AlertMaxx™

Installation & Operating Instructions 

Rev 4

For Ground Water (DMS-270) & Foul Water (DMS-269)

Pump Station High Level Alarm

T.

E.

W.

Summary of Contents for AlertMaxx

Page 1: ...01992 523523 info deltamembranes com www deltamembranes com AlertMaxx Installation Operating Instructions Rev 4 For Ground Water DMS 270 Foul Water DMS 269 Pump Station High Level Alarm T E W ...

Page 2: ...erein must neither be distributed copied reproduced edited or processed for any other purpose nor otherwise transmitted published or made available to a third party without express written consent from Delta Membranes Subject to technical modification without prior notice Delta Membranes 2016 ...

Page 3: ... unit 6 7 0 Installing a finger float into a ground or surface water chamber 7 8 0 Connecting a finger float to the AlertMaxx unit 8 9 0 Installing a pendant float into a foul water chamber 9 10 0 Connecting a pendant float to the AlertMaxx unit 10 11 0 Activating testing the AlertMaxx unit 11 11 1 Turning on the AlertMaxx unit for the first time 11 11 2 Testing the AlertMaxx unit 11 12 0 Connecti...

Page 4: ...lands 2 x Large Blanking Plugs 2 x Small Cable Glands 2 x Small Blanking Plugs 1 x 6V Battery 2 2 AlertMaxx unit contents 1 x AlertMaxx Unit 1 x Chamber Location Sticker Sheet For AlertMaxx 1 x Chamber Location Sticker Sheet For Spurs 1 x Installation Operating Instructions this document This high level alarm is designed to alert home owners when the water level in their pump chamber becomes too h...

Page 5: ...e clearly heard and is permanently accessible 5 0 Mounting the AlertMaxx unit CAUTION The AlertMaxx unit is not waterproof and must be installed indoors or inside a kiosk 1 Using the template provided on page 15 of this instruction manual figure 1 mark the fixing positions on the wall 2 Drill the two holes and fit suitable wall plugs ensure correct wall plugs are used for the wall type 3 Remove th...

Page 6: ...ough the right hand cable gland large and connect the power cable to the terminal strip see figure 2 WARNING Ensure mains power is isolated before connecting it to the AlertMaxx unit Figure 2 Connecting mains E N L BLUE BLACK BROWN BLUE PLEASE NOTE If you have a finger float move to section 7 0 If you have a pendant float move to section 9 0 120 80 Finger float Move to section 7 0 Pendant float Mo...

Page 7: ...loat must only be used for ground water applications and the pendant float must only be used for foul water applications 1 Using the nut and washers provided secure the finger float to the inside of the float housing so that the float rises with rising water levels see figure 2 2 Using the two cable ties provided attach the float housing to the discharge arm so it is 300mm from the base of the cha...

Page 8: ... cable gland into the second from right hole of the AlertMaxx unit 3 Pull the float cable through the small cable gland on the AlertMaxx unit 4 Connect the blue and a brown cable from the float switch cable to the terminal strip see figure 4 PLEASE NOTE If the cable supplied with the float switch is too short the cable can be extended using a cable with a minimum core cross sectional area of 1mm E...

Page 9: ...arm allowing the bottom of the float switch to hang approximately 200mm above the base of the chamber see figure 6 Option 2 Guide rail mounted foul pump 1 Pull the float cable through the float weight 2 Using a cable tie secure the float weight to the float cable so there is 80mm of float cable between the top of the float switch and the bottom of the float weight 3 Drill a hole through the float ...

Page 10: ...Insert a large cable gland into the second from right hole of the AlertMaxx unit 3 Pull the float cable through the large cable gland on the AlertMaxx unit 4 Connect the black and a blue cable from the float switch cable to the terminal strip see figure 7 The brown cable should be disregarded and isolated PLEASE NOTE If the cable supplied with the float switch is too short the cable can be extende...

Page 11: ...ep 4 will stop after approximately 30 60 seconds 11 2 Testing the AlertMaxx unit 1 Test the alarm by pressing and holding the TEST button for 10 15 seconds The alarm will sound and the red LED will flash every second 2 Release the TEST button The alarm and flash from the red LED will stop within 10 seconds 3 Test the float switch by raising the float switch to its upright position The alarm will a...

Page 12: ...xternal devices such as an alarm or beacon When the alarm is activated the relay sends a signal once every second The volt free relay is designed to accept devices with a maximum load of 0 5A and voltage up to 30V If external devices fall outside these parameters the external device must be powered by an external power supply You can use the AlertMaxx to power external devices with a maximum volta...

Page 13: ...n be muted by pressing the RESET button The beep will return 7 days from pressing the RESET button until a service technician resets the alarm unit The AlertMaxx unit has a factory default service interval of 12 months 14 0 Spares Part No Description DMS 194 Pendant float switch for foul water applications DMS 276 Broken finger float switch for ground and surface water applications DMS 277 Shroud ...

Page 14: ...necting mains supply to alarm unit Still doesn t turn on after 3 mins alarm unit is faulty The LEDs flash in the following order red blue green Low battery charge the battery by connecting mains supply to alarm unit The red LED is flashing and the blue LED is solid Float switch cable is faulty check float switch connections and cable for damage Float switch is broken replace float switch Float cab...

Page 15: ...AlertMaxx For technical support please call 01279 757400 15 Figure 1 Scale 1 1 Mounting hole positions Top Bottom ...

Page 16: ...e service engineers to maintain enhance replace equipment Passionate Bespoke design manufacturing installation ensuring our equipment is fit for every requirement Service From fitting to scheduled maintenance we ensure your needs come first Fully stocked vans Emergency breakdown service Out of hours service Planned maintenance Factory trained engineers Unit 12 Haslemere Ind Est Pig Lane Bishop s S...