Date and time
E-Today: 0kWh
Power: 0W
Status: On Grid
10.Sep 2018 14:55
1.
If the default information is displayed, press the
EXIT
button to open the main menu.
Otherwise, press the
EXIT
button repeatedly until the main menu is displayed.
Inverter Info.
General Settings
Install Settings
Active/Reactive Pwr
FRT
2.
Use the
and
buttons to select the
Geneneral Settings
entry and then
press the
ENT
button.
Protocol
Baud rate
Date & Time
Language
3.
Press the
and
buttons to select the entry
Date and time
and press the
ENT
button.
10.Sep 2018 14:55
4.
Use the
and
buttons to configure the value and then press the
ENT
button.
Repeat the procedure for the other settings.
Inverter ID
If multiple inverters are connected to the PV system then a different inverter ID must be set for each inverter. For
example, the inverter ID is used by monitoring systems to uniquely identify each inverter.
E-Today: 0kWh
Power: 0W
Status: On Grid
10.Sep 2018 14:55
1.
If the default information is displayed, press the
EXIT
button to open the main menu.
Otherwise, press the
EXIT
button repeatedly until the main menu is displayed.
Inverter Info.
General Settings
Install Settings
Active/Reactive Pwr
FRT
2.
Use the
and
buttons to select the
Install Settings
entry and then press
the
ENT
button.
Password 0 * * *
energy production.
Adj. would affect
Warning:
3.
This function is protected with password 5555.
Use the
and
buttons to set the individual numerals.
Press the
ENT
button to confirm a numeral.
Grid Settings
Country
Insulation
Inverter ID: 001
4.
Use the
and
buttons to select the
Inverter ID
entry and then press the
ENT
button.
ID=001
Setting ID:
5.
Use the
and
buttons to configure the value and then press the
ENT
button.
Quick installation guide for solar inverter M88H RPI883M121300 RPI883M122300 EU V1 EN 5017414200_00 2019-11-07
50
Commissioning – Further settings (optional)