06 - 15
Low Current Detection Restart Delay Time
Unit: 0.1
Settings
1 to 600 min
Factory Setting: 10
If output current is lower than the setting Pr.06-12 for a time that exceeds Pr.06-13 setting
during operation, the AC drive will warn per Pr.06-14 setting. If Pr.06-14 is set to 03, the AC
drive will restart after the delay time set by Pr.06-15 is up.
06 - 16
User-Defined Low-Voltage Detection Level (Lv)
Unit: 1
Settings
00
Disabled
230V: 220 ~ 300VDC (for VFD-B series)
Factory Setting: 00
460V: 440 ~ 600VDC
Factory Setting: 00
06 - 17
User-Defined Low-Voltage Detection Time
Unit: 0.1
Settings
0.1 to 3600.0 sec
Factory Setting: 0.5
When the DC BUS voltage is lower than the setting of Pr.06-16 for a time exceeding the
setting of Pr.06-17, the AC motor drive will output a signal when Pr.03-00 ~ Pr.03-03 is set to
28.
06 - 18
Reserved
06 - 19
User-Defined Low-Voltage Treatment
Factory Setting: 00
Settings
00
No
action
01
EF
active
06 - 20
Reserved
06 - 21
Reserved
06 - 22
Reserved