5 - 2 8
Modulon DPH Series
1. The protective device’s rated current must comply with the current values shown in
7DEOH
.
7KHVSHFL¿FDWLRQVRIWKHSURWHFWLYHGHYLFH¶VVKRUWFLUFXLWSURWHFWLRQLHWKHWULSSLQJ
current of the fast-acting DC circuit breaker or/ and the melting current of the fast-
acting DC fuse) must be 3 ~ 6 times the values shown in
7DEOH
. Besides, the
response time of the protective device must be less than 20ms.
3. For the choice of the fast-acting DC fuse mentioned above, the A50QS series from
the supplier
)HUUD]6KDZPXW
is suggested. Please contact Delta customer service
for relevant information.
4. The maximum tripping current of the fast-acting DC circuit breaker or/ and the
maximum melting current of the fast-acting DC fuse mentioned above are 3 ~ 8
times the values shown in
7DEOH
. These maximum values are suggested for
general applications only. For actual maximum values, the maximum short-circuit
capacity of the on-site batteries must be taken into consideration. Please contact
Delta customer service for relevant information.
y
The external battery cabinet’s protective device installation methods are as follows.
Option 1: Installation of a 4-pole DC circuit breaker or DC isolated switch (per pole
YROWDJH9GFFRQQHFWHGLQVHULHVZLWKD'&IXVHYROWDJH9GF
-
N
+
-
N
+
UPS
External
Battery
Cabinet
DC Fuse
4-Pole DC Circuit Breaker
or DC Isolated Switch
)LJXUH,QVWDOODWLRQRID3ROH'&&LUFXLW%UHDNHURU
'&,VRODWHG6ZLWFK&RQQHFWHGLQ6HULHVZLWKD'&)XVH
Summary of Contents for DPH-600K
Page 12: ......
Page 26: ......
Page 216: ......
Page 217: ...8 1 8 Optional Accessories 8 Optional Accessories...
Page 220: ......
Page 221: ...9 1 9 Maintenance Maintenance...
Page 223: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1 A1...
Page 226: ......
Page 227: ...A2 1 Appendix 2 Warranty Warranty A2 A2...
Page 229: ......
Page 230: ......
Page 232: ......