Appendix B
Digital Input
To implementation of power management, the digital input interface receives the specifications
of the network operator via a ripple control receiver.
•
Germany : The active power limitation in the stages 0%, 30%, 60% and 100%
•
Italy
: Power output of Max 6KW for PV plant installation.
Remote shutdown
Narrow Frequency limits between 49.5 Hz to 50.5Hz.
•
Australia and New Zealand:
The inverter support the demand response mode(DRMs).
DRM 0 - Operate the disconnection device.
DRM 5 - Do not generate power.
DRM 6 - Do not generate at more than 50% of rated power.
DRM 7 - Do not generate at more than 75% of rated power.
And sink reactive power.
DRM 8 - Increase power generation.
(subject to constraints from other active DRMs)
•
Customer : User defined.
Figure B-1
:
Pin assignment at ripple control receiver
The inverter gives a voltage to Pin 6, and measures Pin 1 to 5.
The inverter can detect the state of the relay of the ripple control receiver.
The information which relay shall be controlled parameter by the network operator.
Ripple control receiver
Digital input
Digital input
D5
D4
D3
D2
D1
58
Appendix B
Summary of Contents for RPI-H3
Page 2: ......
Page 12: ...Figure 2 3 The identification label for H5 RPI H5 12 Installation and Wiring...
Page 15: ...Figure 3 4 LCD display and buttons 3 2 1 LCD Display and Buttons 15 Product Overview...
Page 18: ...Figure 4 1 Screw the mounting bracket for RPI H3 18 Installation...
Page 19: ...Figure 4 2 Screw the mounting bracket for RPI H5 19 Installation...
Page 60: ......
Page 61: ......
Page 62: ......
Page 63: ......
Page 64: ...Version 04180115 5013208606...