C h a p t e r 1 I n t r o d u c t i o n
1 - 1 5
1.8.5
Wiring
Analog
Output Channels
TP70P-22XA1R
DC/DC
converter
Voltage output
Shielded cable*1
Connected to on a
power supply module
System ground
Ground
(Impedance: Less than 100 )
VO5
IO5
AG
CH5
0mA~20mA
CH5
AG
VO4
IO4
AG
CH4
-10V ~+10V
*2
CH4
AG
+15V
-15V
AG
FE
FE
*3
0V
24V
DC24V
*4
AC motor drive, recorder,
proportioning valve.. .
Shielded cable*1
AC motor drive, recorder,
proportioning valve.. .
Current output
TP70P-21EX1R
DC/DC
converter
Shielded cable*1
Connected to on a
power supply module
System ground
Ground
(Impedance: Less than 100 )
AC motor drive, recorder,
proportioning valve.. .
Current output
IO2
AG
CH2
0mA~20mA
CH2
AG
+15V
-15V
AG
FE
*3
0V
24V
DC24V
*4
*1: Please isolate analog output cables from other power cables.
*2: If the ripple voltage of the input terminal of the load connected is large, and results in interference with the
wiring, please connect a 0.1~0.47
μ
F and 25 V capacitor.
*3: If there is much noise, please connect the terminal FE to the ground terminal.
*4: Please connect the ground terminal on a power supply module and the analog output terminal FE to the
system ground, and then ground the system ground or connect the system ground to a distribution box.