D V P - E S 3 S e r i e s O p e r a t i o n Ma n u a l
5 - 2 8
_5
5.3.3
DVP06XA-E2 Control Registers
CR#
Attrib.
Register name
Explanation
0
O
R
Model name
Set up by the system:
DVP06XA-E2 model code = H’00C4
1
O
R
Firmware version
Display the current firmware version in hex.
2
O
R/W CH1 Input mode setting
Input mode: Default = H’0000. Take CH1 for example:
Mode 0 (H’0000):Voltage input (±10V)
Mode 1 (H’0001):Voltage input (±5V)
Mode 2 (H’0002):Voltage input (0 ~+10V)
Mode 3 (H’0003):Voltage input (0 ~+5V)
Mode 4 (H’0004):Current input (±20mA)
Mode 5 (H’0005):Current input (0 ~+20mA)
Mode 6 (H’0006):Current input (4 ~+20mA)
Mode -1 (H’FFFF):Channel 1 unavailable
3
O
R/W CH2 Input mode setting
4
O
R/W CH3 Input mode setting
5
O
R/W CH4 Input mode setting
6
O
R/W CH5 output mode setting
Output mode: Default = H’0000. Take CH5 for example:
Mode 0 (H’0000):Voltage output (±10V)
Mode 1 (H’0001):Current output (0~+20mA)
Mode 2 (H’0002):Current output (4~+20mA)
Mode -1 (H’FFFF):Channel 5 unavailable
7
O
R/W CH6 output mode setting
8
O
R/W CH1 average times
Average times setting of CH1 ~ CH4:
Range = K1 ~ K100
Default = K10
9
O
R/W CH2 average times
10
O
R/W CH3 average times
11
O
R/W CH4 average times
12
X
R
CH1 average input value
Average value of input signals at CH1 ~ CH4
13
X
R
CH2 average input value
14
X
R
CH3 average input value
15
X
R
CH4 average input value
16
X
R/W CH5 output signal value
Voltage output range: K-32,000~K32,000. Current output range:
K0~K32,000.
Default: K0.
17
X
R/W CH6 output signal value
20
X
R
CH1 present input value
Present value of input signals at CH1 ~ CH4
21
X
R
CH2 present input value
22
X
R
CH3 present input value
23
X
R
CH4 present input value
28
O
R/W Adjusted Offset value of CH1
Set the adjusted Offset value of CH1 ~ CH6 Default = K0.
Definition of Offset in DVP06XA -E2:
The corresponding voltage (current) input value when the digital
output value = 0
29
O
R/W Adjusted Offset value of CH2
30
O
R/W Adjusted Offset value of CH3
31
O
R/W Adjusted Offset value of CH4
32
O
R/W Adjusted Offset value of CH5
33
O
R/W Adjusted Offset value of CH6
34
O
R/W Adjusted Gain value of CH1
Set the adjusted Gain value in CH1 ~ CH6
Default = K16,000. Definition of Gain in DVP06XA-E2: The
corresponding voltage (current) input value when the digital output
value = 16,000.
35
O
R/W Adjusted Gain value of CH2
36
O
R/W Adjusted Gain value of CH3
37
O
R/W Adjusted Gain value of CH4
38
O
R/W Adjusted Gain value of CH5
39
O
R/W Adjusted Gain value of CH6