External shutdown (E-Power off, EPO)
E-Today: 0kWh
Power: 0W
Status: On Grid
10.Sep 2018 14:55
1.
If the default information is displayed, press the
EXIT
button to open the main menu.
Otherwise, press the
EXIT
button repeatedly until the main menu is displayed.
Inverter Info.
General Settings
Install Settings
Active/Reactive Pwr
FRT
2.
Use the
and
buttons to select the
Install Settings
entry and then press
the
ENT
button.
Password 0 * * *
energy production.
Adj. would affect
Warning:
3.
This function is protected with password 5555.
Use the
and
buttons to set the individual numerals.
Press the
ENT
button to confirm a numeral.
AC Connection: 3P4W
RCMU: ON
EPO: Normal Close
Anti-islanding: ON
Max. Power: 80000W
4.
Use the buttons
and
to select
EPO
entry and press the
ENT
button.
5.
Use the
and
buttons to select an option and then press the
ENT
button.
Available options
Normally open
: The relay operates as a normally open device.
Normally closed
: The relay operates as a normally closed device.
Active power limitation
Change this setting only after consultation with
Delta customer service.
To change this setting, you need a special
password that you receive from Delta customer
service. You can find the contact information on
the back of this document.
E-Today: 0kWh
Power: 0W
Status: On Grid
10.Sep 2018 14:55
1.
If the default information is displayed, press the
EXIT
button to open the main menu.
Otherwise, press the
EXIT
button repeatedly until the main menu is displayed.
Inverter Info.
General Settings
Install Settings
Active/Reactive Pwr
FRT
2.
Use the
and
buttons to select the
Installation Settings
entry and then
press the
ENT
button.
Password 0 * * *
energy production.
Adj. would affect
Warning:
3.
Enter the password provided by Delta customer service.
Use the
and
buttons to set the individual numerals.
Press the
ENT
button to confirm a numeral.
AC Connection: 3P4W
RCMU: ON
EPO: Normal Close
Anti-islanding: ON
Max. Power: 80000W
4.
Use the
and
buttons to select
Max. Power
entry and then press the
ENT
button.
5.
Use the
and
buttons to configure a value and then press the
ENT
button.
Quick installation guide for solar inverter M88H RPI883M121300 RPI883M122300 EU V1 EN 5017414200_00 2019-11-07
52