Output
Output capacity
500kVA
Grid
Three phase (3P3W-IT)
Utility voltage range
243~378V
Δ
Utility frequency
50/60Hz
Utility frequency range
Domestic regulation (Max 50/60Hz
± 5Hz)
Maximum output current
1080A
Anti-islanding
Domestic regulation
Output reconnect
Connect to utility after utility recover
and countdown finished
Reconnect time
Domestic regulation
Output current DC component
< 0.5% at rated current
Output current harmonic distortion
< 3% at rated power
Reactive power control
0.8 leading to 0.8 lagging
Active power control
1% each step
Nighttime power consumption
< 50 watts (without optional
transformer)
Detection tolerance
● Utility voltage deviation < 2%
● Utility frequency deviation < 0.03
Hz
● Countdown timer deviation < 1.0
sec
● Output power deviation < 3% at
full power
Power limitation
Temperature sensors depend on
heatsink & internal air temperature.
AC Circuitry Breaker
690V/1250A
Protection
● AC Circuitry Breaker & Thermal
protection
● Surge arrestor_600V/30kA
Type 2
Summary of Contents for PhotoVoltaic RPI-C500
Page 1: ...PhotoVoltaic Inverter RPI C500 PV Inverter ...
Page 88: ...INSTALLATION GUIDE 82 ...
Page 89: ...光伏逆变器 RPI C500 光伏逆变器 ...
Page 100: ...安装手册 5 产品外观 外部三角视图 3 2 2 外部三角视图 图 3 2 外部后视图 进气孔 ...
Page 114: ...安装手册 20 安装说明 DC 端连接 图 5 4 DC 端连接端尺寸图 ...
Page 116: ...安装手册 22 安装说明 AC 端连接 5 3 AC 端连接 1 如图 5 6 所示将连接到 AC 端的电缆穿过底板 图 5 6 AC 端配线 ...
Page 119: ...安装手册 25 安装说明 AC 端连接 图 5 9 AC 端连接端尺寸图 ...
Page 156: ...安装手册 62 维修保养 更换风扇模块 7 维修保养 7 1 更换风扇模块 1 按拉且扭转把手 之后打开后门 图 7 1 按拉扭转把手 ...
Page 158: ...安装手册 64 维修保养 更换风扇模块 4 松开锁附在上风扇与机壳上的螺丝 然后将上风扇移除 图 7 4 松开上风扇的螺丝 ...
Page 160: ...安装手册 66 维修保养 更换进气口滤网 3 松开锁附在滤网上的螺丝 图 7 7 松开滤网的螺丝 4 取出滤网 图 7 8 取出滤网 ...
Page 162: ...安装手册 68 维修保养 清理排气孔滤网 4 直接取出挡板和排气孔滤网 图 7 11 取出排气孔滤网 ...
Page 165: ...安装手册 71 维修保养 更换 SURGE PROTECTION DEVICE 4 退出已损坏的 SPD 并更换新的 Figure 7 15 退出已损坏的 SPD ...
Page 176: ...Version 01180521 5013209808 ...