5-5 Protection device
Protection devices and emergency stop devices are provided for protection of the
machine against trouble during operation.
When the warning lamp lights, stop the engine immediately. Check and remove the
cause of trouble.
Table of protection device
a c tio n
w a m i n g ^ - ^ _
turn OFF the
circuit break
er
stop the
engine
indicate by
warning lamp
fu n c tio n
Oil pressure failure
low lubricating oil
(OIL PRESS.)
—
О
О
When the oil
pressure falls
abnormally, the
device acts.
Set point: 0.049MPa
H igh jacket water
temperature
(WATER TEMP.)
—
о
о
When the cooling
water temperature
rises abnormally,
the device acts.
Set point: 115°C
Insufficient charge
—
о
о
When insufficient
charge, the device
acts.
Fuel level failure
(FUEL LEVEL)
—
__
о
W hen fuel runs low,
the device acts.
Over-current
o f generator
О
—
__
When over-current
occurs, the device
acts.