图6-6 : 更换保险丝

图6-7 : 拆解风扇模块

将风扇架四个角落的螺丝松开后,稍微拉出风扇架即可看到风扇接头,依序解开
后可将整个风扇模块拆离逆变器,以便进行清除积尘工作,请参考图6-7。

6.3 清理风扇

*组装所需的螺丝扭力:10 Kgf-cm (1N-m)

128

设备维护

Summary of Contents for RPI M50A 12s

Page 1: ...RPI M50A_12s Operation and Installation Manual Grid tie Transformerless Solar Inverter The power behind competitiveness www deltaww com English 1 75 149...

Page 2: ......

Page 3: ...ection 3 Phase PE or 3 Phase N PE 4 2 1 Required Protective Devices and Cable Cross sections 4 2 2 Permitted earthing systems 4 3 DC Connection from PV Array 4 4 Communication Module Connections 4 4 1...

Page 4: ...P 5 2 9 3 Q V 5 2 9 4 Q T 5 2 10 FRT Fault ride through 6 Maintenance 6 1 Replace Surge Protection Device SPD 6 2 Replace Internal String Fuse 6 3 Clean Fan 6 4 Replace Fan 6 5 Clean Air Inlets 7 Err...

Page 5: ...Rubber ring Figure 4 6 DC Wiring illustration Figure 4 7 Communication module Figure 4 8 Multi inverter connection illustration Figure 4 9 EPO functions Figure 4 10 EPO Digital input parallel connecti...

Page 6: ...igure 5 33 FRT page Figure 5 34 FRT Parameters Figure 6 1 Remove Reassemble front cover Figure 6 2 Recognize the connectors Figure 6 3 Loosen the 6 screws Figure 6 4 Pull out the SPD unit Figure 6 5 P...

Page 7: ...ng of input power Table 4 6 Cable size Table 4 7 Definition of RS 485 pin Table 4 8 Terminal resister setting Table 4 9 Definition of digital input EPO functions Table 5 1 LED indicator Table 5 2 Dry...

Page 8: ...ures and the device surface can become hot Sufficient cooling time is necessary for optimal yield Machine and equipment damage may occur if this hazardous situation is not avoided CAUTION WARNING Deat...

Page 9: ...n as the Figure 1 1 Inverters convert the DC input power supplied from the PV Array into 3 phase AC output power to Grid Figure 1 1 Solar system operation illustration For more detailed or other relat...

Page 10: ...are in the package The standard accessories are shown in following tables and figures Please refer to Figure 2 2 and Table 2 1 Check the model number and the serial number on the packaging is identica...

Page 11: ...lation specification etc 3 AC Plug Mounting Bracket Connector for AC connection Wall mounting bracket to mount the solar inverter on the wall 4 5 DC Plug 12 sets Connector for DC connection 6 Rubber r...

Page 12: ...the model number and the specifications by the information on the label For more detail information please see the Table 2 2 Figure 2 3 Product label Model Name Part Number RPI503M221000 SPD Internal...

Page 13: ...wn in Figure 2 5 Figure 2 4 Inverter s exterior objects 2 4 Exterior Objects Figure 2 5 Input output interface AC Connector 380 400Vac 3Ph Fan 5 Manual Switch String1 String2 String3 Communication RS...

Page 14: ...Please refer to Figure 3 3 Upper 6 screws must be locked at least 2 Attach the inverter to the mounting bracket 3 Fix the inverter with 2 M6 Phillips head screws Please refer to Figure 3 4 3 Installat...

Page 15: ...installed this way Protection cover CAUTION To avoid malfunction of inverter caused by extreme weather ex snow hail etc or non proper installation maintenance an additional protection cover is strongl...

Page 16: ...Figure 3 4 Attach to the bracket and fasten with screws 14 30 3 30 97 8 192 8 129 M6 Screw 6 M6 Screw 6 Wall Figure 3 3 Screw the mounting bracket 16 Installation...

Page 17: ...ion which offers non obscured and safe access in turn ensuring easy access for service and maintenance Please leave an appropriate gap in between units when installing several solar inverter systems a...

Page 18: ...ing 4 1 Preparation Before Wiring Models with Fuses WARNING SHOCK HAZARD Whenever a PV array is exposed to sunlight a shock hazard may exist due to output wires or exposed terminals To reduce the risk...

Page 19: ...Figure 4 1 Floating string with separate connection 1 2 3 4 L1 L2 L3 N PE Communication Wiring 1 2 3 AC Wiring DC Wiring Must be Separate PV strings RPI M50A can support 3P3W system RPI M50A 19 Wiring...

Page 20: ...te that the following value is provided to identified and checked the justification for field wiring instead of the DC current rating of inverter M50A is not suitable to connected with PV combiner box...

Page 21: ...for each wire is necessary if 25mm2 or 3AWG is applied End sleeve is not able to be installed if 1AWG is applied Model Upstream circuit breaker RPI M50A_12s 100A Model Current Rating Recommended Torqu...

Page 22: ...Striping the wires Make sure to choose proper size for AC cable Failed to follow these instructions may cause AC plug damage AC plug s installation must meets the local electrical code If there is any...

Page 23: ...cases To ensure a safe and reliable contact always perform the following work steps Use a conductor cross section at least one number larger due to the lower current carrying capacity Keep the install...

Page 24: ...sitive or negative phase of wire In other words the sequence of L1 L2 L3 can be adjusted arbitrarily According to the diameter of the cable choose the combination of rubber ring D1 or D1 D2 or D1 D2 D...

Page 25: ...to separate Part B and D Refer to Table 4 4 to take out Part C Choose the appropriate rubber ring 4 Insert the internal wire into AC plug L1 L2 N PE L3 A B C C D D 1 The packing has the parts of AC P...

Page 26: ...emble Part A to B In the meantime hold the cable when tighten the part B 7 Tighten the part B with part D by the instruction of Table 4 4 For example For the case of cable with 38mm2 CV diameter is 25...

Page 27: ...0 Vac 20 After wiring installer should choose the AC connection type on the control panel About setting please refer to 5 2 7 Install Settings TT is not recommended The voltage of N has to be very clo...

Page 28: ...n circuit voltage of PV Array Rated current short circuit current of PV Array The input power to the inverter should not higher than the rated power shown in Table 4 5 CAUTION WARNING When undertaking...

Page 29: ...tion The module provides VCC RS 485 dry contact EPO and Digital Input terminals for different use Please use cable with outer diameter lie between 20 AWG 0 5mm to secure the space IP65 4 4 Communicati...

Page 30: ...n Figure 4 8 only the last inverter s terminal resistor must be switched ON Please refer to Table 4 8 for the terminal resister setting Pin Function 1 VCC 12V 2 GND 3 DATA 4 DATA 5 DATA 6 DATA Table 4...

Page 31: ...t function K1 K6 Please refer to Table 4 9 for the digital input setting It have to disable the function of Active Reactive power P F and P U when digital input setting is working The suitable electri...

Page 32: ...the connection SW INV_1 VCC V1 K0 EPO K1 0 Power K2 30 Power K3 60 Power K4 100 Power K5 K6 INV_2 VCC V1 K0 EPO K1 0 Power K2 30 Power K3 60 Power K4 100 Power K5 K6 INV_N VCC V1 K0 EPO K1 0 Power K2...

Page 33: ...ized by users please refer to section 5 2 7 5 Dry Contact The dry contact port can withstand with 250Vac 28Vdc 9A and suitable electric wire is 20 AWG 0 5mm Figure 4 11 Dry contact port Assignments 4...

Page 34: ...gs LCD panel will change the display cursor from to Power Meter Energy Log Event Log Inverter Information General Settings Install Settings Active Reactive Power FRT 5 2 2 5 2 3 5 2 4 5 2 5 5 2 6 5 2...

Page 35: ...according to your region and make sure that there is no any error fault or warning showing on home page Now you can feed in DC power and wait for inverter initially self test about 2 minutes If there...

Page 36: ...ure 5 3 Home page When inverter is operating normally the LCD will display the homepage as shown in Figure 5 3 user can get the information about output power inverter status E today date and time Pre...

Page 37: ...2 2013 15 30 No Gird 2 19 02 2013 09 30 AC Volt Low 5 20 02 2013 15 30 AC Freq High or or EXIT EXIT EXIT EXIT ENT ENT ENT ENT ENT ENT Figure 5 6 Event log Page 5 2 4 Event Log User can view the invert...

Page 38: ...ll Settings 5 2 8 Active Reactive power and 5 2 9 FRT Fault ride through Figure 5 7 Inverter information page 5 2 5 Inverter Information S N RN11179CB0 Install 30 04 2014 DSP 1 80 Red 1 65 Comm 1 65 I...

Page 39: ...h Deutsch Fran ais Italiano Espa ol Nederlands Language Date and Time Baud Rate Protocol Language Date and Time Baud Rate Protocol 9600 19200 38400 Language Date and Time Baud Rate Protocol Delta Soli...

Page 40: ...EPO AC Connection Max Power Manufacturer Level All Settings Installer Level Inverter ID Insulation Country Grid Settings Dry Contact EPO AC Connection Max Power Figure 5 9 Install settings page Figure...

Page 41: ...r must select the appropriate method based on PV array s wiring Each country has its own electricity regulations Installer must select the country correctly Inverter ID 002 Insulation Country Grid Set...

Page 42: ...V 259 0V Hi Off Sl T Lo Off Slow Lo On Slow Lo Off Sl T 600 0s 184 0V 219 0V 1 0s Voltage Protection Freq Protection Reconnect T P Ramp Up High Off High On High Off T Low Off 51 50Hz 50 05Hz 0 1s 47 5...

Page 43: ...or warning occurs Any Error occurs Any Fault occurs Setting Disable On Grid Fan Fail Insulat Alarm Error Fault Any Warning occurs Warning Table 5 2 Dry Contact Trigger Setting Figure 5 14 Dry Contact...

Page 44: ...e select the correct AC wiring type Electricity regulation in some area requests that inverter must have power limit function In these areas users can adjust Max Power to limit the maximum output powe...

Page 45: ...ol mode can reduce the output power to a percentage of inverter s rated power Users can limit the output power by set the Set Point in Power Limit page Inverter will reduce output power when grid freq...

Page 46: ...V lock in and inverter s present output power is greater than lock in power P lock in inverter will reduce the output power and keep it at a certain value P lock out until grid voltage drop back to lo...

Page 47: ...the lock in voltage V lock in inverter will enable cosphi P function automatically and disabled it when grid voltage reach lock out voltage V lock out Constant cosphi Cosphi P Constant Q Q V Mode cosp...

Page 48: ...ock out power to assign Q V function operation interval Constant cosphi Cosphi P Constant Q Q V Mode Fix Q OFF Ind 90 EXIT ENT Constant cosphi Cosphi P Constant Q Q V Mode V1s V2s Qs limit OFF 248 4V...

Page 49: ...the information of each control modes Q setting point Q P Q V Q T 5 2 9 Q setting 24 7 In Q setting point user can assign a percentage of reactive power to the inverter Figure 5 30 Q setting point pa...

Page 50: ...tive Pwr FRT Mode Dead Band Vdrop t1 OFF 10 0 0 30s U1 t3 K factor 20 3 00s 2 0 Warning Adj would affect energy production Password EXIT EXIT EXIT ENT ENT Figure 5 33 FRT page Figure 5 34 FRT Paramete...

Page 51: ...spikes e g struck by lighting SPD will protect the inverter and got damaged If you find a warning message SPD Fail shown on display panel please follow the steps below to replace the SPD 1 Switch AC...

Page 52: ...cognize the connectors Remove Reassemble Reassemble Remove Remove Reassemble Reassemble Remove Remove Reassemble Reassemble Remove Remove Reassemble Reassemble Remove Remove Reassemble Reassemble Remo...

Page 53: ...Figure 6 3 Loosen the 6 screws Figure 6 4 Pull out the SPD unit Screw torque required for assembling 8 Kgf cm 0 8N m 53 Maintenance...

Page 54: ...ont cover Figure 6 1 3 Pull out the fuse holder and check the fuse Figure 6 5 4 Replace the fuse if necessary Figure 6 6 5 Reassemble the inverter Please be careful the waterproof tape for ensure the...

Page 55: ...ling fan panel Loosen the 4 screws shown in Figure 6 7 Once the screws are loose pulling the fan bracket out will expose the connectors Each fan has one wire connected 6 3 Clean Fan Screw torque requi...

Page 56: ...s around the fans and disconnect the connector right behind the fan bracket Then replace new fan and reassemble the 4pcs screws Unscrew the 4 screws of air inlets and clean them regularly 6 5 Clean Ai...

Page 57: ...lity voltage is under the UVR setting 2 Incorrect country or Grid setting 3 Wrong connections in AC plug 4 Detection circuit malfunction 1 Check the utility voltage connection to the inverter terminal...

Page 58: ...uit inside the inverter HW FAN W11 1 One or more fans are locked 2 One or more fans are defective 3 One ore more fans are disconnected 4 Detection circuit malfunction 1 Remove the object that stuck in...

Page 59: ...8 1 Ambient temperature 90 or 30 2 Detection circuit malfunction 1 Check the installation ambient and environment 2 Check the detection circuit inside the inverter HW NTC3 Fail F09 1 Ambient temperatu...

Page 60: ...iary circuitry inside the inverter 3 Check the detection circuit inside the inverter HW Red ADC1 F18 HW Red ADC2 F19 HW Eff F20 1 The calibration is incorrect 2 Current feedback circuit is defective 1...

Page 61: ...und 3 Driver for boost is defective or disconnected 4 Detection circuit malfunction 1 Check the inputs connections 2 Check the PV Array insulation 3 Check the driver circuit for boost inside the inver...

Page 62: ...nverter stage 3 Check the detection circuit inside the inverter The detection circuit for synchronal signal malfunction Check the detection circuit for synchronal signal inside the inverter HW AC OCR...

Page 63: ...Switch off AC circuit breaker to disconnect with electricity grid Switch off the PV array switch to disconnect from the PV array Use proper voltmeter to confirm that the AC and DC power are disconnec...

Page 64: ...nvironmental category Outdoor wet locations Protection degree IP65 Electronics Pollution degree II Overvoltage category AC output III DC Input II Maximum backfeed current to the array 0 Class I metal...

Page 65: ...2A Nominal power 50kW 50kVA Maximum power 55kW 55kVA Refer to Figure 9 1 to 9 3 73A 230Vac 76A 220Vac Maximum current 80A Inrush current 200A 100 s Maximum output fault current rms 106 4A 91 2A Rated...

Page 66: ...s record 2 RS 485 connections EN 61000 3 11 CE conformity Yes Grid interface VDE0126 1 1 VDE AR N 4105 BDEW UK G59 3 UTE C15 712 NB T 32004 Emission EN 61000 6 3 Harmonics EN 61000 3 12 EN 61000 6 2 C...

Page 67: ...Figure 9 1 M50A Efficiency Curve Efficiency Pn 50kW Efficiency of M50A Output voltage at 400Vac 10 20 40 80 60 90 91 92 93 94 95 96 97 98 99 100 520V 600V 800V Output Power 100 110 67 Technical Data...

Page 68: ...Thermal Derating Curve cos 1 0 50 55 60 65 70 75 80 85 90 95 100 105 110 115 25 30 35 40 45 50 55 60 Temperature Derating of RPI M50A P Pn Pn 50kW Cos 1 0 Ambient Temperature 520Vdc 600Vdc 800Vdc 68...

Page 69: ...Curve cos 0 95 50 55 60 65 70 75 80 85 90 95 100 105 110 115 25 30 35 40 45 50 55 60 Temperature Derating of RPI M50A S 520Vdc P 520Vdc S 600Vdc P 600Vdc S 800Vdc P 800Vdc P Pn Pn 50kW Cos 0 95 Ambie...

Page 70: ...Curve cos 0 9 50 55 60 65 70 75 80 85 90 95 100 105 110 115 25 30 35 40 45 50 55 60 Temperature Derating of RPI M50A S 520Vdc P 520Vdc S 600Vdc P 600Vdc S 800Vdc P 800Vdc P Pn Pn 50kW Cos 0 9 Ambien...

Page 71: ...Voltage Derating Curve cos 1 0 Input Voltage P Pn Pn 50kW 10 20 30 40 50 60 70 80 90 100 110 0 200 400 600 520 800 1000 V AMB 40 C AMB 25 C AMB 45 C AMB 50 C AMB 55 C Input Voltage Derating of RPI M5...

Page 72: ...els maximum power can not exceed this I V curve If the user uses an external fuse the user shall ensure that the fuse at 1000Vdc above fusing characteristics Appendix Appendix A I V curve limitation A...

Page 73: ...ote NO Location Screw torque 5 SPD board 8 Kgf cm 0 8N m 4 Fans 8 Kgf cm 0 8N m 2 Air inlet 8 Kgf cm 0 8N m 3 Fan panel 8 Kgf cm 0 8N m 1 Front cover 10 Kgf cm 1N m Appendix B 1 Assembly Note 1 Append...

Page 74: ...on cover 8 Kgf cm 0 8N m 20 AWG 0 5mm 12 10AWG 4 6mm Appendix B 2 Assembly Note 2 D1 D2 D3 PV KST 4 6 PV KBT 4 6 2 AC plug 60 80 kgf cm 5 9 7 8N m 6 Communication module 3 Rubber rings D1 66 204 Kgf c...

Page 75: ...RPI M50A_12s The power behind competitiveness www deltaww com English 1 75 149...

Page 76: ...3 2 4 3 4 4 1 DC 4 2 AC 3P PE 3P N PE 4 2 1 AC 4 2 2 4 3 4 4 4 4 1 RS 485 4 4 2 4 4 3 5 5 1 LCD 5 2 5 2 1 5 2 2 Power Meter 5 2 3 Energy Log 5 2 4 Event Log 5 2 5 Inverter Information 5 2 6 General Se...

Page 77: ...Cosphi P 5 2 8 6 Constant Q 5 2 8 7 Q V 5 2 9 Q setting 24 7 5 2 9 1 Q setting point 5 2 9 2 Q P 5 2 9 3 Q V 5 2 9 4 Q T 5 2 10 FRT Fault ride through 6 6 1 SPD 6 2 DC 6 3 6 4 6 5 7 8 9 A I V curve l...

Page 78: ...Power meter 5 5 Energy log 5 6 Event log 5 7 Inverter information 5 8 General settings 5 9 Install settings 5 10 Inverter ID 5 11 Insulation 5 12 Country 5 13 Grid Settings 5 14 Dry Contact Figure 82...

Page 79: ...hi P 5 26 Constant Q 5 27 Q V 5 28 Q V 5 29 Q setting 24 7 5 30 Q setting point 5 31 Q P 5 32 Q T 5 33 FRT 5 34 FRT 6 1 6 2 6 3 6 4 SPD 6 5 6 6 6 7 6 8 6 9 9 1 M50A 9 2 M50A cos 1 0 9 3 M50A cos 0 95...

Page 80: ...Table 2 1 M50A 2 2 4 1 4 2 4 3 AC 4 4 4 5 4 6 4 7 RS 485 4 8 4 9 EPO 5 1 LED 5 2 7 1 7 2 7 3 9 1 RPI M50A B 1 1 B 2 2 84 85 93 94 94 97 101 101 103 104 104 108 116 130 131 132 137 146 147 80...

Page 81: ...81...

Page 82: ...PI M50A solar inverter PV array stand alone 1 1 1 1 RPI M50A http www deltaww com 1 1 1 1 2 1 3 PV Array Electrical Grid Solar Inverter 3PH AC Distribution box Surge arrestor AC breaker 3 phase N PE 8...

Page 83: ...2 1 RPI M50A 2 1 2 2 2 1 2 2 1 2 2 83...

Page 84: ...2 2 M50A RPI M50A 1 1 pc 1 pc 1 pc 1 pc RPI 2 3 AC AC 4 5 1 5mm x 4 6 DC 12 DC 2 1 M50A 1000V 1A Midget 84...

Page 85: ...2 3 2 3 RPI503M221000 DC RPI M50A_12s 2 2 2 3 85...

Page 86: ...n 5 Manual Switch String1 String2 String3 Communication RS 485 2 EPO 1 Dry Contact 2 Digital Input 6 DC1 DC2 String10 String11 String12 String4 String5 String6 String7 String8 String9 Display Air inle...

Page 87: ...AC DC 1 12 M6 3 3 6 2 3 2 M6 3 4 12 6 5 460 0 400 0 82 0 82 0 82 0 82 0 82 0 25 0 14 1 127 7 31 0 4 R10 0 30 0 105 3 3 1 87...

Page 88: ...3 2 90 Not Recommended Not Recommended Keep 30 cm from floor and water if installed this way 88...

Page 89: ...3 3 3 4 14 30 3 30 97 8 192 8 129 M6 Screw 6 M6 Screw 6 Wall 89...

Page 90: ...3 5 3 5 25 60 3 6 30cm 20cm 50cm 30cm 30cm 90...

Page 91: ...M50A DC 15A DC 10A 4 1 MC4 DC AC DC DC insulation 5 2 7 Install Settings 4 4 1 DC OFF E34 L1 L2 L3 N 91...

Page 92: ...4 1 DC 1 2 3 4 L1 L2 L3 N PE Communication Wiring 1 2 3 AC Wiring DC Wiring Must be Separate PV strings RPI M50A can support 3P3W system RPI M50A 92...

Page 93: ...M50A M50A Note for Field Wiring M50A 16A 4 2 4 1 4 2 RPI M50A_12s 16A 93...

Page 94: ...phase N and PE M50A 1AWG M50A 25mm2 3AWG Model Upstream circuit breaker RPI M50A_12s 100A 100 A RPI M50A_12s 3 N m G N L1 L3 L2 N L1 L2 L3 PE To solar inverter AC plug 4 2 4 3 AC 25 38mm2 3 1AWG 37 4...

Page 95: ...4 3 AC AC AC 95mm 22 2mm L1 L2 L3 N PE 22 2mm 95 mm 0 5 95...

Page 96: ...AC 4 4 AC Plug 4 4 1 2 3 4 5 96...

Page 97: ...D1 D2 D3 P D1 6 5 20 30 8 44 7 1 7 5 D2 11 17 26 8 35 4 1 6 D3 13 14 21 9 27 6 1 3 5 12 25 3 5 D3 38 P 94 P 95 L1 L2 L3 mm N m mm 4 4 4 5 97...

Page 98: ...1 AC AC 55kgf cm 75kgf cm 2 A B 3 B B D 4 4 4 L1 L2 L3 N PE D1 D2 D3 L1 L2 N PE L3 A B C C D D A B C D 98...

Page 99: ...O 5 3 3N M 6 A B B 7 4 4 B D 38 2CV 25 12N m 99...

Page 100: ...AC L1 L2 400 Vac 20 L1 N 230 Vac 20 L1 L3 400 Vac 20 L2 N 230 Vac 20 L2 L3 400 Vac 20 L3 N 230 Vac 20 AC AC 5 2 7 Install Settings N PE 20Vrms TT TN S Yes TN C Yes TN C S Yes TT Yes IT No 4 2 2 100...

Page 101: ...RPI M50A 58 kW DC1 DC2 35 kW 4 5 DC1 string TDC2 string Voc 1000Vdc 4 5 PV Array 4 6 4 3 RPI M50A_12s DC 15A 4 6 mm2 12 10 AWG 4 6 DC DC 4 6 PV KST 4 6 PV KBT 4 6 101...

Page 102: ...4 7 RPI M50A 4 7 VCC RS 485 20 AWG 0 5mm 4 4 Dry Contact VCC RS 485 EPO 1 Digital Inputs 6 Terminal Resistor 102...

Page 103: ...ction 1 VCC 12V 2 GND 3 DATA 4 DATA 5 DATA 6 DATA 4 7 RS 485 4 8 4 4 1 RS 485 Data Format Baud rate 9600 19200 default or 38400 Data bits 8 Stop bit 1 Parity N A RS485 USB or RS485 RS232 Terminal Resi...

Page 104: ...Terminal Resistor OFF OFF ON 4 8 4 9 EPO 4 9 EPO 30 60 100 V1 K0 V1 K1 V1 K2 V1 K3 V1 K4 V1 K5 V1 K6 4 4 2 RPI M50A EPO Install Settings 5 2 7 6 EPO 6 K1 K6 4 9 digital input Active Reactive power PF...

Page 105: ...CC V1 K0 EPO K1 0 Power K2 30 Power K3 60 Power K4 100 Power K5 K6 INV_2 VCC V1 K0 EPO K1 0 Power K2 30 Power K3 60 Power K4 100 Power K5 K6 INV_N VCC V1 K0 EPO K1 0 Power K2 30 Power K3 60 Power K4 1...

Page 106: ...4 11 4 4 3 RPI M50A 2 5 2 7 5 Dry Contact 250Vac 28Vdc 9A 20 AWG 0 5mm Dry Contact B Dry Contact A 106...

Page 107: ...Inverter Information General Settings Install Settings Active Reactive Power FRT 5 2 2 5 2 3 5 2 4 5 2 5 5 2 6 5 2 7 5 2 8 5 2 9 5 1 5 5 1 LCD 70 LED Indicator RED LED Indicator GRN EXIT Exit Menu Do...

Page 108: ...5 2 Are you sure to set country XXX Yes No AU NZ LV AU NZ MV AU NZ AU NZ PL 4 99k Select Language English Deutsch Fran ais Setting ID ID 002 Are you sure to set ID 001 Yes No Delta Solivia prot Sunsp...

Page 109: ...tatus Power E Today 7935 192 W kWh On Grid Today Energy Inverter Status Output Power Day Time or or ENT ENT V 400 400 400 I 11 5 11 5 11 5 P V A W 2645 2645 2645 L1 L2 L3 AC PF Power Frequency E Today...

Page 110: ...d Report Error Events Grid Report 1 20 02 2013 15 30 No Gird 2 19 02 2013 09 30 AC Volt Low 5 20 02 2013 15 30 AC Freq High or or EXIT EXIT EXIT EXIT ENT ENT ENT ENT ENT ENT Meter Energy Log Event Log...

Page 111: ...r Information S N RN11179CB0 Install 30 04 2014 DSP 1 80 Red 1 65 Comm 1 65 ID 002 Country Insulation Baud Rate Germany MV 250k 19200bps FRT Settings EPO Grid Settings Active Pwr Settings React Pwr Se...

Page 112: ...erlands Language Date and Time Baud Rate Protocol Language Date and Time Baud Rate Protocol 9600 19200 38400 Language Date and Time Baud Rate Protocol Delta Solivia prot Sunspec prot EXIT EXIT ENT EXI...

Page 113: ...Inverter ID Insulation Country Dry Contact EPO AC Connection Max Power Manufacturer Level All Settings Installer Level Inverter ID Insulation Country Grid Settings Dry Contact EPO AC Connection Max P...

Page 114: ...Insulation Country Grid Settings AU NZ Austria Belgium China EXIT ENT 5 2 7 2 Insulation 5 2 7 3 Country Inverter ID 002 Insulation Country Grid Settings Mode ON Resistance 250k ON Plus Grounded Minu...

Page 115: ...tion Freq Protection Reconnect T P Ramp Up High Off High On High Off T Low Off 51 50Hz 50 05Hz 0 1s 47 50Hz Low On Low Off T Hi Off Slow Hi On Slow 47 55Hz 0 1s 65 00Hz 64 95Hz Hi Off Slow T Lo Off Sl...

Page 116: ...4 Dry Contact 5 2 7 5 Dry Contact EXIT EXIT EXIT EXIT EXIT ENT ENT ENT ENT ENT ENT ENT DC Injection Dry Cont RCMU EPO ON Normal Close Alarm Error Fault Warning Disable On Grid Fan Fail Insulat Dry Con...

Page 117: ...Injection Dry Contact RCMU EPO ON Normal Close 5 15 EPO 5 16 AC 5 17 Max Power AC Connection Anti islanding Max Power Return to Factory 3P4W ON 55000W AC Connection Anti islanding Max Power Return to...

Page 118: ...Power Limit Power vs Frequency P V Mode Set Point ON 100 EXIT ENT Power Limit Power vs Frequency P V Mode F start F recovery Gradient ON 50 20 Hz 50 20 Hz 40 T recovery 300s EXIT EXIT ENT Active Powe...

Page 119: ...Others f recovery fprotection fprotection 5 21 Power vs Frequency 5 22 P V V lock in P lock in P lock out V lock out T recovery Power Limit Power vs Frequency P V Mode P lock in P lock out V lock in...

Page 120: ...s P lower P upper 5 25 Cosphi P 5 2 8 4 Constant cosphi 5 2 8 5 Cosphi P Constant cosphi Cosphi P Constant Q Q V Mode cosphi OFF Ind 1 000 EXIT ENT Constant cosphi Cosphi P Constant Q Q V Mode Q upper...

Page 121: ...6 Constant Q 5 2 8 7 Q V Constant cosphi Cosphi P Constant Q Q V Mode V1s V2s Qs limit OFF 248 4V 253 0V Ind 44 V1i V2i Qi limit T delay 211 6V 207 0V Cap 44 10 00s P lock in P lock out 20 5 EXIT EXI...

Page 122: ...P lower Q lower OFF Ind 0 45 Ind 44 Q setting point Q P Q V Q T P upper V lock in V lock out 100 249 3V 304 7V EXIT EXIT ENT 5 29 Q setting 24 7 Q setting 24 7 Q setting point Q P Q V Q T Q setting p...

Page 123: ...0s 2 0 Warning Adj would affect energy production Password EXIT EXIT EXIT ENT ENT 5 33 FRT 5 34 FRT FRT 5 2 10 FRT Fault ride through 100 U1 0 t1 Fault occurrence t3 time Ugrid Unom Umin Udrop Disconn...

Page 124: ...RPI M50A_12s AC DC PV Inverter 6 6 1 SPD AC DC SPD Fail 1 AC DC 2 6 1 3 6 2 4 6 3 5 SPD 6 4 6 7 8 6 1 10Kgf cm 124...

Page 125: ...6 1 6 2 125...

Page 126: ...6 3 6 4 SPD 8 Kgf cm 0 8N m 126...

Page 127: ...6 5 4 6 6 5 6 5 6 2 DC Item String Fuse source 2 Part number 10GPV15U0 Rate amp 15 A Rate voltage 1000 V Manufacturers Hollyland Item String Fuse source 1 Part number 0SPF015 T Rate amp 15 A Rate volt...

Page 128: ...6 6 6 7 6 7 6 3 10 Kgf cm 1N m 128...

Page 129: ...6 8 6 9 6 9 4 6 5 6 4 8 Kgf cm 0 8N m 8 Kgf cm 0 8N m 129...

Page 130: ...E15 E20 AC Volt High E11 E13 E16 E18 E21 E23 Solar1 High E30 1 2 3 1 2 3 1 AC 2 1 AC 2 AC 1 2 3 AC 4 1 2 3 4 1 Solar1 1000Vdc 2 1 2 3 1 2 3 1 AC 2 1 AC 2 AC 1 2 3 AC 4 1 2 3 4 1 solar array Voc 1000V...

Page 131: ...AN W11 SPD Fail 7 2 1 2 3 1 2 3 1 Solar1 2 Solar1 0 3 1 Solar2 2 Solar1 0 3 1 2 3 4 1 2 SPD 3 SPD 4 1 Solar1 2 boost1 3 1 Solar2 voltage 2 boost2 3 1 2 3 4 1 2 SPD 3 SPD 4 De rating W07 1 2 3 4 P F 5...

Page 132: ...TC1 Fail F06 HW NTC2 Fail F08 HW NTC3 Fail F09 HW NTC4 Fail F10 HW RLY F13 HW DSP ADC1 F15 1 2 1 60 2 1 30 2 1 90 30 2 1 90 30 2 1 90 30 2 1 90 30 2 1 2 3 1 2 3 1 2 1 2 1 2 RTM1 RTB1 RTG1 and RTH1 1 2...

Page 133: ...HW COMM1 F23 HW COMM2 F22 Ground Cur F24 1 2 3 1 2 3 1 2 3 1 2 3 1 2 1 DSP 2 3 1 Red CPU 2 1 2 3 Boost Boost 4 1 150Vdc 2 3 1 150Vdc 2 3 1 150Vdc 2 3 1 150Vdc 2 3 1 2 1 DSP reset crystal 2 DSP COMM 3...

Page 134: ...gh F36 F37 F38 F39 F40 F41 HW CT A Fail F42 1 2 1 RCMU 2 1 2 driver 1 2 3 Vgrid Vout 1 2 3 Boost 4 1 Boost 2 Voc 1000Vdc 3 4 1 2 Inverter stage 3 4 1 2 CSC1 3 1 2 1 RCMU 2 1 2 1 2 3 Vgrid Vout 1 2 3 b...

Page 135: ...OCR F45 HW ZC Fail F50 DC Cur High F60 F61 F70 F71 7 3 1 2 CSC2 3 1 2 CSC3 3 1 2 3 1 Boost 2 Boost 3 1 WC3 CNC16 2 CSC2 3 1 WC3 CNC16 2 CSC3 3 1 2 inverter stage 3 1 boost 2 boost 3 Ext Comm Fail F74...

Page 136: ...8 Manual Switch OFF AC voltmeter AC DC AC DC RS 485 136...

Page 137: ...tdoor wet locations IP65 Electronics II AC output III DC Input II 0 Class I metal enclosure with protective earth 612 740 278mm Weather resistant connectors 58kW 52 5kW 63kW 600Vdc 200Vdc 1000 Vdc 250...

Page 138: ...50 60Hz Programmable 45Hz 65Hz 3 0 99 full power Adjustable 0 80 leading 0 80 lagging 0 5 rated current 2W 3 Ph N PE 3 phase AC plug that meets IP67 and specifications in table 4 2 98 6 98 4 Grid sid...

Page 139: ...3 11 CE conformity Yes Grid interface VDE0126 1 1 VDE AR N 4105 BDEW UK G59 3 UTE C15 712 NB T 32004 Emission EN 61000 6 3 Harmonics EN 61000 3 12 EN 61000 6 2 CS Immunity PFMF IEC 61000 4 2 IEC 6100...

Page 140: ...9 1 M50A Efficiency Pn 50kW Efficiency of M50A Output voltage at 400Vac 10 20 40 80 60 90 91 92 93 94 95 96 97 98 99 100 520V 600V 800V Output Power 100 110 140...

Page 141: ...9 2 M50A cos 1 0 50 55 60 65 70 75 80 85 90 95 100 105 110 115 25 30 35 40 45 50 55 60 Temperature Derating of RPI M50A P Pn Pn 50kW Cos 1 0 Ambient Temperature 520Vdc 600Vdc 800Vdc 141...

Page 142: ...os 0 95 50 55 60 65 70 75 80 85 90 95 100 105 110 115 25 30 35 40 45 50 55 60 Temperature Derating of RPI M50A S 520Vdc P 520Vdc S 600Vdc P 600Vdc S 800Vdc P 800Vdc P Pn Pn 50kW Cos 0 95 Ambient Tempe...

Page 143: ...os 0 9 50 55 60 65 70 75 80 85 90 95 100 105 110 115 25 30 35 40 45 50 55 60 Temperature Derating of RPI M50A S 520Vdc P 520Vdc S 600Vdc P 600Vdc S 800Vdc P 800Vdc P Pn Pn 50kW Cos 0 9 Ambien Temperat...

Page 144: ...9 5 M50A cos 1 0 Input Voltage P Pn Pn 50kW 10 20 30 40 50 60 70 80 90 100 110 0 200 400 600 520 800 1000 V AMB 40 C AMB 25 C AMB 45 C AMB 50 C AMB 55 C Input Voltage Derating of RPI M50A 144...

Page 145: ...IV 1000Vdc A I V A I V curve limitation 145 A I V curve limitation...

Page 146: ...B B 1 1 NO 5 SPD board 8 Kgf cm 0 8N m 4 Fans 8 Kgf cm 0 8N m 2 Air inlet 8 Kgf cm 0 8N m 3 Fan panel 8 Kgf cm 0 8N m 1 Front cover 10 Kgf cm 1N m 146 B...

Page 147: ...n cover 8 Kgf cm 0 8N m 20 AWG 0 5mm 12 10AWG 4 6mm D1 D2 D3 PV KST 4 6 PV KBT 4 6 2 AC plug 60 80 kgf cm 5 9 7 8N m 6 Communication module 3 Rubber rings D1 66 204 Kgf cm 6 5 20N m D2 112 173 Kgf cm...

Page 148: ......

Page 149: ...RPI M50A_12s The power behind competitiveness www deltaww com English 1 75 149...

Page 150: ...2 2 2 3 2 4 3 4 4 1 DC 4 2 AC 3P PE 3P N PE 4 2 1 AC 4 2 2 4 3 4 4 4 4 1 RS 485 4 4 2 4 4 3 5 5 1 LCD 5 2 5 2 1 5 2 2 Power Meter 5 2 3 Energy Log 5 2 4 Event Log 5 2 5 Inverter Information 5 2 6 Gen...

Page 151: ...Cosphi P 5 2 8 6 Constant Q 5 2 8 7 Q V 5 2 9 Q setting 24 7 5 2 9 1 Q setting point 5 2 9 2 Q P 5 2 9 3 Q V 5 2 9 4 Q T 5 2 10 FRT Fault ride through 6 6 1 SPD 6 2 DC 6 3 6 4 6 5 7 8 9 A I V curve li...

Page 152: ...ter 5 5 Energy log 5 6 Event log 5 7 Inverter information 5 8 General settings 5 9 Install settings 5 10 Inverter ID 5 11 Insulation 5 12 Country 5 13 Grid Settings 5 14 Dry Contact Figure 156 157 158...

Page 153: ...hi P 5 26 Constant Q 5 27 Q V 5 28 Q V 5 29 Q setting 24 7 5 30 Q setting point 5 31 Q P 5 32 Q T 5 33 FRT 5 34 FRT 6 1 6 2 6 3 6 4 SPD 6 5 6 6 6 7 6 8 6 9 9 1 M50A 9 1 M50A cos 1 0 9 2 M50A cos 0 95...

Page 154: ...Table 2 1 M50A 2 2 4 1 4 2 4 3 AC 4 4 4 5 4 6 4 7 RS 485 4 8 4 9 EPO 5 1 LED 5 2 7 1 7 2 7 3 9 1 RPI M50A B 1 1 B 2 2 158 159 167 168 168 171 175 175 177 178 178 182 190 204 205 206 211 220 221 154...

Page 155: ...155...

Page 156: ...PI M50A solar inverter PV array stand alone 1 1 RPI M50A http www deltaww com 1 1 1 1 2 1 3 1 1 PV Array Electrical Grid Solar Inverter 3PH AC Distribution box Surge arrestor AC breaker 3 phase N PE 1...

Page 157: ...2 1 RPI M50A 2 1 2 2 2 1 2 2 1 2 2 157...

Page 158: ...2 2 M50A RPI M50A 1 1 pc 1 pc 1 pc 1 pc RPI 2 3 AC AC 4 5 1 5mm x 4 6 DC 12 DC 2 1 M50A 1000V 1A Midget 158...

Page 159: ...2 3 2 3 DC 2 2 2 3 RPI503M221000 RPI M50A_12s 159...

Page 160: ...n 5 Manual Switch String1 String2 String3 Communication RS 485 2 EPO 1 Dry Contact 2 Digital Input 6 DC1 DC2 String10 String11 String12 String4 String5 String6 String7 String8 String9 Display Air inle...

Page 161: ...AC DC 1 12 M6 3 3 6 2 3 2 M6 3 4 3 3 1 12 6 5 460 0 400 0 82 0 82 0 82 0 82 0 82 0 25 0 14 1 127 7 31 0 4 R10 0 30 0 105 161...

Page 162: ...3 2 90 Not Recommended Not Recommended Keep 30 cm from floor and water if installed this way 162...

Page 163: ...3 3 3 4 14 30 3 30 97 8 192 8 129 M6 Screw 6 M6 Screw 6 Wall 163...

Page 164: ...3 5 3 5 25 60 3 6 30cm 20cm 50cm 30cm 30cm 164...

Page 165: ...M50A DC 15A DC 10A 4 1 MC4 DC AC DC DC insulation 5 2 7 Install Settings 4 4 1 DC OFF E34 L1 L2 L3 N 165...

Page 166: ...4 1 DC 1 2 3 4 L1 L2 L3 N PE Communication Wiring 1 2 3 AC Wiring DC Wiring Must be Separate PV strings RPI M50A can support 3P3W system RPI M50A 166...

Page 167: ...M50A M50A Note for Field Wiring M50A 16A 4 2 4 1 4 2 RPI M50A_12s 16A 167...

Page 168: ...phase N and PE M50A 1AWG M50A 25mm2 3AWG 100 A 3 N m G N L1 L3 L2 N L1 L2 L3 PE To solar inverter AC plug 4 2 4 3 AC 25 38mm2 3 1AWG 37 44mm 4 2 AC 3P PE 3P N PE 4 2 1 AC Model Upstream circuit break...

Page 169: ...4 3 AC AC AC L1 L2 L3 N PE 22 2mm 95 mm 0 5 95mm 22 2mm 169...

Page 170: ...AC 4 4 AC Plug 4 4 1 2 3 4 5 170...

Page 171: ...D1 D2 D3 P D1 6 5 20 30 8 44 7 1 7 5 D2 11 17 26 8 35 4 1 6 D3 13 14 21 9 27 6 1 3 5 12 25 3 5 D3 38 mm N m mm 4 4 4 5 P 164 P 165 L1 L2 L3 171...

Page 172: ...1 AC AC 55kgf cm 75kgf cm 2 A B 3 B B D 4 4 4 L1 L2 L3 N PE D1 D2 D3 L1 L2 N PE L3 A B C C D D A B C D 172...

Page 173: ...O 5 3 3N M 6 A B B 7 4 4 B D 38 2CV 25 12N m 173...

Page 174: ...AC L1 L2 400 Vac 20 L1 N 230 Vac 20 L1 L3 400 Vac 20 L2 N 230 Vac 20 L2 L3 400 Vac 20 L3 N 230 Vac 20 AC AC 5 2 7 Install Settings N PE 20Vrms TT TN S Yes TN C Yes TN C S Yes TT Yes IT No 4 2 2 174...

Page 175: ...RPI M50A 58 kW DC1 DC2 35 kW 4 5 DC1 string TDC2 string Voc 1000Vdc 4 5 PV Array RPI M50A_12s DC 15A 4 6 mm2 12 10 AWG 4 6 4 3 4 6 DC DC 4 6 PV KBT4 6 PV KST4 6 175...

Page 176: ...4 7 RPI M50A 4 7 VCC RS 485 20 AWG 0 5mm 4 4 Dry Contact VCC RS 485 EPO 1 Digital Inputs 6 Terminal Resistor 176...

Page 177: ...ction 1 VCC 12V 2 GND 3 DATA 4 DATA 5 DATA 6 DATA 4 7 RS 485 4 8 1 2 3 4 5 6 4 4 1 RS 485 Data Format Baud rate 9600 19200 default or 38400 Data bits 8 Stop bit 1 Parity N A RS485 USB or RS485 RS232 T...

Page 178: ...FF OFF ON 4 8 4 9 EPO 4 9 EPO RPI M50A EPO Install Settings 5 2 7 6 EPO 6 K1 K6 4 9 digital input Active Reactive power P F and P U 20 AWG 0 5mm 30 60 100 V1 K0 V1 K1 V1 K2 V1 K3 V1 K4 V1 K5 V1 K6 4 4...

Page 179: ...CC V1 K0 EPO K1 0 Power K2 30 Power K3 60 Power K4 100 Power K5 K6 INV_2 VCC V1 K0 EPO K1 0 Power K2 30 Power K3 60 Power K4 100 Power K5 K6 INV_N VCC V1 K0 EPO K1 0 Power K2 30 Power K3 60 Power K4 1...

Page 180: ...RPI M50A 2 5 2 7 5 Dry Contact 250Vac 28Vdc 9A 20 AWG 0 5mm 4 11 Dry Contact A Dry Contact B 4 4 3 180...

Page 181: ...Inverter Information General Settings Install Settings Active Reactive Power FRT 5 2 2 5 2 3 5 2 4 5 2 5 5 2 6 5 2 7 5 2 8 5 2 9 5 1 5 5 1 LCD 70 LED Indicator RED LED Indicator GRN EXIT Exit Menu Do...

Page 182: ...5 2 Are you sure to set country XXX Yes No AU NZ LV AU NZ MV AU NZ AU NZ PL 4 99k Select Language English Deutsch Fran ais Setting ID ID 002 Are you sure to set ID 001 Yes No Delta Solivia prot Sunsp...

Page 183: ...tatus Power E Today 7935 192 W kWh On Grid Today Energy Inverter Status Output Power Day Time or or ENT ENT V 400 400 400 I 11 5 11 5 11 5 P V A W 2645 2645 2645 L1 L2 L3 AC PF Power Frequency E Today...

Page 184: ...d Report Error Events Grid Report 1 20 02 2013 15 30 No Gird 2 19 02 2013 09 30 AC Volt Low 5 20 02 2013 15 30 AC Freq High or or EXIT EXIT EXIT EXIT ENT ENT ENT ENT ENT ENT Meter Energy Log Event Log...

Page 185: ...r Information S N RN11179CB0 Install 30 04 2014 DSP 1 80 Red 1 65 Comm 1 65 ID 002 Country Insulation Baud Rate Germany MV 250k 19200bps FRT Settings EPO Grid Settings Active Pwr Settings React Pwr Se...

Page 186: ...erlands Language Date and Time Baud Rate Protocol Language Date and Time Baud Rate Protocol 9600 19200 38400 Language Date and Time Baud Rate Protocol Delta Solivia prot Sunspec prot EXIT EXIT ENT EXI...

Page 187: ...Inverter ID Insulation Country Dry Contact EPO AC Connection Max Power Manufacturer Level All Settings Installer Level Inverter ID Insulation Country Grid Settings Dry Contact EPO AC Connection Max P...

Page 188: ...Insulation Country Grid Settings AU NZ Austria Belgium China EXIT ENT 5 2 7 2 Insulation 5 2 7 3 Country Inverter ID 002 Insulation Country Grid Settings Mode ON Resistance 250k ON Plus Grounded Minu...

Page 189: ...0V 1 0s Voltage Protection Freq Protection Reconnect T P Ramp Up High Off High On High Off T Low Off 51 50Hz 50 05Hz 0 1s 47 50Hz Low On Low Off T Hi Off Slow Hi On Slow 47 55Hz 0 1s 65 00Hz 64 95Hz H...

Page 190: ...5 14 Dry Contact 5 2 7 5 Dry Contact Alarm Error Fault Warning Disable On Grid Fan Fail Insulat Dry Cont A Dry Cont B Insulat On Grid Dry Cont A Dry Cont B Insu On Grid Alarm Error Fault Warning Disab...

Page 191: ...Injection Dry Contact RCMU EPO ON Normal Close 5 15 EPO 5 16 AC 5 17 Max Power AC Connection Anti islanding Max Power Return to Factory 3P4W ON 55000W AC Connection Anti islanding Max Power Return to...

Page 192: ...Power Limit Power vs Frequency P V Mode Set Point ON 100 EXIT ENT Power Limit Power vs Frequency P V Mode F start F recovery Gradient ON 50 20 Hz 50 20 Hz 40 T recovery 300s EXIT EXIT ENT Active Powe...

Page 193: ...Others f recovery fprotection fprotection 5 21 Power vs Frequency 5 22 P V V lock in P lock in P lock out V lock out T recovery Power Limit Power vs Frequency P V Mode P lock in P lock out V lock in...

Page 194: ...s P lower P upper 5 25 Cosphi P 5 2 8 4 Constant cosphi 5 2 8 5 Cosphi P Constant cosphi Cosphi P Constant Q Q V Mode cosphi OFF Ind 1 000 EXIT ENT Constant cosphi Cosphi P Constant Q Q V Mode Q upper...

Page 195: ...4V 253 0V Ind 44 V1i V2i Qi limit T delay 211 6V 207 0V Cap 44 10 00s P lock in P lock out 20 5 EXIT EXIT EXIT ENT V1s V2s V1i V2i Qi limit Qs limit V Q V1s V2s V1i V2i Qi limit Qs limit V Q Curve A...

Page 196: ...P lower Q lower OFF Ind 0 45 Ind 44 Q setting point Q P Q V Q T P upper V lock in V lock out 100 249 3V 304 7V EXIT EXIT ENT 5 2 9 Q setting 24 7 5 2 9 1 Q setting point 5 2 9 2 Q P 5 29 Q setting 24...

Page 197: ...0s 2 0 Warning Adj would affect energy production Password EXIT EXIT EXIT ENT ENT 5 33 FRT 5 34 FRT FRT 5 2 8 7 5 32 Q T 5 2 10 FRT Fault ride through 100 U1 0 t1 Fault occurrence t3 time Ugrid Unom U...

Page 198: ...RPI M50A_12s AC DC PV Inverter 6 6 1 SPD AC DC SPD Fail 1 AC DC 2 6 1 3 6 2 4 6 3 5 SPD 6 4 6 7 8 6 1 10Kgf cm 198...

Page 199: ...6 1 6 2 199...

Page 200: ...6 3 6 4 SPD 8 Kgf cm 0 8N m 200...

Page 201: ...6 5 4 6 6 5 6 2 DC Item String Fuse source 2 Part number 10GPV15U0 Rate amp 15 A Rate voltage 1000 V Manufacturers Hollyland Item String Fuse source 1 Part number 0SPF015 T Rate amp 15 A Rate voltage...

Page 202: ...6 6 6 7 6 7 6 3 10 Kgf cm 1N m 202...

Page 203: ...6 8 6 9 6 9 4 6 5 6 4 8 Kgf cm 0 8N m 8 Kgf cm 0 8N m 203...

Page 204: ...E15 E20 AC Volt High E11 E13 E16 E18 E21 E23 Solar1 High E30 1 2 3 1 2 3 1 AC 2 1 AC 2 AC 1 2 3 AC 4 1 2 3 4 1 Solar1 1000Vdc 2 1 2 3 1 2 3 1 AC 2 1 AC 2 AC 1 2 3 AC 4 1 2 3 4 1 solar array Voc 1000V...

Page 205: ...AN W11 1 2 3 1 2 3 1 Solar1 2 Solar1 0 3 1 Solar2 2 Solar1 0 3 1 2 3 4 1 Solar1 2 boost1 3 1 Solar2 voltage 2 boost2 3 1 2 3 4 De rating W07 1 2 3 4 P F 5 P V 6 7 8 1 2 3 4 5 6 1 6 2 7 PV panel 8 PV p...

Page 206: ...TC1 Fail F06 HW NTC2 Fail F08 HW NTC3 Fail F09 HW NTC4 Fail F10 HW RLY F13 HW DSP ADC1 F15 1 2 1 60 2 1 30 2 1 90 30 2 1 90 30 2 1 90 30 2 1 90 30 2 1 2 3 1 2 3 1 2 1 2 1 2 RTM1 RTB1 RTG1 and RTH1 1 2...

Page 207: ...HW COMM1 F23 HW COMM2 F22 Ground Cur F24 1 2 3 1 2 3 1 2 3 1 2 3 1 2 1 DSP 2 3 1 Red CPU 2 1 2 3 Boost Boost 4 1 150Vdc 2 3 1 150Vdc 2 3 1 150Vdc 2 3 1 150Vdc 2 3 1 2 1 DSP reset crystal 2 DSP COMM 3...

Page 208: ...gh F36 F37 F38 F39 F40 F41 HW CT A Fail F42 1 2 1 RCMU 2 1 2 driver 1 2 3 Vgrid Vout 1 2 3 Boost 4 1 Boost 2 Voc 1000Vdc 3 4 1 2 Inverter stage 3 4 1 2 CSC1 3 1 2 1 RCMU 2 1 2 1 2 3 Vgrid Vout 1 2 3 b...

Page 209: ...HW ZC Fail F50 DC Cur High F60 F61 F70 F71 7 3 1 2 CSC2 3 1 2 CSC3 3 1 WC3 CNC16 2 CSC3 3 1 Boost 2 Boost 3 1 WC3 CNC16 2 CSC2 3 1 WC3 CNC16 2 CSC3 3 1 2 inverter stage 3 1 boost 2 boost 3 Ext Comm F...

Page 210: ...8 Manual Switch OFF AC voltmeter AC DC AC DC RS 485 210...

Page 211: ...tdoor wet locations IP65 Electronics II AC output III DC Input II 0 Class I metal enclosure with protective earth 612 740 278mm Weather resistant connectors 58kW 52 5kW 63kW 600Vdc 200Vdc 1000 Vdc 250...

Page 212: ...Hz Programmable 45Hz 65Hz 3 0 99 full power Adjustable 0 80 leading 0 80 lagging 0 5 rated current 2W 3 Ph N PE 3 phase AC plug that meets IP67 and specifications in Table 4 2 98 6 98 4 Grid side RPI...

Page 213: ...ions EN 61000 3 11 CE conformity Yes Grid interface VDE AR N 4105 VDE0126 1 1 NB T 32004 Emission EN 61000 6 3 Harmonics EN 61000 3 12 EN 61000 6 2 CS Immunity PFMF IEC 61000 4 2 IEC 61000 4 3 IEC 610...

Page 214: ...9 1 M50A Efficiency Pn 50kW Efficiency of M50A Output voltage at 400Vac 10 20 40 80 60 90 91 92 93 94 95 96 97 98 99 100 520V 600V 800V Output Power 100 110 214...

Page 215: ...50 55 60 65 70 75 80 85 90 95 100 105 110 115 25 30 35 40 45 50 55 60 Temperature Derating of RPI M50A P Pn Pn 50kW Cos 1 0 Ambient Temperature 9 2 M50A cos 1 0 520Vdc 600Vdc 800Vdc 215...

Page 216: ...os 0 95 50 55 60 65 70 75 80 85 90 95 100 105 110 115 25 30 35 40 45 50 55 60 Temperature Derating of RPI M50A S 520Vdc P 520Vdc S 600Vdc P 600Vdc S 800Vdc P 800Vdc P Pn Pn 50kW Cos 0 95 Ambient Tempe...

Page 217: ...os 0 9 50 55 60 65 70 75 80 85 90 95 100 105 110 115 25 30 35 40 45 50 55 60 Temperature Derating of RPI M50A S 520Vdc P 520Vdc S 600Vdc P 600Vdc S 800Vdc P 800Vdc P Pn Pn 50kW Cos 0 9 Ambien Temperat...

Page 218: ...9 5 M50A cos 1 0 Input Voltage P Pn Pn 50kW 10 20 30 40 50 60 70 80 90 100 110 0 200 400 600 520 800 1000 V AMB 40 C AMB 25 C AMB 45 C AMB 50 C AMB 55 C Input Voltage Derating of RPI M50A 218...

Page 219: ...IV 1000Vdc A I V A I V curve limitation 219 A I V curve limitation...

Page 220: ...B B 1 1 NO 5 SPD board 8 Kgf cm 0 8N m 4 Fans 8 Kgf cm 0 8N m 2 Air inlet 8 Kgf cm 0 8N m 3 Fan panel 8 Kgf cm 0 8N m 1 Front cover 10 Kgf cm 1N m 220 B...

Page 221: ...n cover 8 Kgf cm 0 8N m 20 AWG 0 5mm 12 10AWG 4 6mm D1 D2 D3 PV KST 4 6 PV KBT 4 6 2 AC plug 60 80 kgf cm 5 9 7 8N m 6 Communication module 3 Rubber rings D1 66 204 Kgf cm 6 5 20N m D2 112 173 Kgf cm...

Page 222: ......

Page 223: ......

Page 224: ...Version 06190528 5013237005...

Reviews: