Chapter 5 Parameters
|
VFD-BW Series
5-72
Revision May 2009, BWE0, SW V1.05
19
Auto accel/decel failure (CFA)
20
Software/password protection (codE)
21
Emergency stop (EF1)
22
Phase-Loss
(PHL)
23
Preliminary count value attained, EF active (cEF)
24
Low current (Lc)
25
Analog feedback signal error (AnLEr)
26
PG feedback signal error (PGErr)
27
Motor overheat (oH9F)
28
Motor overheat warning (oH9L)
29
Fan Power Fault (FAnP)
30
Fan 1 Fault (FF1)
31
Fan 2 Fault (FF2)
32
Fan 3 Fault (FF3)
33
Fan 1, 2, 3 Fault (FFo)
34
Fan 1, 2 Fault (FF12)
35
Fan 1, 3 Fault (FF13)
36
Fan 2, 3 Fault (FF23)
37
Gate Drive Low Voltage Protect (Fv)
38
Error PID feedback of tension (rFbE)
39
Broken line detection of tension (rLbr)
In Pr.06-08 to Pr.06-11 the four most recent faults that occurred, are stored. After removing the
cause of the fault, use the reset command to reset the drive.
06 - 12
Low Current Detection Level
Unit: 1
Settings
00 ~ 100%
Factory Setting: 00
00
Disabled
06 - 13
Low Current Detection Time
Unit: 0.1
Settings
0.1 to 3600.0 sec
Factory Setting: 10.0
06 - 14
Low Current Detection Mode
Factory Setting: 00
Settings
00
Warn and keep operating
01
Warn and ramp to stop
02
Warn and coast to stop
03
Warn, after coast to stop, restart (delay 06-15 setting time)