ERROR
Message
Possible cause
Action
7
Error message and Trouble Shooting
AC Freq
High
(E01)
1. Actual utility frequency is over
the OFR setting
2. Incorrect country setting
3. Detection circuit malfunction
1. Check the utility frequency on the
inverter terminal
2. Check country setting
3. Check the detection circuit inside the
inverter
AC Freq
Low
(E02)
1. Actual utility frequency is under
the UFR setting
2. Incorrect country or Grid setting
3. Detection circuit malfunction
1. Check the utility frequency on the
inverter terminal
2. Check country & Grid setting
3. Check the detection circuit inside the
inverter
Grid Quality
(E07)
Non-linear load in Grid and near
to inverter
Grid connection of inverter need to be
far away from non-linear load if necessary
HW Con.
Fail
(E08)
1. Wrong connection in AC plug
2. Detection circuit malfunction
1. Check the AC connection, must accords
to manual
2. Check the detection circuit inside the
inverter
No Grid
(E09)
1. AC breaker is OFF
2. Disconnect in AC plug
1. Switch on AC breaker
2. Check the connection in AC plug and
make sure it connects to inverter
AC Volt
Low
(E10, E15,
E20)
1. Actual utility voltage is under
the UVR setting
2. Incorrect country or Grid setting
3. Wrong connections in AC plug
4. Detection circuit malfunction
1. Check the utility voltage connection
to the inverter terminal
2. Check country & Grid setting
3. Check the connection in AC plug
4. Check the detection circuit inside the
inverter
AC Volt
High
(E11, E13,
E16, E18,
E21, E23)
1. Actual utility voltage is over the
OVR setting
2. Utility voltage is over the Slow
OVR setting during operation
3. Incorrect country or Grid setting
4. Detection circuit malfunction
1. Check the utility voltage on the inverter
terminal
2. Check the utility voltage on the inverter
terminal
3. Check country & Grid setting
4. Check the detection circuit inside the
inverter
Solar1
High
(E30)
1. Actual Solar1 voltage is over
1000Vdc
2. Detection circuit malfunction
1. Modify the solar array setting, and
make the Voc less than 1000Vdc
2. Check the detection circuit inside the
inverter
EPO
(E25)
1. EPO is activated by user
2. Detection circuit malfunction
1. Release the EPO button
2. Check the detection circuit inside the
inverter
Solar2
High
(E31)
1. Actual Solar2 voltage is over
1000Vdc
2. Detection circuit malfunction
1. Modify the solar array setting, and
make the Voc less than 1000Vdc
2. Check the detection circuit inside the
inverter
57
Error message and Trouble Shooting
Summary of Contents for RPI M50A 12s
Page 2: ......
Page 75: ...RPI M50A_12s The power behind competitiveness www deltaww com English 1 75 149...
Page 81: ...81...
Page 83: ...2 1 RPI M50A 2 1 2 2 2 1 2 2 1 2 2 83...
Page 85: ...2 3 2 3 RPI503M221000 DC RPI M50A_12s 2 2 2 3 85...
Page 89: ...3 3 3 4 14 30 3 30 97 8 192 8 129 M6 Screw 6 M6 Screw 6 Wall 89...
Page 90: ...3 5 3 5 25 60 3 6 30cm 20cm 50cm 30cm 30cm 90...
Page 93: ...M50A M50A Note for Field Wiring M50A 16A 4 2 4 1 4 2 RPI M50A_12s 16A 93...
Page 95: ...4 3 AC AC AC 95mm 22 2mm L1 L2 L3 N PE 22 2mm 95 mm 0 5 95...
Page 96: ...AC 4 4 AC Plug 4 4 1 2 3 4 5 96...
Page 99: ...O 5 3 3N M 6 A B B 7 4 4 B D 38 2CV 25 12N m 99...
Page 125: ...6 1 6 2 125...
Page 126: ...6 3 6 4 SPD 8 Kgf cm 0 8N m 126...
Page 128: ...6 6 6 7 6 7 6 3 10 Kgf cm 1N m 128...
Page 129: ...6 8 6 9 6 9 4 6 5 6 4 8 Kgf cm 0 8N m 8 Kgf cm 0 8N m 129...
Page 136: ...8 Manual Switch OFF AC voltmeter AC DC AC DC RS 485 136...
Page 145: ...IV 1000Vdc A I V A I V curve limitation 145 A I V curve limitation...
Page 148: ......
Page 149: ...RPI M50A_12s The power behind competitiveness www deltaww com English 1 75 149...
Page 155: ...155...
Page 157: ...2 1 RPI M50A 2 1 2 2 2 1 2 2 1 2 2 157...
Page 159: ...2 3 2 3 DC 2 2 2 3 RPI503M221000 RPI M50A_12s 159...
Page 163: ...3 3 3 4 14 30 3 30 97 8 192 8 129 M6 Screw 6 M6 Screw 6 Wall 163...
Page 164: ...3 5 3 5 25 60 3 6 30cm 20cm 50cm 30cm 30cm 164...
Page 167: ...M50A M50A Note for Field Wiring M50A 16A 4 2 4 1 4 2 RPI M50A_12s 16A 167...
Page 169: ...4 3 AC AC AC L1 L2 L3 N PE 22 2mm 95 mm 0 5 95mm 22 2mm 169...
Page 170: ...AC 4 4 AC Plug 4 4 1 2 3 4 5 170...
Page 173: ...O 5 3 3N M 6 A B B 7 4 4 B D 38 2CV 25 12N m 173...
Page 199: ...6 1 6 2 199...
Page 200: ...6 3 6 4 SPD 8 Kgf cm 0 8N m 200...
Page 202: ...6 6 6 7 6 7 6 3 10 Kgf cm 1N m 202...
Page 203: ...6 8 6 9 6 9 4 6 5 6 4 8 Kgf cm 0 8N m 8 Kgf cm 0 8N m 203...
Page 210: ...8 Manual Switch OFF AC voltmeter AC DC AC DC RS 485 210...
Page 219: ...IV 1000Vdc A I V A I V curve limitation 219 A I V curve limitation...
Page 222: ......
Page 223: ......
Page 224: ...Version 06190528 5013237005...