5 - 3
5 Installation and Wiring
1. Keep a distance of 1000 mm (39.4") from the front of the UPS for maintenance and
ventilation.
2. Keep a distance of at least 350 mm (13.8") from the rear of the UPS for ventilation,
or at least 500 mm (19.7") for maintenance.
3. Keep a distance of 500 mm (19.7") from the top of the UPS for maintenance, wiring
and ventilation.
Air Outlet
Air Inlet
)LJXUH836$LU,QOHW 2XWOHW'LUHFWLRQ
y
Keep the installation area clean. Please note that wiring routes must be hermetic to pre-
vent possible damage from rodents.
y
Keep the installation area’s temperature around 25°C (77°F) and humidity within 95%.
The highest operating altitude is 1000 meters (3280 ft) above sea level.
y
For safety concerns, we suggest that you:
1. Equip surroundings of the installation area with CO
2
RUGU\SRZGHU¿UHH[WLQJXLVKHUV
,QVWDOOWKH836LQDQHQYLURQPHQWZKHUH¿UHSURRIPDWHULDOVDUHXVHGWRFRQVWUXFW
WKHZDOOVÀRRUVDQGFHLOLQJV
,QVWDOOWKH836RQDÀRRUWKDWLVPDGHRIQRQFRPEXVWLEOHPDWHULDOV
y
'RQRWDOORZXQDXWKRUL]HGSHUVRQQHOWRHQWHUWKHLQVWDOODWLRQDUHDDQGDVVLJQVSHFL¿HG
personnel to keep the UPS key.
WARNING:
Do not use air conditioners or similar equipment to blow into the rear of the
UPS and hinder ventilation.
Summary of Contents for DPH-600K
Page 12: ......
Page 26: ......
Page 216: ......
Page 217: ...8 1 8 Optional Accessories 8 Optional Accessories...
Page 220: ......
Page 221: ...9 1 9 Maintenance Maintenance...
Page 223: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1 A1...
Page 226: ......
Page 227: ...A2 1 Appendix 2 Warranty Warranty A2 A2...
Page 229: ......
Page 230: ......
Page 232: ......