 Communication Parameter Setting 

Content 

Baudrate 2,400bps 

4,800bps 

9,600bps 

19,200bps 38,400bps 57,600bps 115,200bps

Parity bit 

None (N) 

Even (E) 

Odd (O) 

 

 

 

 

Table 4

 

 Error Codes 

The error codes can be read from address H1000 ~ H1007. When the input operation is in normal status, H1000 ~ H1007 are for input values. 
When input error occurs (except for stable status and input exceeding the range), DTE will read error codes in H8001 ~ H8002. 

 

H1000 Error 

description 

H8001 

EEPROM cannot be written in. 

H8002 

Input sensor is not connected. 

H8003 

Group INB is not connected. 

Table 5

 

Analog output current tuning scale: 

1

μ

A/scale 

Analog output voltage tuning scale:

 1mV/scale

 

Returning to Default Value: 

Write H1234 into address H10F1 and H1357 into address H10F2. Restart DTE. 

 Programmable Communication Parameter Setting 

 

 

INA 

INB 

Content 

Explanation 

CH1 

CH2 

CH3 

CH4 

CH5 

CH6 

CH7 

CH8 

Read remaining time of the step 

Unit: sec 

H111E

H121E

H131E

H141E

H151E 

H161E 

H171E

H181E

Read remaining time of the step 

Unit: min 

H111F

H121F

H131F

H141F

H151F 

H161F 

H171F

H181F

Read the NO. of the current 
pattern 

0 ~ 7 

H1120

H1220

H1320

H1420

H1520 

H1620 

H1720

H1820

Read the NO. of the current step  0 ~ 7 

H1121

H1221

H1321

H1421

H1521 

H1621 

H1721

H1821

NO. of start pattern 

0 ~ 7 

H1122

H1222

H1322

H1422

H1522 

H1622 

H1722

H1822

NO. of start step 

0 ~ 7 

H1123

H1223

H1323

H1423

H1523 

H1623 

H1723

H1823

 Programmable Parameter Setting 

Content 

Explanation 

Pattern 0 Pattern 1 Pattern 2 Pattern 3 Pattern 4  Pattern 5  Pattern 6 Pattern 7

Max. number of 
steps in the pattern 

0 ~ 7 = N: The pattern 
executes from step 0 to 
N. 

H2068

H2069

H206A

H206B

H206C H206D H206E

H206F

Number of cycles of 
pattern 0 ~ 7 
execution 

0 ~ 199: The pattern has 
been executed for 1 ~ 
200 times 

H2070

H2071

H2072

H2073

H2074

H2075 H2076

H2077

NO. of current link 
pattern 

0 ~ 8: 8 refers to end of 
program; 0 ~ 7 refer to 
the NO. of next pattern 

H2078

H2079

H207A

H207B

H207C H207D H207E

H207F

 

Address 

Default 

Content 

Explanation 

2000H ~ 203FH 

Target temperatures for pattern 0 ~ 7 
Pattern 0: 2000H ~ 2007H 

Unit: 0.1°C 

2080H ~ 20BFH 

Execution time for pattern 0 ~ 7 
Pattern 0: 2080H ~ 2087H 

Time: 0 ~ 900 (Unit: 1 min) 

4.  Communication format: H03 = read bit data; H06 = write bit data 

 

 

Call 1(800)985-6929 for Sales

deltaacdrives.com

[email protected]

Call 1(800)985-6929 for Sales

deltaacdrives.com

[email protected]

Summary of Contents for DTE10T Series

Page 1: ...the main unit 5 Make sure to use compensation wire which matches the thermocouple or platinum resistance when extending or connecting the thermocouple or platinum resistance 6 Keep the wire as short a...

Page 2: ...only applicable in the model with linear voltage and current output for OUT1 OUT2 Alarm modes 13 alarm modes available Communication RS 485 digital communication supports baudrate 2 400 to 115 200bps...

Page 3: ...hannels of input Every channel corresponds to 2 groups of output and 2 groups of alarms OUT1 and SUB1 are for control output and OUT1 can be used for proportional output OUT2 and SUB2 are fixed for al...

Page 4: ...larm output will be enabled when the PV is between SV AL H and SV AL L ON OFF AL L SV AL H 5 Alarm output will be enabled when the temperature reaches the absolute value of the upper and lower limits...

Page 5: ...ed Slot INA offers 4 channels of input and CH1 CH4 correspond to the current detected at CT1 CT4 Hardware requirement Accessory DTE2CT inserted in the slot AUX How to Operate 1 Enable the CT function...

Page 6: ...Bit0 Flag Hot runner control Slope control Latch CT EVENT Notes The flag to enable EVENT is at bit1 of 4824H Write 0002H to bit1 to set it on If the multistate function is enabled for example writing...

Page 7: ...ID latch function Write 1234H into the address 47F1H and then 0008H into address 4824H bits in 4824H Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0 Flag Hot runner control Slope control Latch CT EVENT Notes...

Page 8: ...the weighted average value of the current PV and previous PV The filter equation PV displayed value previous PV x filter times 1 current PV filter times The bigger the filter times the bigger the weig...

Page 9: ...006 H1700 H1007 H1800 Set temperature value Unit 0 1 H1008 H1101 H1009 H1201 H100A H1301 H100B H1401 H100C H1501 H100D H1601 H100E H1701 H100F H1801 Max temperature value Disabled when higher than def...

Page 10: ...B8 H1117 H10B9 H1217 H10BA H1317 H10BB H1417 H10BC H1517 H10BD H1617 H10BE H1717 H10BF H1817 Alarm 1 output mode See Alarm Output section H10C0 H1118 H10C1 H1218 H10C2 H1318 H10C3 H1418 H10C4 H1518 H1...

Page 11: ...of the current pattern 0 7 H1120 H1220 H1320 H1420 H1520 H1620 H1720 H1820 Read the NO of the current step 0 7 H1121 H1221 H1321 H1421 H1521 H1621 H1721 H1821 NO of start pattern 0 7 H1122 H1222 H132...

Page 12: ...content e g H01 H03 H10 H00 H00 H02 H16 Obtain 2 scomplement H EA RTU Mode Read Command Read Response Message Write Command Write Response Message Machine address H01 Machine address H01 Machine addre...

Page 13: ...l Size Connect maximum 7 DTC2000 or DTC2001 controllers to DTE by using DIN rail Call 1 800 985 6929 for Sales deltaacdrives com sales deltaacdrives com Call 1 800 985 6929 for Sales deltaacdrives com...

Reviews: