances installed in that
space. Rooms communicating directly with
the space in which the appliances are in-
stalled*, through openings not furnished
with doors, are considered a part of the
unconfined space.

* Adjoining rooms are communicating only
if there are doorless passageways or ventila-
tion grills between them.

AIR FOR
COMBUSTION AND
VENTILATION

Today’s homes are built more energy effi-
cient than ever. New materials, increased
insulation, and new construction methods
help reduce heat loss in homes. Home own-
ers weather strip and caulk around windows
and doors to keep the cold air out and the
warm air in. During heating months, home
owners want their homes as airtight as pos-
sible.

While it is good to make your home energy
efficient, your home needs to breathe. Fresh
air must enter your home. All fuel-burning
appliances need fresh air for proper com-
bustion and ventilation.

Exhaust fans, fireplaces, clothes dryers, and
fuel burning appliances draw air from the
house to operate. You must provide ad-
equate fresh air for these appliances. This
will insure proper venting of vented fuel-
burning appliances.

Continued

 WARNING: This heater shall

not be installed in a confined
space unless provisions are pro-
vided for adequate combustion
and ventilation air. Read the fol-
lowing instructions to insure
proper fresh air for this and other
fuel-burning appliances in your
home.

Unusually Tight Construction

The air that leaks around doors and win-
dows may provide enough fresh air for
combustion and ventilation. However, in
buildings of unusually tight construction,
you must provide additional fresh air.

Unusually tight construction is de-
fined as construction where:

a.

walls and ceilings exposed to the
outside atmosphere have a con-
tinuous water vapor retarder with
a rating of one perm (6 x 10

-11

 kg

per-pa-sec-m

2

) or less with open-

ings gasketed or sealed 

and

b. weather stripping has been

added on openable windows and
doors 

and

c.

caulking or sealants are applied
to areas such as joints around
window and door frames, be-
tween sole plates and floors, be-
tween wall-ceiling joints, be-
tween wall panels, at penetra-
tions for plumbing, electrical, and
gas lines, and at other openings.

If your home meets all of the three
criteria above, you must provide ad-
ditional fresh air. See 

Ventilation Air

From Outdoors, page 5.

If your home does not meet all of the
three criteria above, proceed to 

De-

termining Air Flow For Heater Loca-
tion.

Summary of Contents for American Oak Design Unvented Propane Gas Log Heater Model Split Oak and American Oak Design

Page 1: ...sup plier call the fire department Installation and service must be performed by a qualified installer ser vice agency or the gas supplier WARNING Improper installation adjust ment alteration service...

Page 2: ...spect chimney flue for damage If damaged operate heater with flue damper closed 7 If fireplace has glass doors never op erate this heater with glass doors closed If you operate heater with doors close...

Page 3: ...n is not permitted 1 Remove logs and heater base assem bly from carton Note Do not pick up heater base assembly by burners This could damage heater Always handle base assembly by grate 2 Remove all pr...

Page 4: ...3 per kw of the aggregate inputratingofallappliancesinstalledinthat space Rooms communicating directly with the space in which the appliances are in stalled through openings not furnished with doors a...

Page 5: ...e ANSI Z223 1 1992 Section 5 3 VENTILATION AIR Ventilation Air From Inside Building This fresh air would come from an adjoining unconfined space When ventilating to an adjoining unconfined space you m...

Page 6: ...learances see Figure 5 A Clearances from the side of the fire place opening to any combustible wall should not be less than 16 inches B Clearances from the top of the fireplace opening to the ceiling...

Page 7: ...antel shelf See chart below and Figures 7 and 8 page 8 for minimum clearances IMPORTANT Ifyoucannotmeettheseminimumclearances youmustoperateheaterwith chimney flue damper open Go to Installing Damper...

Page 8: ...050 GA6052 Top of Fireplace Opening Underside of Mantel Shelf Floor Clearances A If installing appliance on the floor level you must maintain the minimum dis tance of 14 to combustibles see Fig ure 9...

Page 9: ...xible gas hose and fittings not provided if allowed by local codes sealant resistant to LP gas not provided electric drill with 3 16 masonry drill bit 1 Apply pipe joint sealant lightly to male thread...

Page 10: ...excess sealant from going into pipe Excess sealant in pipe could result in clogged heater valves CAUTION Use only new black iron or steel pipe Inter nally tinned copper tubing may be used in certain...

Page 11: ...on necting to Gas Supply page 10 CHECKING GAS CONNECTIONS ON POSITION OFF POSITION Figure 16 Manual Shutoff Valve Open Closed Manual Shutoff Valve Figure 17 Checking Gas Joints Thermostat Gas Valve or...

Page 12: ...Slide rear log 1 into place behind rear burner see Figure 18 2 Slide front log 2 into place behind front burner Make sure tabs at bottom of log are behind front burner see Fig ure 19 3 Place crossover...

Page 13: ...behind metal posts on front burner Make sure the grooves in the bottom of the log fit over the grate Bring the log forward next to the metal posts The pegs on the log must be on top see Figure 23 3 S...

Page 14: ...lace will cause glass to burst Also if fireplace opening has vents at the bottom you must open the vents before operating heater You must operate this heater withafireplacescreeninplace Make sure fire...

Page 15: ...mostat Controlled Models Only Thethermostatcontrolknobcanbesetto anycomfortlevelbetweenHiandLo The thermostat will gradually modulate the heatoutputandflameheightfromhigher to lower settings or pilot...

Page 16: ...tting Off Burners Only pilot stays lit 1 Turn the control knob clockwise Clockwise to the HIGH position 2 Press in and turn control knob clock wise Clockwise to the pilot position Thermocouple Ignitor...

Page 17: ...lames with yellow tipping Dirt or other fine particles are burned by heater causing brief patches of orange flame CORRECT FLAME PATTERN AT HIGH POSITION INCORRECT FLAME PATTERN AT HIGH POSITION Figure...

Page 18: ...ODS pilot 6 Thermocouple connection loose at con trol valve 7 Thermocouple damaged 8 Control valve damaged REMEDY 1 Reconnect ignitor cable 2 Free ignitor cable if pinched by any metal or tubing Keep...

Page 19: ...debris If found clean burner s see Cleaning and Maintenance page 17 2 Replace gas regulator 1 Problem will stop after a few hours of operation 1 Turn control knob to LO position and let warm up for a...

Page 20: ...ntrol valve defective 1 Foreign matter between control valve and burner 2 Gas leak See Warning statement at top of page 1 Thermostat sensing bulb needs to be repositioned REMEDY 1 This is common with...

Page 21: ...thermostat sensing bulb IMPORTANT Do not force or bend the thermostat sensing bulb or capillary 4 The thermostat sensing bulb may be located to the lower right front side of fireplace Determine locat...

Page 22: ...ropane Only Propane Only Propane Only Ignition Piezo Piezo Piezo Manifold Pressure 7 9 W C 7 9 W C 7 9 W C Inlet Gas Pressure in of water Maximum 14 14 14 Minimum 11 11 11 For purpose of input adjustm...

Page 23: ...CS30NV A B CS30PV A B VENT FREE LOGMATE FIRE BOXES Available in 32 36 and 42 models May be paired with the logs listed below Circulating fireboxes feature louvers and anoptionalblower Non circulating...

Page 24: ...G HEATER ILLUSTRATED PARTS BREAKDOWN Variable Manually Controlled Models 18 20 19 26 25 21 21 27 28 6 7 8 29 29 25 10 9 11 12 13 15 22 23 27 1 27 2 24 7 1 7 2 14 16 17 4 5 3 2 1L 1R VS18PVB CFS18PVB V...

Page 25: ...ezoIgnitor 1 12 098867 10 098867 10 098867 10 Gas Regulator 1 13 M11084 38 M11084 38 M11084 38 Screw 2 14 101011 01 101011 02 101011 03 Inlet Tube 1 15 098354 01 098354 01 098354 01 Control Knob 1 16...

Page 26: ...ROPANE GAS LOG HEATER 31 6 25 6 7 8 9 10 11 8 8 29 13 12 13 14 15 16 18 17 19 24 26 27 7 1 7 2 29 22 23 21 28 20 30 10 1 10 2 4 5 3 2 1R 1L ILLUSTRATED PARTS BREAKDOWN Thermostat Controlled Models VS1...

Page 27: ...01331 06 101331 07 Base Assembly with decals 1 13 098271 07 098271 06 098271 06 Ignitor Cable 1 14 102445 01 102445 01 102445 01 Piezo Ignitor 1 15 098867 10 098867 10 098867 10 Gas Regulator 1 16 M11...

Page 28: ...ED PROPANE GAS LOG HEATER ILLUSTRATED PARTS BREAKDOWN Variable Manually Controlled Models VL18PV VL24PV VL30PV 18 20 19 26 25 21 21 27 28 6 7 8 29 29 25 10 9 11 12 13 15 22 23 27 1 27 2 24 7 1 7 2 14...

Page 29: ...98867 10 098867 10 Gas Regulator 1 13 M11084 38 M11084 38 M11084 38 Screw 2 14 101011 01 101011 02 101011 03 Inlet Tube 1 15 098354 01 098354 01 098354 01 Control Knob 1 16 098462 03 098462 03 098462...

Page 30: ...___________________________ _______________________________________________________________________________________________ ____________________________________________________________________________...

Page 31: ...______________________________________ _______________________________________________________________________________________________ _________________________________________________________________...

Page 32: ...ns furnished with the unit This warranty does not apply to parts that are not in original condition because of normal wear and tear or parts that fail or become damaged as a result of misuse accidents...

Reviews: