Chapter 5 Parameters and Functions
5-3
_5
16
40023 Baud Rate
0: 9600
1: 19200
2: 38400
word bps
2
R/W
17
40024 Communication mode 1: RTU
word
2
R/W
18
40025 Data bit
0: 8
word
bit
2
R/W
19
40026 Parity bit
0: None
1: Even
2: Odd
word
2
R/W
1A
40027 Stop bit
0: 1
word
bit
2
R/W
1B
40028 Modbus address
0 – 254
word
2
R/W
1C
40029 Reset
0: None
word
2
W
1: Reset to factory default
2: Reset energy value
1. Meter Parameters: 0100 – 01FF
100
40257
Phase A voltage
0.000 – 99999.999
float
V
4
R
101
40258
102
40259
Phase B voltage
0.000 – 99999.999
float
V
4
R
103
40260
104
40261
Phase C voltage
0.000 – 99999.999
float
V
4
R
105
40262
106
40263
Average phase voltage 0.000 – 99999.999
float
V
4
R
107
40264
108
40265
A–B line voltage
0.000 – 99999.999
float
V
4
R
109
40266
10A
40267
B–C line voltage
0.000 – 99999.999
float
V
4
R
10B
40268
10C
40269
C–A line voltage
0.000 – 99999.999
float
V
4
R
10D
40270
10E
40271
Average line voltage
0.000 – 99999.999
float
V
4
R
10F
40272
120
40289 Phase A current
0.000 – 99999.999
float
A
4
R
Summary of Contents for DPM-C510
Page 3: ......
Page 9: ...Multi functional Power Meter DPM C510 Operation Manual 1 4 _1 _1 MEMO...
Page 28: ...Chapter 4 Operation 4 7 4_ MEMO...
Page 37: ...6 1 Chapter 6 Error Codes Table of Contents 6 1 Error Codes 6 2 6...