![Dentech AYRDYNE 4.0 Installation, Operation And Maintenance Manual Download Page 40](http://html1.mh-extra.com/html/dentech/ayrdyne-4-0/ayrdyne-4-0_installation-operation-and-maintenance-manual_2483474040.webp)
38
www.ayrdyne.com
ALARMS
38
This section contains basic troubleshooting guidelines. Only a qualified individual should troubleshoot
the system. For maintenance of the system, “lock out tag out” (LOTO) safety protocol applies. This means
that any time maintenance on this system is performed, the machine must be shut down, unplugged, and
tagged or labeled, explaining that maintenance is taking place.
The alarms list below is to be used as a method of troubleshooting. Alarms may differ based on system
configuration and features.
POTENTIAL CAUSE
ALARM TEXT
CORRECTIVE ACTION
• Overload tripped
Blower Motor Overload
Tripped
• Inspect motor for proper operation
• Reset the overload
• Verify motor current draw is within nameplate
parameters
• VFD Fault
Blower VFD Faulted. Check
VFD screen for fault code.
• Obtain fault codes from the VFD Settings screen
• Reference VFD manual for detailed corrective actions
•
Compressed air leak detected
•
Compressed air flow switch stuck ON
Cleaning System
Compressed Air Leak
Detected
• Inspect cleaning system for compressed air leaks
•
Inspect compressed air flow switch for proper
operation
•
Compressed air low or off
• All cleaning solenoids failed
•
Compressed air flow switch stuck OFF
Cleaning System
Compressed Air Low or Off
• Adjust or turn on compressed air
• Inspect solenoids and replace as needed
•
Inspect compressed air flow switch for proper
operation
•
Cleaning solenoid failed
•
Compressed air low or off
Cleaning System Pulse
Solenoid Failure
• Inspect solenoid and replace as needed
• Adjust or turn on compressed air
• Filters are dirty or clogged
•
Clogged or damaged tubing
Primary Filters Clogged
•
Inspect filters and replace as needed
• Unclog or repair tubing
• Filters are nearing end of life
Time to Order Primary Filters
and Schedule Service
• Order and Schedule Primary Filters Service
• Filters have reached end of life
Time to Replace Primary
Filters
• Replace Primary Filters
• Overload tripped
Rotary Valve Motor Overload
Tripped
• Lock-out tag-out
•
Clear any material from valve
• Verify proper chain tension
• Reset the overload
• Verify motor current draw is within nameplate
parameters
• Rotary Valve OFF while the system is
running
Rotary Valve Bypassed
• Place the Rotary Valve in either AUTO or HAND mode
• Valve not turning
• Sensor needs adjustment
Rotary Valve Not Turning
• Lock-out tag-out
•
Clear any material from valve
• Verify proper chain tension
•
Filter Dirty or Clogged
•
Clogged and/or damaged tubing
Secondary Filter Clogged
•
Inspect filters and replace as needed
• Unclog or repair tubing
• System not balanced
Blower Running at Limit
• Schedule System Balancing
• Remote stop button missing or pressed
Remote Stop Button Missing
or Pressed
• Install Remote Stop
• Release Remote Stop
• System is nearing maintenance due set
point
Schedule System
Maintenance
• Schedule System Maintenance
• System has reached maintenance due
set point
Perform System Maintenance
• Perform System Maintenance
3.1
TROUBLESHOOTING
Summary of Contents for AYRDYNE 4.0
Page 1: ...www ayrdyne com Installation Operation and Maintenance Manual 4 0 ...
Page 6: ...4 www ayrdyne com ...
Page 10: ...www ayrdyne com SYSTEM 8 2 1 3 MAIN SCREEN OVERVIEW 2 1 OPERATION 9 8 7 10 1 3 2 4 5 6 ...
Page 16: ...www ayrdyne com SYSTEM 14 2 1 6 SETTINGS USERS 2 1 OPERATION 1a 2 3 ci cii ciii 1b 1c 1d ...
Page 18: ...www ayrdyne com SYSTEM 16 2 1 7 SETTINGS I O 2 1 OPERATION 1 3 2 ...
Page 20: ...18 www ayrdyne com SYSTEM 2 1 OPERATION 2 1 8 SETTINGS DEVICES 5 6 7 2 3 4 1 ...
Page 22: ...www ayrdyne com FILTERS 20 2 2 1 PRIMARY INFO 2 2 OPERATION 6 1 7 8 9 2 3 4 5 ...
Page 24: ...www ayrdyne com FILTERS 22 2 2 2 PRIMARY SETTINGS 2 2 OPERATION 1 8 9 10 11 12 2 3 4 5 6 7 ...
Page 32: ...www ayrdyne com AIRFLOW 30 2 3 3 VFD SETTINGS 2 3 OPERATION 6 7 8 5 9 10 1 11 2 12 3 4 ...
Page 34: ...www ayrdyne com DISCHARGE 32 2 4 1 ROTARY VALVE IF EQUIPPED 2 4 OPERATION 1 4 2 3 5 6 ...
Page 49: ...47 www ayrdyne com NOTES ...