Dry contacts (relays)
E-Today: 0kWh
Power: 0W
Status: On Grid
10.Sep 2018 14:55
1.
If the default information is displayed, press the
EXIT
button to open the main menu.
Otherwise, press the
EXIT
button repeatedly until the main menu is displayed.
Inverter Info.
General Settings
Install Settings
Active/Reactive Pwr
FRT
2.
Use the
and
buttons to select the
Install Settings
entry and then press
the
ENT
button.
Password 0 * * *
energy production.
Adj. would affect
Warning:
3.
This function is protected with password 5555.
Use the
and
buttons to set the individual numerals.
Press the
ENT
button to confirm a numeral.
Grid Settings
DC Injection
Dry Contact
RCMU: ON
PID Function: ON
4.
Use the
and
buttons to select the
Dry Contact
entry and then press the
ENT
button.
Dry Cont.B Disable
Dry Cont.A Disable
5.
Use the
and
buttons to select a dry contact and press the
ENT
button. The
current setting is shown after the name of the dry contact.
On Grid
Fan Fail
Insulation
Disable
6.
Use the
and
buttons to select an option and then press the
ENT
button.
53
Quick installation guide for solar inverter M88H RPI883M121300 RPI883M122300 EU V1 EN 5017414200_00 2019-11-07
Commissioning – Further settings (optional)