67
5.5.6 Group
Setting
Path: Main Page
→
Setup
→
Group Control Setting
1. Group Mode OFF
ON (Enable group function)
2. Select how many cooling units in a group, and how many cooling units for backup (less
than group number).
3. The time interval (h:m) for cooling units to shaft between operation modes (on or
standby).
4. “Over Heat Backup” means that when the cooling unit return air temperature is higher
than the alarm value, the backup unit will automatically turn on.