Chapter 5 Parameters
|
VFD-BW Series
Revision May 2009, BWE0, SW V1.05
5-49
When the display shows c5555, the drive has counted 5,555 times. If display shows c5555
•
, it
means that real counter value is between 55,550 to 55,559.
03 - 09
Preliminary Count Value
Unit: 1
Settings
00 to 65500
Factory Setting: 00
When the counter value reaches this value, the corresponding multi-function output terminal
will be activated, provided one of Pr.03-00 to Pr.03-03 set to 15 (Preliminary Count Value
Setting). This multi-function output terminal will be deactivated upon completion of Terminal
Count Value Attained.
The timing diagram:
Terminal Count Value
(Pr. 03-00~Pr. 03-03=14)
Preliminary Count Value
(Pr. 03-00~Pr. 03-03=15)
Display
(Pr.00-04=01)
TRG
Counter Trigger
The width of trigger signal
should not be less than
2ms(<250 Hz)
2msec
2msec
Ex:03-08=5,03-09=3
03 - 11
EF Active when Preliminary Count Value Attained
Factory Setting: 00
Settings
00
Preliminary count value attained, no EF display
01
Preliminary count value attained, EF active
If this parameter is set to 01 and the desired value of counter is attained, the AC drive will treat
it as a fault. The drive will stop and show the “cEF” message on the display.
03 - 12
Fan Control
Factory Setting: 00
Settings
00
Fan always ON
01
1 minute after AC motor drive stops, fan will be OFF
02
AC motor drive runs and fan ON, AC motor drive stops and fan
OFF
03
Fan ON to run when preliminary heatsink temperature attained
This parameter determines the operation mode of cooling fan.
03 - 13
Mechanical Brake Release Frequency
Unit: 0.01
Settings
0.00 to 400.00Hz
Factory Setting: 0.00