I
NSTALLATION
G
UIDE
39
I
NSTALLATION
A
CTIVE
/R
EACTIVE
P
OWER
C
ONTROL
A
ND
F
AULT
R
IDE
T
HROUGH
Below the blue line shown in Figure 2.5.1.2-2, there are no requirements saying that
generating plants have to remain connected to the network.
Voltage drops with values above the borderline 1 must not lead to instability or to the
disconnection of the generating plant from the network (TC2007; 3.3.13.5, section 13;
extended to asymmetrical voltage drops).
If the voltage drops at values above the borderline 2 and below the borderline 1, generating
units shall pass through the fault without disconnecting from the network. Feed-in of a short-
circuit current during that time is to be agreed with the network operator. In consultation with
the network operator, it is permissible to shift the borderline 2 if the generating plant’s
connection concept requires to do so. Also in consultation with the network operator, a short-
time disconnection from the network is permissible if the generating plant can be
resynchronized 2 seconds, at the latest, after the beginning of the short-time disconnection.
After resynchronization, the active power must be increased with a gradient of at least 10% of
the nominal capacity per second (TC2007; 3.3.13.5, section 14).
Figure 5-26. Borderlines of the voltage profile of a type-2 generating plant at the
network connection point
RPI-C500 implements the FRT behavior as the figure below, in area
1. Keep normally operate
2. Feed-
in reactive current according to ΔU/Un and K factor
3. Short time disconnect
4. Long time disconnect
U/Un
I
B
/I
n
K factor
K factor
+10
-10
100%
U1
0
t1
t2
Fault occurence
t3
time
U
grid/
U
nom
2
3
4
1
U2
Udrop
Figure 5-27. FRT characteristic
Summary of Contents for PhotoVoltaic RPI-C500
Page 1: ...PhotoVoltaic Inverter RPI C500 PV Inverter ...
Page 88: ...INSTALLATION GUIDE 82 ...
Page 89: ...光伏逆变器 RPI C500 光伏逆变器 ...
Page 100: ...安装手册 5 产品外观 外部三角视图 3 2 2 外部三角视图 图 3 2 外部后视图 进气孔 ...
Page 114: ...安装手册 20 安装说明 DC 端连接 图 5 4 DC 端连接端尺寸图 ...
Page 116: ...安装手册 22 安装说明 AC 端连接 5 3 AC 端连接 1 如图 5 6 所示将连接到 AC 端的电缆穿过底板 图 5 6 AC 端配线 ...
Page 119: ...安装手册 25 安装说明 AC 端连接 图 5 9 AC 端连接端尺寸图 ...
Page 156: ...安装手册 62 维修保养 更换风扇模块 7 维修保养 7 1 更换风扇模块 1 按拉且扭转把手 之后打开后门 图 7 1 按拉扭转把手 ...
Page 158: ...安装手册 64 维修保养 更换风扇模块 4 松开锁附在上风扇与机壳上的螺丝 然后将上风扇移除 图 7 4 松开上风扇的螺丝 ...
Page 160: ...安装手册 66 维修保养 更换进气口滤网 3 松开锁附在滤网上的螺丝 图 7 7 松开滤网的螺丝 4 取出滤网 图 7 8 取出滤网 ...
Page 162: ...安装手册 68 维修保养 清理排气孔滤网 4 直接取出挡板和排气孔滤网 图 7 11 取出排气孔滤网 ...
Page 165: ...安装手册 71 维修保养 更换 SURGE PROTECTION DEVICE 4 退出已损坏的 SPD 并更换新的 Figure 7 15 退出已损坏的 SPD ...
Page 176: ...Version 01180521 5013209808 ...