ERROR
Message
Possible cause
Action
Insulation
(E34)
1. PV array insulation fault
2. Large PV array capacitance
between Plus to Ground or
Minus to Ground or both.
3. Detection circuit malfunction
1. Check the insulation of Solar inputs
2. Check the capacitance, dry PV panel
if necessary
3. Check the detection circuit inside the
inverter
Table 7-1 : Error Message
Warning
Message
Possible cause
Action
Solar1
Low
(W01)
1. Actual Solar1 voltage is under
the limit
2. Some devices were damaged
inside the inverter if the actual
Solar1 voltage is close to "0"
3. Detection circuit malfunction
1. Check the Solar1 voltage connection
to the inverter terminal
2. Check all switching devices in boost1
3. Check the detection circuit inside the
inverter
Solar2
Low
(W02)
1. Actual Solar2 voltage is under
the limit
2. Some devices were damaged
inside the inverter if the actual
Solar2 voltage is close to "0"
3. Detection circuit malfunction
1. Check the Solar2 voltage connection
to the inverter terminal
2. Check all switching devices in boost2
3. Check the detection circuit inside the
inverter
HW FAN
(W11)
1. One or more fans are locked
2. One or more fans are defective
3. One ore more fans are
disconnected
4. Detection circuit malfunction
1. Remove the object that stuck in the
fan(s)
2. Replace the defective fan(s)
3. Check the connections of all fans
4. Check the detection circuit inside the
inverter
De-rating
(W07)
1. Over temperature
2. Fan fail
3. Power Limit function
4. Power vs. Frequency function
5. P(V) function
6. Grid Voltage low
7. Solar Voltage low
8. Solar Voltage High
1. Check the installation ambient and
environment
2. Check the fan(s)
3. Check country & Grid setting
4. Check the utility frequency on the inverter
terminal
5. Check the utility voltage on the inverter
terminal
6-1. Check the utility voltage on the inverter
terminal
6-2. Check reactive power setting
7. Check the Solar voltage on the inverter
terminal
8. Check the Solar voltage on the inverter
terminal
SPD Fail
1. Inverter was struck by lighting.
2. One or more SPD are defective
3. One or more SPD are
disconnected
4. Detection circuit malfunction
1. Check inverter’s status
2. Replace the defective SPD
3. Check the connections of SPDs
4. Check the detection circuit inside the
inverter
Table 7-2 : Warning Message
58
Error message and Trouble Shooting
Summary of Contents for RPI M50A 12s
Page 2: ......
Page 75: ...RPI M50A_12s The power behind competitiveness www deltaww com English 1 75 149...
Page 81: ...81...
Page 83: ...2 1 RPI M50A 2 1 2 2 2 1 2 2 1 2 2 83...
Page 85: ...2 3 2 3 RPI503M221000 DC RPI M50A_12s 2 2 2 3 85...
Page 89: ...3 3 3 4 14 30 3 30 97 8 192 8 129 M6 Screw 6 M6 Screw 6 Wall 89...
Page 90: ...3 5 3 5 25 60 3 6 30cm 20cm 50cm 30cm 30cm 90...
Page 93: ...M50A M50A Note for Field Wiring M50A 16A 4 2 4 1 4 2 RPI M50A_12s 16A 93...
Page 95: ...4 3 AC AC AC 95mm 22 2mm L1 L2 L3 N PE 22 2mm 95 mm 0 5 95...
Page 96: ...AC 4 4 AC Plug 4 4 1 2 3 4 5 96...
Page 99: ...O 5 3 3N M 6 A B B 7 4 4 B D 38 2CV 25 12N m 99...
Page 125: ...6 1 6 2 125...
Page 126: ...6 3 6 4 SPD 8 Kgf cm 0 8N m 126...
Page 128: ...6 6 6 7 6 7 6 3 10 Kgf cm 1N m 128...
Page 129: ...6 8 6 9 6 9 4 6 5 6 4 8 Kgf cm 0 8N m 8 Kgf cm 0 8N m 129...
Page 136: ...8 Manual Switch OFF AC voltmeter AC DC AC DC RS 485 136...
Page 145: ...IV 1000Vdc A I V A I V curve limitation 145 A I V curve limitation...
Page 148: ......
Page 149: ...RPI M50A_12s The power behind competitiveness www deltaww com English 1 75 149...
Page 155: ...155...
Page 157: ...2 1 RPI M50A 2 1 2 2 2 1 2 2 1 2 2 157...
Page 159: ...2 3 2 3 DC 2 2 2 3 RPI503M221000 RPI M50A_12s 159...
Page 163: ...3 3 3 4 14 30 3 30 97 8 192 8 129 M6 Screw 6 M6 Screw 6 Wall 163...
Page 164: ...3 5 3 5 25 60 3 6 30cm 20cm 50cm 30cm 30cm 164...
Page 167: ...M50A M50A Note for Field Wiring M50A 16A 4 2 4 1 4 2 RPI M50A_12s 16A 167...
Page 169: ...4 3 AC AC AC L1 L2 L3 N PE 22 2mm 95 mm 0 5 95mm 22 2mm 169...
Page 170: ...AC 4 4 AC Plug 4 4 1 2 3 4 5 170...
Page 173: ...O 5 3 3N M 6 A B B 7 4 4 B D 38 2CV 25 12N m 173...
Page 199: ...6 1 6 2 199...
Page 200: ...6 3 6 4 SPD 8 Kgf cm 0 8N m 200...
Page 202: ...6 6 6 7 6 7 6 3 10 Kgf cm 1N m 202...
Page 203: ...6 8 6 9 6 9 4 6 5 6 4 8 Kgf cm 0 8N m 8 Kgf cm 0 8N m 203...
Page 210: ...8 Manual Switch OFF AC voltmeter AC DC AC DC RS 485 210...
Page 219: ...IV 1000Vdc A I V A I V curve limitation 219 A I V curve limitation...
Page 222: ......
Page 223: ......
Page 224: ...Version 06190528 5013237005...