(1) Replace air cleaner element
The element should be replaced referring to "Clean air cleaner element"
(See p.40) every 500 hours or
2
years.
In situations where the generator has not been operated for 500 hours or more, as a
general rule, the air cleaner will need to be replaced after it has been cleaned 6 times.
(2) Clean radiator
When the fm or tube is blinded, it should be cleaned with steam or running water.
Do not use a high pressure washer to prevent damage to the fm and tube.
8-6 Check/every 500 hours
8-7 Check/every 1000 hours
(1) Clean inside of fuel tank
Drain the fuel in the fuel tank completely, and wash out
deposits and water collected inside the tank.
(2) Adjust fuel injection nozzle
8-8 Check/every 2000 hours
(1) Measure the engine compression pressure
(2) Check the valve clearance
(3) ^Replace radiator water (if LLC is used)
(4) Check on nylon and rubber hose
Check on the nylon and rubber hose whether they are hardened or deteriorate.
Contact distributor or our office to replace the nylon hose and rubber hose, if
necessary.
(5) Checking terminals and connections
Check for main and sub circuit whether there are no abnormality such as loosening,
corrosion and burning, etc.
8-9 Other Checks and Maintenance
(1) Check on lining
Check on the lining whether it deteriorates greatly, or it is stained by clinging of oil
or the like, or it is removed. Contact distributor or our office to replace the lining, if
necessary.