Pr.
Explanation
Settings
Factory
Setting
NOTE
02.05
Line Start Lockout
0: Disable. Operation status is not changed
even if operation command source Pr.02.01
is changed.
1: Enable. Operation status is not changed
even if operation command source Pr.02.01
is changed.
2: Disable. Operation status will change if
operation command source Pr.02.01 is
changed.
3: Enable. Operation status will change if
operation command source Pr.02.01 is
changed.
1
02.06
Loss of ACI Signal
(4-20mA)
0: Decelerate to 0 Hz
1: Coast to stop and display “AErr”
2: Continue operation by last frequency
command
1
02.07
Up/Down Mode
0: by UP/DOWN Key
1: Based on accel/decel time
2: Constant speed (Pr.02.08)
3: Pulse input unit (Pr.02.08)
0
02.08
Accel/Decel Rate of
Change of
UP/DOWN
Operation with
Constant Speed
0.01~10.00 Hz
0.01
0: Digital keypad UP/DOWN keys or Multi-
function Inputs UP/DOWN. Last used
frequency saved.
1: 0 to +10V from AVI
2: 4 to 20mA from ACI or 0 to +10V from
AVI2
3: RS-485 (RJ-45)/USB communication
4: Digital keypad potentiometer
5: CANopen communication
0
a
02.09
Source of Second
Frequency
Command
For VFD*E*C models, the factory setting is 5
a
02.10
Combination of the
First and Second
Master Frequency
Command
0: First Master Frequency Command
1: First Master Frequency
Second Master Frequency Command
2: First Master Frequency Command -
Second Master Frequency Command
0
a
02.11
Keypad Frequency
Command
0.00 to 600.0Hz
60.00
a
02.12
Communication
Frequency
Command
0.00 to 600.0Hz
60.00
02.13
The Selections for
Saving Keypad or
Communication
Frequency
Command
0: Save Keypad & Communication
Frequency
1: Save Keypad Frequency only
2: Save Communication Frequency only
0