Multi-functional Power Meter DPM-C510 Operation Manual
5-2
_5
5.1
Overview of Parameters
Modbus
Address
Item
Range
Data
Type
Unit
Data
Size
(byte)
Read (R) /
Write (W)
Hex
Modicom
Format
0. System Parameters: 0001 – 00FF
5
40006 Meter Constant
3200
uint P/kWh
2
R
6
40007 Meter Model
0: None
4: DMP–C510
word
2
R
7
40008 Total running time of the
meter
0 ~ 4294967295
uint Minute
4
R
8
40009
9
40010 Firmware version
0.00 ~ 9.99
word
2
R
A
40011
Firmware release date
Year: 00–99
Month: 1–12
byte
Year,
Month
2
R
B
40012
Date: 1–31
word Date
2
R
C
40013
Reserved
D
40014
Power system
configuration
0: 3φ4W
1: 3φ3W
2:
1φ2W
3:
1φ3W
word
2
R/W
E
40015 Primary CT (A)
1 – 9999
uint
A
2
R/W
F
40016 Secondary CT (A)
0: 1A
1: 5A
word
A
2
R/W
10
40017 Primary PT
1 ~ 65534
uint
V
2
R / W
11
40018 Secondary PT
1 ~ 9999
uint
V
2
R / W
13
40020
Reserved
14
40021
Backlight delay
*For model C501L, this
function is only
supported by firmware
V1.006 and above.
0 – 99
0: Backlight remains OFF.
99: Backlight remains ON.
word Second 2
R/W
15
40022
Reserved
Summary of Contents for DPM-C510
Page 3: ......
Page 9: ...Multi functional Power Meter DPM C510 Operation Manual 1 4 _1 _1 MEMO...
Page 28: ...Chapter 4 Operation 4 7 4_ MEMO...
Page 37: ...6 1 Chapter 6 Error Codes Table of Contents 6 1 Error Codes 6 2 6...