- 3 -
Input
The standard DTE main unit is attached with 4 channels of inputs. You can purchase additional DTE20T or DTE20P to expand the number of
input channels. DTE supports maximum 8 channels of inputs which belong to group INA and group INB. Each group possesses 4 input
channels.
DTE series supports the following input sensors:
Input Sensor Type
Register Value
Range
For DTE10P / DTE20P
Temperature measurement resistance (Cu50)
13
-50 ~ 150°C
Platinum resistance (Pt100)
12
-200 ~ 600°C
Platinum resistance (JPt100)
11
-20 ~ 400°C
For DTE10T / DTE20T
Thermocouple TXK type
10
-200 ~ 800°C
Thermocouple U type
9
-200 ~ 500°C
Thermocouple L type
8
-200 ~ 850°C
Thermocouple B type
7
100 ~ 1,800°C
Thermocouple S type
6
0 ~ 1,700°C
Thermocouple R type
5
0 ~ 1,700°C
Thermocouple N type
4
-200 ~ 1,300°C
Thermocouple E type
3
0 ~ 600°C
Thermocouple T type
2
-200 ~ 400°C
Thermocouple J type
1
-100 ~ 1,200°C
Thermocouple K type
0
-200 ~ 1,300°C
Note: The default setting in DTE10T is “thermocouple K type”. The default setting in DTE10P is “Pt100".
Communication address: Input sensor types at H10A0 ~ H10A7; input upper limits at H1010 ~ H1017; input lower limits at H1018 ~ H101F.
Output
DTE supports maximum 16 channels of outputs, belonging to output groups OUT1, OUT2, SUB1 and SUB2, each group with 4 channels. See
the explanations below for how input channels correspond to output groups.
Without group INB (4 channels of input): Every channel corresponds to 2 groups of output and 2 groups of alarms. OUT1 and SUB1 are for
control output, and OUT1 can be used for proportional output. OUT2 and SUB2 are fixed for alarm output.
With group INB (8 channels of input): Every channel is paired with 2 groups of outputs. OUT1 and OUT2 are used for control output or
proportional output of CH1 ~ CH8. SUB1 and SUB2 are used for control output or alarm output.
See Table 1 for the relations between input and output.
4 channels of input
8 channels of input
Output Group
INA (CH1 ~ CH4)
INA (CH1 ~ CH4)
INB (CH5 ~ CH8)
OUT1
Main control output or
proportional output
Main control output or
proportional output
No corresponding output
OUT2
Alarm 1 output
No corresponding output
Main control output or
proportional output
SUB1
Control output
Control output or alarm output
No corresponding output
SUB2
Alarm 2 output
No corresponding output
Control output or alarm output
Table 1
Note:
SUB1 and SUB2 do not support DTE20L and DTE20C. Please install the optional output modules you purchase into the correct slot.
Communication Address of Output & How to Set up Parameters
See Table 2 for the communication addresses of output and Table 3 for the definition of the value in the address.
INA
INB
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
OUT1, OUT2
H10A8
H10A9
H10AA
H10AB
H10AC
H10AD
H10AE
H10AF
SUB1, SUB2
H10B0
H10B1
H10B2
H10B3
H10B4
H10B5
H10B6
H10B7
Table 2