- 8 -

 

Output Limits

!

 Function

!

The output is limited between the maximum and minimum percentages. 

 How to Operate

 

Set up relevant parameters using the table below. 

CH 

CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8 

Max. 

output 

(%)  1980H 1981H 1982H 1983H 1984H 1985H 1986H 1987H 

Min. output (%) 

1988H 

1989H 

198AH 

198BH 

198CH 

198DH 

198EH 

198FH 

Note: When the output volume is limited at 20 to 80%, it means the output volume 0 to 100% calculated by the controller is corresponding 
to the actual output 20 to 80%. 

 

Programmable Control Time Unit

!

 Function

!

The unit of programmable control time can be “minute” or “second”. 

 How to Operate

!

Write 0 to the address to set the time unit to “minute” (default) or write 1 to set it to “second”. 

CH 

CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8 

Address for time unit 

1978H 

1979H 

197AH 

197BH 

197CH 

197DH 

197EH 

197FH 

 

Input Filter

!

 Function

!

To avoid unstable PV display due to interferences, DTE10T offers the filter function. Instead of averaging the values, the filter function here 
calculate the weighted average value of the “current PV” and “previous PV”. 

The filter equation: PV (displayed value) = [previous PV x (filter times – 1) + current PV] / filter times 

The bigger the filter times, the bigger the weight of the previous PV, and the smoother the temperature display, which is a good way to 
suppress interferences. 

 How to Operate

!

Set up relevant parameters using the table below. 

Parameter Address  Default 

value 

Range 

Filter times 

10F7H 

0 ~ 50 

Filter range 

10F9H 

1.0 

0.1 ~ 10.0 

 

Hot Runner Control

!

 Function

!

The hot runner control includes 3 steps: 
1.  Heating up by constant output volume 
2.  Timed PID control (Soak) 
3.  Slope heating to the target temperature (SV) 

 

 How to Operate

!

1.  Enable the hot runner control function: Write 1234H into the address 47F1H and then 0060H into address 4824H. 

bits in 4824H 

Bit7 

Bit6 

Bit5 

Bit4 Bit3 Bit2 Bit1 Bit0 

Flag -- 

Hot runner 

control 

Slope control

-- 

Latch 

CT 

EVENT 

-- 

Notes: 

 The flag to enable hot runner control is at bit6 of 4824H (and bit5 as to be enabled at the same time). Write 0060H to set both bits on. 

Call 1(800)985-6929 for Sales

deltaacdrives.com

[email protected]

Call 1(800)985-6929 for Sales

deltaacdrives.com

[email protected]

Summary of Contents for DTE10T Series

Page 1: ...the main unit 5 Make sure to use compensation wire which matches the thermocouple or platinum resistance when extending or connecting the thermocouple or platinum resistance 6 Keep the wire as short a...

Page 2: ...only applicable in the model with linear voltage and current output for OUT1 OUT2 Alarm modes 13 alarm modes available Communication RS 485 digital communication supports baudrate 2 400 to 115 200bps...

Page 3: ...hannels of input Every channel corresponds to 2 groups of output and 2 groups of alarms OUT1 and SUB1 are for control output and OUT1 can be used for proportional output OUT2 and SUB2 are fixed for al...

Page 4: ...larm output will be enabled when the PV is between SV AL H and SV AL L ON OFF AL L SV AL H 5 Alarm output will be enabled when the temperature reaches the absolute value of the upper and lower limits...

Page 5: ...ed Slot INA offers 4 channels of input and CH1 CH4 correspond to the current detected at CT1 CT4 Hardware requirement Accessory DTE2CT inserted in the slot AUX How to Operate 1 Enable the CT function...

Page 6: ...Bit0 Flag Hot runner control Slope control Latch CT EVENT Notes The flag to enable EVENT is at bit1 of 4824H Write 0002H to bit1 to set it on If the multistate function is enabled for example writing...

Page 7: ...ID latch function Write 1234H into the address 47F1H and then 0008H into address 4824H bits in 4824H Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0 Flag Hot runner control Slope control Latch CT EVENT Notes...

Page 8: ...the weighted average value of the current PV and previous PV The filter equation PV displayed value previous PV x filter times 1 current PV filter times The bigger the filter times the bigger the weig...

Page 9: ...006 H1700 H1007 H1800 Set temperature value Unit 0 1 H1008 H1101 H1009 H1201 H100A H1301 H100B H1401 H100C H1501 H100D H1601 H100E H1701 H100F H1801 Max temperature value Disabled when higher than def...

Page 10: ...B8 H1117 H10B9 H1217 H10BA H1317 H10BB H1417 H10BC H1517 H10BD H1617 H10BE H1717 H10BF H1817 Alarm 1 output mode See Alarm Output section H10C0 H1118 H10C1 H1218 H10C2 H1318 H10C3 H1418 H10C4 H1518 H1...

Page 11: ...of the current pattern 0 7 H1120 H1220 H1320 H1420 H1520 H1620 H1720 H1820 Read the NO of the current step 0 7 H1121 H1221 H1321 H1421 H1521 H1621 H1721 H1821 NO of start pattern 0 7 H1122 H1222 H132...

Page 12: ...content e g H01 H03 H10 H00 H00 H02 H16 Obtain 2 scomplement H EA RTU Mode Read Command Read Response Message Write Command Write Response Message Machine address H01 Machine address H01 Machine addre...

Page 13: ...l Size Connect maximum 7 DTC2000 or DTC2001 controllers to DTE by using DIN rail Call 1 800 985 6929 for Sales deltaacdrives com sales deltaacdrives com Call 1 800 985 6929 for Sales deltaacdrives com...

Reviews: