3 - 2 4
Modulon DPH Series
3.2.11 Manual Bypass Mode_ Dual Input_ Parallel Units
WARNING:
1. In Manual Bypass mode, make sure that all of the breakers (except each
UPS’s Manual Bypass Switch (Q3)) are in the
OFF
position before working on
any of the parallel UPSs’ internal circuits. This avoids electric shock.
$IWHUWKHSRZHULQVLGHHDFKRIWKHSDUDOOHO836VLVFRPSOHWHO\FXWRႇWKHUHLV
no high voltage inside all parallel UPSs and maintenance can be performed
safely. However, to avoid electric shock, please do not touch the following parts
on each parallel UPS: AC Input terminal block, Bypass Input terminal block,
UPS Output terminal block, Battery Input terminal block, grounding terminals
(see
)LJXUH
~
)LJXUH
for the location of these terminal blocks and
terminals) and any copper bars connected to the Manual Bypass Switch (Q3),
as they may carry high voltage.
3. During Manual Bypass mode, each parallel UPS’s input power is completely
FXWRႇDQGWKHFRQQHFWHGFULWLFDOORDGVDUHQRWSURWHFWHG
4. For parallel UPSs, if you want to turn off one of the parallel UPSs for
maintenance, please make sure the total connected critical loads will not
exceed the remaining parallel units’ total capacity.
In Manual Bypass mode (parallel), if one of the parallel UPSs needs maintenance, please
¿UVWFRQ¿UPWKDWWKHE\SDVV$&VRXUFHDQGHDFKSDUDOOHO836¶V676PRGXOHDUHQRUPDO
After confirmation, please follow the procedures below to manually switch each of the
parallel UPSs to Manual Bypass mode.
1
Tap each LCD’s ON/ OFF Button (
) and the '
POWER OFF?
' screen will pop up to
DVNLI\RXZDQWWRSRZHURႇWKH836¶VLQYHUWHU3OHDVHVHOHFW
'
YES
'.
2
Turn
ON
each UPS’s Manual Bypass Switch (Q3).
3
Turn
OFF
each UPS’s Bypass Switch (Q2).
4
Turn
OFF
each UPS’s Input Switch (Q1) and Output Switch (Q4).
5
Turn
OFF
each external battery cabinet’s breaker (Q5).
In Manual Bypass mode, all power inside the parallel UPSs is completely cut off and
maintenance personnel can perform maintenance safely. Power of the connected critical
loads will be supplied by manual bypass. During Manual Bypass mode (parallel), all parallel
836V¶WULFRORU/('VDQG/&'VDUHRႇ3OHDVHVHH
)LJXUH
for the path of electrical
power through the parallel UPSs in Manual Bypass mode.
Summary of Contents for DPH-600K
Page 12: ......
Page 26: ......
Page 216: ......
Page 217: ...8 1 8 Optional Accessories 8 Optional Accessories...
Page 220: ......
Page 221: ...9 1 9 Maintenance Maintenance...
Page 223: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1 A1...
Page 226: ......
Page 227: ...A2 1 Appendix 2 Warranty Warranty A2 A2...
Page 229: ......
Page 230: ......
Page 232: ......