Chapter 5 Parameters
|
VFD-BW Series
Revision May 2009, BWE0, SW V1.05
5-57
Settings Function
Description
00 No
Function
Any unused terminals should be programmed to 0 to
insure they have no effect on operation.
01
Multi-Step Speed Command 1
02
Multi-Step Speed Command 2
03
Multi-Step Speed Command 3
04
Multi-Step Speed Command 4
These four inputs select the multi-speed defined by
Pr.05-00 to Pr.05-14 as shown in the diagram at the end
of this table.
NOTE: Pr.05-00 to Pr.05-14 can also be used to
control output speed by programming the AC motor
drive’s internal PLC function. There are 17 step
speed frequencies (including Master Frequency and
Jog Frequency) to select for application.
05 External
Reset
(N.O.)
The External Reset has the same function as the Reset
key on the Digital keypad. After faults such as O.H.,
O.C. and O.V. are cleared this input can be used to
reset the drive.
06 Accel/Decel
Inhibit
When the command is active, acceleration and
deceleration is stopped and the AC motor drive
maintains a constant speed.
07
Accel/Decel Time Selection
Command 1 for Accel/Decel
Time 1/2
08
Accel/Decel Time Selection
Command 2 for Accel/Decel
Time 3/4
Used to select the one of four Accel/Decel Times (Pr.01-
09 to Pr.01-12, Pr.01-18 to Pr.01-21). See explanation at
the end of this table.
09
External Base Block (N.O.)
(Refer to Pr. 08-06)
10
External Base Block (N.C.)
(Refer to Pr. 08-06)
Parameter values 9, 10 program Multi-Function Input
Terminals for external Base Block control.
NOTE: When a Base-Block signal is received, the AC
motor drive will block all output and the motor will
free run. When base block control is deactivated, the
AC drive will start its speed search function and
synchronize with the motor speed, and then
accelerate to Master Frequency.
11
UP: Increment Master
Frequency
12
DOWN: Decrement Master
Frequency
Increment/decrement the Master Frequency each time
an input is received or continuously when the input stays
active. When both inputs are active at the same time, the
Master Frequency increment/decrement is halted. Please
refer to Pr.02-08, 02-09. This function is also called
“motor potentiometer”.
13 Counter
Reset
When active, the counter is reset and inhibited. To
enable counting the input should be OFF. Refer to Pr.03-
08 and 03-09.
14
Run PLC Program
To run the AC motor drive internal PLC program.
NOTE: Pr.05-00 to Pr.05-16 define the PLC program.
15 Pause
PLC
Program
When the PLC program runs, a Multi-Function Input
Terminal, when set to 15, can be used to pause the PLC
program.