Object
Mapping
R/W
AV512
CO2CalibrationValue
Sensor reading in ppm.
When in manual calibration mode (AV511=1), use a
manual command to change the AV512 present value.
The CO2 reading follows this reference value within
seconds.
Calibration value change can only be done when the
AV512 object is in manual mode. A value change via GCL
will not update sensor value. This object is auto-created
in the database if the model name includes the CO2
sensor option.
See the information in the
section.
R/W
AV517
AV517 Sticky Arrow value. Shows which arrow is on. Write
0 to turn off sticky arrow.
R/W
AV518
AV518 Slider Mode – Controls whether the slider is under
advanced (GCL) control (0) or simple control (1=lower
LCD line or 2=Main LCD line). See the GCL Programming
section for more information.
W
AV519
Min slider value – minimum range for slider when using
simple control, (AV518=1)
W
AV520
Max slider value – maximum range for slider when using
simple control. (AV518=1)
W
AV521
Slider increment amount – amount of
increment/decrement for one press of +/- when using
simple control (AV518=1)
W
AV522
Current slider value – Current value being controlled.
Changes as the slider is pressed when using simple
control (AV518=1).
R/W