40
Vac High Off Slow T
The function is same as Vac High Off T, but the time must be
longer than former.
Vac Low Off Slow
The function is same as Vac Low Off, but the value must be
higher than former.
Vac Low On Slow
The function is same as Vac Low On, but the value must be
higher than former.
Vac Low Off Slow T
The function is same as Vac High Off T, but the time must be
longer than former.
Fac High Off
Inverter will be disconnected from grid if AC frequency rises to
this value.
Fac High On
Inverter will be reconnected to grid if AC frequency drops to this
value.
Fac High Off T
If AC frequency reaches to the value of Fac High Off, inverter
will be disconnected in this time.
Fac Low Off
Inverter will be disconnected from if AC frequency drops to this
value.
Fac Low On
Inverter will be reconnected to grid if AC frequency rises to this
value.
Fac Low Off T
If AC frequency reaches to the value of Fac Low Off, inverter
will be disconnected in this time.
Reconnection Time
The countdown time before inverter connected to grid.
7.2.6.4
Active/Reactive Power Control
Only when country sets as Germany LV, Germany MV, Italy LV, or Italy MV can
user enters this page. User has to enter user
’
s password before enter this page.
Password
21. Jun 2010 13:50
ENT
ENT
EXIT
ENT
EXIT
Active/Reactive Power
21. Jun 2010 13:50
Power vs. Frequency
Power Limit
Constant cos
φ
cos
φ
(P)
Constant Reactive Power
Q(V)
*1
*2
*3
Settings
21. Jun 2010 13:50
Coefficients Settings
Personal Settings
Install Settings
Active/Reactive Power Control
FRT
Figure 7-18 Active/Reactive powersetting page