Baud rate for RS485
E-Today: 0kWh
Power: 0W
Status: On Grid
10.Sep 2018 14:55
1.
If the default information is displayed, press the
EXIT
button to open the main menu.
Otherwise, press the
EXIT
button repeatedly until the main menu is displayed.
Inverter Info.
General Settings
Install Settings
Active/Reactive Pwr
FRT
2.
Use the
and
buttons to select the
General Settings
entry and then press
the
ENT
button.
Protocol
Baud rate
Date & Time
Language
3.
Use the buttons
and
to select the entry
Baud Rate
and press the
ENT
button.
38400
19200
9600
4.
Use the
and
buttons to configure a value and then press the
ENT
button.
Repeat the procedure for the other settings.
AC connection type
By default, the AC connection type is set to 3P4W (3 N + PE). You only need to change this setting if you
are using an AC system with 3 PE (3P3W).
E-Today: 0kWh
Power: 0W
Status: On Grid
10.Sep 2018 14:55
1.
If the default information is displayed, press the
EXIT
button to open the main menu.
Otherwise, press the
EXIT
button repeatedly until the main menu is displayed.
Inverter Info.
General Settings
Install Settings
Active/Reactive Pwr
FRT
2.
Use the
and
buttons to select the
Install Settings
entry and then press
the
ENT
button.
Password 0 * * *
energy production.
Adj. would affect
Warning:
3.
This function is protected with password 5555.
Use the
and
buttons to set the individual numerals.
Press the
ENT
button to confirm a numeral.
AC Connection: 3P4W
RCMU: ON
EPO: Normal Close
Anti-islanding: ON
Max. Power: 80000W
4.
Use the buttons
and
to select the
AC connection
entry and press the
ENT
button.
AC Connection: 3P3W
RCMU: ON
EPO: Normal Close
Anti-islanding: ON
Max. Power: 80000W
5.
Use the
and
buttons to select the
3P3W
entry and then press the
ENT
button.
51
Quick installation guide for solar inverter M88H RPI883M121300 RPI883M122300 EU V1 EN 5017414200_00 2019-11-07