- 7 -
How to Operate
1. Enable the slope function: Write 1234H into the address 47F1H and then 0020H into address 4824H.
bits in 4824H
Bit7
Bit6
Bit5
Bit4 Bit3 Bit2 Bit1 Bit0
Flag --
Hot runner
control
Slope control
--
Latch
CT
EVENT
--
Notes:
The flag to enable slope function is at bit5 of 4824H. Write 0020H to bit5 to set it on.
If the “multistate” function is enabled, for example, writing 0022H means enabling bit5 and bit1 at the same time.
If there is already a set value in 4824H and you would like to modify it, reset it to 0 before you set up a new value.
2. Set up relevant parameters using the table below.
CH
CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8
Set value (SV)
1008H
1009H
100AH
100BH
100CH
100DH
100EH
100FH
Slope
(unit:
0.1°) 1970H 1971H 1972H 1973H 1974H 1975H 1976H 1977H
Note: To stabilize the control, first execute auto-tuning when the slope function is selected. When auto-tuning is being executed, the slope
control will stop.
Programmable PID Latch Function
!
Function
DTE10T offers programmable PID latch function. When the power is off and on again, the status before the power is cut off can be retained.
How to Operate
1. Enable the programmable PID latch function: Write 1234H into the address 47F1H and then 0008H into address 4824H.
bits in 4824H
Bit7
Bit6
Bit5
Bit4 Bit3 Bit2 Bit1 Bit0
Flag --
Hot runner
control
Slope control
--
Latch
CT
EVENT
--
Notes:
The flag to enable PID latch is at bit3 of 4824H. Write 0008H to bit3 to set it on.
If the “multistate” function is enabled, for example, writing in 0028H means enabling bit5 and bit3 at the same time.
If there is already a set value in 4824H and you would like to modify it, reset it to 0 before you set up a new value.
Opposite Output
!
Function
!
The 8 channels on DTE10T can be set to opposite output, that is, when the output is set to 0, the actual output will be 1.
How to Operate
!
To set CH1 and CH3 to opposite output, first write 1234H into the address 47F1H and then 0005H into address 4821H to set on CH1 (bit0)
and CH3 (bit2).
CH8
CH7
CH6
CH5
CH4
CH3
CH2
CH1
Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0
Delayed Alarm
!
Function
!
When the set condition for alarms is met, the alarm will be enabled after a pre-set period of time.
How to Operate
!
Set up the time using the table below. Unit: second
CH
CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8
Address for
delayed alarm
1990H 1991H 1992H 1993H 1994H 1995H 1996H 1997H