InfraSuite R Series – Air Cooled Type
52
Electronic connection
The rated value of the input power conforms to that marked on the nameplate.
The equipment has been properly grounded.
All electronic connections are tight and stable.
The remote temperature (humidity) sensors have been correctly connected
and located properly.
Mechanical connection
The discharge pipe and the liquid pipe are free of rupture or damage.
The condensed water drain pipe has been correctly connected and insulated,
and led to the draining site.
The schrader valve and the shutoff valve are free of rupture or damage.
The shutoff valves connecting the indoor and the outdoor units are all open.
4.2 Power
On
Power on the cooling unit and it will automatically enter standby mode. For the sake of safety,
the fans will not automatically rotate. After the system is connected to the power feed,
screens to be read appear on the touch screen monitor; the status page automatically
displays.
(Figure 4-1: Main Page)