5.3 DC Connection (from PV Array)
WARNING
When doing DC wiring, please choose the proper wiring by
connect to the correct polarity.
When doing DC wiring, please confir
m that PV Array’s power
switch is off.
CAUTION
The connection number of PV Array, open circuit voltage and
power of String_1 and String _2 must be coherent.
The connection number of PV Array, open circuit voltage and
power of String _3 and String _4 must be coherent.
The maximum open circuit voltage of PV Array can not be higher
then 1000V.
The range of Vmpp of Input1 and Input2 shall be in 350~800 Vdc.
The device installed between PV Array and inverter must meet the
rating of voltage >1000 Vdc and > Short current.
The input power to the inverter is not recommended to exceed the
maximum rated power which show in table 5-3.
Table 5-4 Maximum rating of input power
Type of limit
RPI-M8
RPI-M10
RPI-M12
RPI-M15
Total input power
8.8 kW
11 kW
13.2 kW
16.5 kW
Input1 or Input2
5.9 kW
7.4 kW
8.8 kW
8.25 kW
Type of limit
RPI-M15A
RPI-M20
RPI-M20A
RPI-M30
Total input power
16.5 kW
22 kW
22 kW
32 kW
Input1 or Input2
8.25 kW
11 kW
11 kW
16 kW
Table 5-5 Cable size
Model
Current Rating
Wire size
Temperature
M8
DC 10A
2 - 3mm
2
/ 14 AWG
Meet UL 10070
M10/ M12
DC 20A
3 - 5mm
2
/ 12 AWG
Meet UL 10070
M15A/ M20A
DC 34A
5 - 6mm
2
/ 10 AWG
Meet UL 10070
M15/ M20/ M30
DC 34A
5 - 6mm
2
/ 10 AWG
Meet UL 10070