For Cu AC wires:
Delta recommends the AC cables used should be flexible unarmored multi-strand
and with suitable ampacity.
For Al AC wires:
To make sure good conductivity, bi-metal sleeves must be used in conjunction
with aluminum wires. (Shown as
Figure 4-4
)
Figure 4-4 : Bi-metal sleeves
Al
Cu
Extreme temperature rise at the clamping point
If the contact resistance between the aluminum conductor and clamping point is too
high, the clamping point can become very hot and even catch fire in extreme cases.
To ensure a safe and reliable contact,
always
perform the following work steps:
Use a conductor cross-section at least one number larger due to the lower
current-carrying capacity.
Keep the installation location as free as possible from moisture or corrosive
atmospheres.
Connect the aluminum cables quickly.
Mechanically clean the stripped end of the aluminum conductor (using for instance
a knife blade to scrape off the oxide layer). Then immediately dip the aluminum
conductor into acid-fee and alkaline-free (=neutral) Vaseline and straight away
insert it into the terminal block.
Tighten the clamping screw in the clamping body with the maximum permissible
tightening torque.
NOTICE
23
Wiring
Summary of Contents for RPI M50A 12s
Page 2: ......
Page 75: ...RPI M50A_12s The power behind competitiveness www deltaww com English 1 75 149...
Page 81: ...81...
Page 83: ...2 1 RPI M50A 2 1 2 2 2 1 2 2 1 2 2 83...
Page 85: ...2 3 2 3 RPI503M221000 DC RPI M50A_12s 2 2 2 3 85...
Page 89: ...3 3 3 4 14 30 3 30 97 8 192 8 129 M6 Screw 6 M6 Screw 6 Wall 89...
Page 90: ...3 5 3 5 25 60 3 6 30cm 20cm 50cm 30cm 30cm 90...
Page 93: ...M50A M50A Note for Field Wiring M50A 16A 4 2 4 1 4 2 RPI M50A_12s 16A 93...
Page 95: ...4 3 AC AC AC 95mm 22 2mm L1 L2 L3 N PE 22 2mm 95 mm 0 5 95...
Page 96: ...AC 4 4 AC Plug 4 4 1 2 3 4 5 96...
Page 99: ...O 5 3 3N M 6 A B B 7 4 4 B D 38 2CV 25 12N m 99...
Page 125: ...6 1 6 2 125...
Page 126: ...6 3 6 4 SPD 8 Kgf cm 0 8N m 126...
Page 128: ...6 6 6 7 6 7 6 3 10 Kgf cm 1N m 128...
Page 129: ...6 8 6 9 6 9 4 6 5 6 4 8 Kgf cm 0 8N m 8 Kgf cm 0 8N m 129...
Page 136: ...8 Manual Switch OFF AC voltmeter AC DC AC DC RS 485 136...
Page 145: ...IV 1000Vdc A I V A I V curve limitation 145 A I V curve limitation...
Page 148: ......
Page 149: ...RPI M50A_12s The power behind competitiveness www deltaww com English 1 75 149...
Page 155: ...155...
Page 157: ...2 1 RPI M50A 2 1 2 2 2 1 2 2 1 2 2 157...
Page 159: ...2 3 2 3 DC 2 2 2 3 RPI503M221000 RPI M50A_12s 159...
Page 163: ...3 3 3 4 14 30 3 30 97 8 192 8 129 M6 Screw 6 M6 Screw 6 Wall 163...
Page 164: ...3 5 3 5 25 60 3 6 30cm 20cm 50cm 30cm 30cm 164...
Page 167: ...M50A M50A Note for Field Wiring M50A 16A 4 2 4 1 4 2 RPI M50A_12s 16A 167...
Page 169: ...4 3 AC AC AC L1 L2 L3 N PE 22 2mm 95 mm 0 5 95mm 22 2mm 169...
Page 170: ...AC 4 4 AC Plug 4 4 1 2 3 4 5 170...
Page 173: ...O 5 3 3N M 6 A B B 7 4 4 B D 38 2CV 25 12N m 173...
Page 199: ...6 1 6 2 199...
Page 200: ...6 3 6 4 SPD 8 Kgf cm 0 8N m 200...
Page 202: ...6 6 6 7 6 7 6 3 10 Kgf cm 1N m 202...
Page 203: ...6 8 6 9 6 9 4 6 5 6 4 8 Kgf cm 0 8N m 8 Kgf cm 0 8N m 203...
Page 210: ...8 Manual Switch OFF AC voltmeter AC DC AC DC RS 485 210...
Page 219: ...IV 1000Vdc A I V A I V curve limitation 219 A I V curve limitation...
Page 222: ......
Page 223: ......
Page 224: ...Version 06190528 5013237005...