InfraSuite R Series – Air Cooled Type
70
Parameter
Setting Range
Description
Default Setting
Note
Rotation Time 0-999h:0-60m
Setting group
unit operating
rotation time
0h:0m
When using the
Group
Function, it is
recommended
to set to
24h:00m.
5.6.4 Setup-->Alarm Setting-->Sensor
Supply Air
Sensor 1-2
Abnormality
On/Off
When the sensor
signal is lost, the
alarm will go off
On
Return Air
Sensor 1-2
Abnormality
On/Off
When the sensor
signal is lost, the
alarm will go off
On
Discharge
Temp
Abnormality
On/Off
When the sensor
signal is lost, the
alarm will go off
On
Liquid Temp
Abnormality
On/Off
When the sensor
signal is lost, the
alarm will go off
On
Suction Temp
Abnormality
On/Off
When the sensor
signal is lost, the
alarm will go off
On
Ambient
Temp
Abnormality
On/Off
When the sensor
signal is lost, the
alarm will go off
On
Discharge P
Sensor
Abnormality
On/Off
When the sensor
signal is lost, the
alarm will go off
On
Suction P
Sensor
Abnormality
On/Off
When the sensor
signal is lost, the
alarm will go off
On
5.6.5 Setup-->Alarm Setting-->Cooling System
Fan 1-6CH
Abnormality
On/Off
When there is a
fan abnormality,
the alarm will go
off
On
Summary of Contents for InfraSuite RDA037
Page 11: ...11 Unit inch Figure 2 4 Outdoor Unit Appearance and Dimensions...
Page 63: ...63 5 5 2 Data History Path Main Page Measurement Data History...
Page 64: ...InfraSuite R Series Air Cooled Type 64 5 5 3 Warning Path Main Page Maintenance Warning...
Page 65: ...65 5 5 4 Historical Event Path Main Page Maintenance Historical Event...
Page 88: ......
Page 89: ......
Page 90: ......
Page 92: ...5013295900...