5 Planning the installation
Planning the device communication and plant monitoring
48
5.6.6 Connection of a DC1 data collector from
Delta
You can use the DC1 data collector for, among other things:
●
Commissioning the inverter (see “6. Planning the Commis-
sioning”, page 53 and “8. Commissioning”, page 101)
● Updating the firmware
●
Connecting to the MyDeltaSolar Cloud or another monitor-
ing system
Follow the instructions in the DC1 manual to connect the inverter
to the DC1.
The inverter can be connected to the DC1 via RS485, Sub-1G or
Wi-Fi.
Connection via RS485
Observe the general instructions in section “5.6.5 Connection of
a data logger via RS485”, page 47.
The DC1 does not have an integrated RS485 termination resis-
tor. For this reason, refer to the information in Fig. 5.27, p. 48.
RS485-1
3
4
120Ω
RS485-1
3
4
Termination resistor = ON
Termination resistor = OFF
Termination resistor = OFF
Termination resistor = ON
Termination resistor = ON
Termination resistor = OFF
Fig. 5.27: RS485 connection diagram for a DC1 data collector
with multiple inverters
Installation and Operation Manual for Solar Power Inverter M70A EU V2.0 EN 2020-08-03