61
Tare loss
<2 W
Maximum efficiency
98.3 %
EU efficiency
97.7 %
AC connector
3 Ph + N + PE ; IP67 3-phase AC plug suitable for
4 mm
2
and 6 mm
2
Fuse
N/A. Please connect to an external protection
device (1.25 rated current)
SYSTEM INFORMATION / COMMUNICATION
User interface
Black-on-white graphical LCD display
365 days data logger and real time clock
30 events record
Externalcommunication
2 RS-485 connections
REGULATIONS & DIRECTIVES
CE conformity
Yes
Grid interface
VDE0126-1-1, VDE-AR-N 4105, RD1699, CEI 0-21
Emission
EN 61000-6-3
Harmonics
EN 61000-3-12
Variations and flicker
EN 61000-3-11
Immunity
EN 61000-6-2
Immunity
ESD
IEC 61000-4-2
RS
IEC 61000-4-3
EFT
IEC 61000-4-4
Surge
IEC 61000-4-5
CS
IEC 61000-4-6
PFMF
IEC 61000-4-8
Electrical safety
IEC 62109-1/ -2
MISCELLANEOUS
Cooling
Fan, 2pcs
Enclosure
Mounting bracket
Aluminum with powder coating