8 Error events and troubleshooting
Warnings
8.2
Warnings
Number
Message
Possible causes
Correction suggestions
W01
Solar Low
DC input voltage is too low.
Check the DC input voltage on the inverter dis-
play.
There may be insufficient solar radiation.
W11
Int Fan Fail
Ext Fan Fail
One or more fans are blocked.
One or more fans are defective.
One or more fans are disconnected from the
power supply.
Clean or replace the fans.
Check the connections for all fans.
W16
DC Surge
Lightning has struck near the inverter.
Check the inverter status.
One or more surge protection devices are
defective.
Replace the defective surge protection devices.
One or more surge protection devices are incor-
rectly fitted.
Check all surge protection devices.
W16
AC Surge
Lightning has struck near the inverter.
Check the inverter status.
One or more surge protection devices are
defective.
Replace the defective surge protection devices.
One or more surge protection devices are incor-
rectly fitted.
Check all surge protection devices.